Mini Amazon III Series
68
Table 2-7.6: KMF-80 DVN4 heating capacity (continued)
Combination (%)
(Capacity index)
Outdoor
temperature
(°C DB)
Indoor temperature(°C WB)
16.00
18.00
20.00
21.00
22.00
24.00
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
°C DB
°C WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
110%
-13.7
-15
6.10
1.82
6.08
1.86
6.06
1.90
6.06
1.86
6.06
1.89
6.03
1.94
-11.8
-13
6.19
1.85
6.17
1.89
6.17
1.93
6.15
1.88
6.15
1.92
6.13
1.96
-9.8
-11
6.29
1.85
6.26
1.89
6.26
1.93
6.24
1.91
6.24
1.94
6.22
1.99
-9.5
-10
6.33
1.87
6.33
1.91
6.31
1.95
6.29
1.92
6.29
1.96
6.26
2.01
-8.5
-9.1
6.38
1.89
6.35
1.93
6.35
1.97
6.33
1.94
6.33
1.98
6.31
2.03
-7
-7.6
6.45
1.91
6.42
1.95
6.42
1.99
6.40
1.96
6.40
2.00
6.38
2.04
-5
-5.6
6.95
1.94
6.93
1.98
6.90
2.02
6.90
1.98
6.90
2.02
6.70
2.01
-3
-3.7
7.04
1.95
7.02
1.99
6.99
2.03
6.99
2.00
6.99
2.04
6.70
1.98
0
-0.7
7.18
2.00
7.15
2.04
7.15
2.08
7.13
2.02
7.13
2.06
6.70
1.95
3
2.2
7.84
2.09
7.84
2.13
7.82
2.17
7.61
2.10
7.31
2.08
6.70
1.94
5
4.1
9.14
2.28
8.53
2.27
7.93
2.12
7.61
2.06
7.31
2.02
6.70
1.93
7
6
9.14
2.20
8.53
2.14
7.93
2.01
7.61
1.96
7.31
1.93
6.70
1.88
9
7.9
9.14
2.10
8.53
2.03
7.93
1.94
7.61
1.91
7.31
1.89
6.70
1.85
11
9.8
9.14
2.02
8.53
1.95
7.93
1.89
7.61
1.84
7.31
1.83
6.70
1.79
13
11.8
9.14
1.96
8.53
1.89
7.93
1.83
7.61
1.79
7.31
1.77
6.70
1.73
15
13.7
9.14
1.91
8.53
1.83
7.93
1.76
7.61
1.73
7.31
1.71
6.70
1.66
100%
-13.7
-15
6.17
2.18
6.15
2.20
6.15
2.22
6.13
2.23
6.13
2.25
6.10
2.19
-11.8
-13
6.26
2.18
6.24
2.20
6.24
2.23
6.22
2.24
6.22
2.25
6.10
2.17
-9.8
-11
6.31
2.18
6.31
2.21
6.29
2.23
6.29
2.24
6.26
2.25
6.10
2.16
-9.5
-10
6.35
2.18
6.33
2.21
6.33
2.23
6.31
2.24
6.31
2.26
6.10
2.15
-8.5
-9.1
6.42
2.19
6.42
2.21
6.40
2.24
6.38
2.24
6.38
2.26
6.10
2.11
-7
-7.6
6.93
2.19
6.90
2.21
6.90
2.29
6.88
2.33
6.65
2.21
6.10
2.11
-5
-5.6
7.02
2.19
6.99
2.21
6.99
2.23
6.93
2.26
6.65
2.15
6.10
2.05
-3
-3.7
7.15
2.19
7.13
2.21
7.13
2.16
6.93
2.13
6.65
2.08
6.10
1.98
0
-0.7
7.34
2.20
7.75
2.21
7.20
2.10
6.93
2.03
6.65
1.98
6.10
1.89
3
2.2
7.82
2.15
7.75
2.16
7.20
2.04
6.93
1.93
6.65
1.86
6.10
1.80
5
4.1
8.30
2.12
7.75
2.05
7.20
1.94
6.93
1.85
6.65
1.78
6.10
1.72
7
6
8.30
2.09
7.75
1.95
7.20
1.82
6.93
1.75
6.65
1.71
6.10
1.64
9
7.9
8.30
1.97
7.75
1.84
7.20
1.77
6.93
1.71
6.65
1.66
6.10
1.59
11
9.8
8.30
1.85
7.75
1.73
7.20
1.71
6.93
1.64
6.65
1.60
6.10
1.52
13
11.8
8.30
1.73
7.75
1.69
7.20
1.64
6.93
1.58
6.65
1.54
6.10
1.47
15
13.7
8.30
1.65
7.75
1.62
7.20
1.58
6.93
1.52
6.65
1.49
6.10
1.41
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (comp outdoor fan motor) (kW)
Notes:
1. Shaded cells are tested under our standard condition.
2. Avoid running the outdoor unit when outdoor air temperature is below -15 degrees in heating mode.
3. The above table shows the average value of conditions may operate.
4. It is recommended to connect less than 130%.