5.2 Cooling Capacity Tables
Table 2-5.3: KEM-30 DRS4 cooling capacity
Ambient
temp.
(°C)
Chilled water outlet temperature (°
C)
5.00
7.00
10.00
13.00
15.00
20.00
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
-10.00
-
-
-
-
30.19
7.33
31.88
7.79
32.86
8.33
35.08
8.09
-5.00
-
-
-
-
29.06
7.29
30.89
7.69
31.52
8.12
34.65
8.11
5.00
-
-
-
-
28.69
7.31
31.06
7.84
31.25
8.06
34.50
8.21
10.00
-
-
-
-
28.55
7.05
30.55
7.66
31.05
7.96
33.60
8.05
17.00
44.43
12.41
46.52
13.02
48.68
13.69
51.73
13.13
54.55
13.85
58.35
14.20
25.00
39.98
11.50
42.51
12.28
42.73
12.07
46.58
12.04
46.66
11.80
55.15
12.80
30.00
34.45
11.27
37.61
12.16
38.16
11.41
39.98
11.08
40.05
10.80
48.49
13.92
35.00
29.66
11.18
32.51
12.05
31.98
10.71
33.64
10.25
36.06
10.46
40.87
11.59
40.00
22.15
10.21
25.45
10.61
28.27
10.92
31.57
11.27
28.93
9.72
34.45
9.96
43.00
19.03
8.45
20.30
7.79
22.81
7.96
24.17
8.12
28.03
9.23
32.29
9.44
Abbreviations:
TC: Total capacity (kW)
PI: Power input (kW)
Notes:
1. Performance specifications measured with water pump operating at rated water flow rate.
Table 2-5.4: KEM-60 DRS4 cooling capacity
Ambient
temp.
(
°
C)
Chilled water outlet temperature (°
C)
5.00
7.00
10.00
13.00
15.00
20.00
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
-10.00
-
-
-
-
54.67
11.98
62.73
12.86
63.47
14.37
64.97
14.41
-5.00
-
-
-
-
53.81
12.71
57.12
13.42
59.21
13.83
63.23
13.63
5.00
-
-
-
-
53.41
12.91
57.61
13.49
60.17
13.97
62.42
13.86
10.00
-
-
-
-
52.87
12.86
56.67
13.45
59.64
14.15
59.97
13.76
17.00
82.69
22.76
84.12
24.97
90.12
26.12
93.64
27.21 100.21
28.12
110.54
28.19
25.00
73.23
22.26
75.76
23.26
80.87
24.01
86.23
24.98
89.19
25.94
98.56
26.87
30.00
64.91
19.91
66.46
20.15
69.51
21.24
68.22
22.10
77.80
23.10
91.10
25.96
35.00
59.71
22.98
61.12
23.67
63.72
20.13
65.70
21.65
67.87
22.46
80.73
23.98
40.00
47.61
22.21
49.34
23.27
53.89
23.91
57.56
25.16
59.76
25.54
65.25
26.21
43.00
43.98
20.65
45.10
21.87
47.53
23.74
50.24
24.56
59.42
25.15
63.63
26.23
Abbreviations:
TC: Total capacity (kW)
PI: Power input (kW)
Notes:
Performance specifications measured with water pump operating at rated water flow rate.
Part 2 - Engineering Da
ta
DC Inverter Chiller
27