V6R VRF 50Hz
Part 2 - Out
door Unit Engineering Da
ta
Mini Amazon III Series
83
Table 2-7.9: KMF-140 DVN4 heating capacity (continued)
Combination (%) (Capacity
index)
Outdoor temperature
(°C DB)
Indoor temperature(°C WB)
16.00
18.00
20.00
21.00
22.00
24.00
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
°C DB
°C WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
110%
-13.7
-15
13.56
4.09
13.51
4.18
13.46
4.27
13.46
4.16
13.46
4.25
13.41
4.35
-11.8
-13
13.77
4.15
13.71
4.24
13.71
4.33
13.66
4.21
13.66
4.30
13.61
4.40
-9.8
-11
13.97
4.15
13.92
4.24
13.92
4.33
13.87
4.28
13.87
4.35
13.82
4.46
-9.5
-10
14.07
4.20
14.07
4.29
14.02
4.38
13.97
4.30
13.97
4.40
13.92
4.50
-8.5
-9.1
14.17
4.24
14.12
4.33
14.12
4.42
14.07
4.34
14.07
4.44
14.02
4.55
-7
-7.6
14.32
4.29
14.27
4.38
14.27
4.47
14.22
4.40
14.22
4.49
14.17
4.57
-5
-5.6
15.44
4.34
15.39
4.43
15.34
4.53
15.34
4.45
15.34
4.52
14.88
4.52
-3
-3.7
15.64
4.38
15.59
4.47
15.54
4.56
15.54
4.48
15.54
4.58
14.88
4.44
0
-0.7
15.95
4.48
15.90
4.57
15.90
4.66
15.85
4.52
15.85
4.62
14.88
4.38
3
2.2
17.42
4.68
17.42
4.77
17.37
4.86
16.91
4.70
16.25
4.65
14.88
4.34
5
4.1
20.32
5.11
18.95
5.10
17.63
4.75
16.91
4.62
16.25
4.54
14.88
4.32
7
6
20.32
4.92
18.95
4.80
17.63
4.51
16.91
4.39
16.25
4.33
14.88
4.21
9
7.9
20.32
4.70
18.95
4.54
17.63
4.35
16.91
4.28
16.25
4.23
14.88
4.14
11
9.8
20.32
4.53
18.95
4.38
17.63
4.23
16.91
4.13
16.25
4.10
14.88
4.00
13
11.8
20.32
4.40
18.95
4.24
17.63
4.09
16.91
4.01
16.25
3.96
14.88
3.87
15
13.7
20.32
4.27
18.95
4.10
17.63
3.96
16.91
3.87
16.25
3.82
14.88
3.73
100%
-13.7
-15
13.71
4.88
13.66
4.93
13.66
4.98
13.61
5.01
13.61
5.04
13.56
4.91
-11.8
-13
13.92
4.88
13.87
4.94
13.87
4.99
13.82
5.02
13.82
5.04
13.56
4.86
-9.8
-11
14.02
4.89
14.02
4.94
13.97
5.00
13.97
5.02
13.92
5.05
13.56
4.85
-9.5
-10
14.12
4.90
14.07
4.94
14.07
5.01
14.02
5.03
14.02
5.06
13.56
4.81
-8.5
-9.1
14.27
4.90
14.27
4.95
14.22
5.02
14.17
5.03
14.17
5.06
13.56
4.74
-7
-7.6
15.39
4.91
15.34
4.95
15.34
5.13
15.29
5.22
14.78
4.96
13.56
4.72
-5
-5.6
15.59
4.91
15.54
4.95
15.54
5.01
15.39
5.07
14.78
4.81
13.56
4.59
-3
-3.7
15.90
4.92
15.85
4.96
15.85
4.84
15.39
4.78
14.78
4.66
13.56
4.44
0
-0.7
16.30
4.93
17.22
4.96
16.00
4.71
15.39
4.56
14.78
4.43
13.56
4.24
3
2.2
17.37
4.83
17.22
4.84
16.00
4.57
15.39
4.34
14.78
4.17
13.56
4.04
5
4.1
18.44
4.75
17.22
4.60
16.00
4.36
15.39
4.14
14.78
4.00
13.56
3.86
7
6
18.44
4.69
17.22
4.36
16.00
4.08
15.39
3.92
14.78
3.84
13.56
3.69
9
7.9
18.44
4.42
17.22
4.13
16.00
3.97
15.39
3.82
14.78
3.72
13.56
3.57
11
9.8
18.44
4.14
17.22
3.88
16.00
3.83
15.39
3.67
14.78
3.59
13.56
3.42
13
11.8
18.44
3.88
17.22
3.78
16.00
3.69
15.39
3.54
14.78
3.46
13.56
3.30
15
13.7
18.44
3.69
17.22
3.62
16.00
3.55
15.39
3.41
14.78
3.34
13.56
3.17
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (comp outdoor fan motor) (kW)
Notes:
1. Shaded cells are tested under our standard condition.
2. Avoid running the outdoor unit when outdoor air temperature is below -15 degrees in heating mode.
3. The above table shows the average value of conditions may operate.
4. It is recommended to connect less than 130%.