background image

 

5.5 Water pipe installation

 

 

 

NOTE

 

 

 

■  If there is no glycol (anti-freeze) in the system there is a power 

supply  or  pump  failure,  drain  the  system  (as  shown  in  the 
figure below). 

 
 

WARNING

 

 

 

 
 

A

  <A

 

 

When water is not moving inside the system in 
cold weather, freezing is very likely and will 
damage the system.

 

 

 

5.5.1 Water quality control

 

 

1 Water quality control

 

 

When  industrial  water  is  used  as  chilled  water,  little  furring  may 
occur;  however,  well  water  or  river  water,  used  as  chilled  water, 
may cause much sediment, such as furring, sand, and so on.

 

 

Therefore, well water or river water must be filtered and softened 
in softening water equipment before flowing into chilled water 
system. If sand and clay settle in the evaporator, circulation of 
chilled water may be blocked, and thus leading to freezing 
accidents; if hardness of chilled water is too high, furring may 
occur easily, and the devices may be corroded. Therefore, the 
quality of chilled water should be analysed before being used, 
such as PH value, conductivity, concentration of chloride ion, 
concentration of sulphide ion, and so on.

 

 

2 Applicable standard of water quality for the unit

 

 
 

  

PH value

 

6

8

 

 

   

 

 

  

Total hardness

 

<50ppm

 

 

   

 

 

  

Conductivity

 

<200μV/cm

(25℃)

 

 

   

 

 

  

Sulfide ion

 

No

 

 

  

Chloride ion

 

<50ppm

 

 

   

 

 

  

Ammonia ion

 

No

 

 

   

 

 

  

Sulfate ion

 

<50ppm

 

 

   

 

 

  

Silicon

 

<30ppm

 

 

   

 

 

  

Iron content

 

<0.3ppm

 

 

  

Sodium ion

 

No requirement

 

 

   

 

 

  

Calcium ion

 

<50ppm

 

 

   

 

 

 

5.5.2 Checking the water circuit

 

 

The units are equipped with a water inlet and outlet for connection to 
a water circuit. This circuit must be provided by a licensed technician 
and must comply with local laws and regulations.

 

  

The unit is only to be used in a closed water system. 
Application in an open water circuit can lead to excessive 
corrosion of the water piping.

 

 

 

Before continuing installation of the unit, check the following:

 

 

■  The maximum water pressure can not exceed 3 bar. 

 

■  The maximum water temperature is 60°C according to safety 

device setting. 

 

■  Always use materials that are compatible with the water used in the 

system and with the materials used in the unit. 

 

■  Ensure that components installed in the field piping can withstand 

the water pressure and temperature. 

 

■  Drain taps must be provided at all low points of the system to 

permit complete drainage of the circuit during maintenance. 

■  Air vents must be provided at all high points of the system. The 

vents should be located at points that are easily accessible for 
servicing. An automatic air purge is provided inside the unit. Check 
that this air purge valve is not tightened too much so that 
automatic release of air in the water circuit remains possible. 

 

5.5.3 Checking the water volume and expansion vessel 

pre-pressure

 

 

The unit is equipped with expansion vessel that has a 
default pre-pressure of 1.5 bar.

 

 

To assure proper operation of the unit, the pre-pressure of the 
expansion vessel might need to be adjusted and the minimum 
and maximum water volume must be checked.

 

 

1.  Check that the total water volume in the installation, excluding 

the internal water volume of the unit, is at least 20L. Refer to 14 

 

Technical specifications to find the total internal water volume of 

the unit.

 

 

 

NOTE

 

 

 

■ In most applications this minimum water volume will 
be satisfactory. 

 

■ In critical processes or in rooms with a high heat load 
though, extra water might be required. 

 

■ When circulation in each space heating loop is controlled by 
remotely controlled valves, it is important that this minimum water 
volume is kept even if all the valves are closed. 

 

2.  Using the table below, determine if the expansion vessel 

pre- pressure requires adjustment. 

3.  Using the table and instructions below, determine if the total 

water volume in the installation is below the maximum allowed 
water volume. 

  

Installation

    

Water volume

 

 

 

height

 

 

5/7kW

 

58 L

 

5/7kW

 

58 L

 

 

difference

(a)

 

 

 

 

10~16kW 

88 L

 

10~16kW 

88 L

 

 

 

   

 

Actions required:

 

 

 

 

   

 

• pre-pressure must be decreased,

 

 

 

   

 

calculate according to "Calculating

 

 

≤7 m

 

No pre-pressure adjustment

 

the pre-pressure of the expansion

 

 

vessel"

 

 

 

required.

 

 

 

 

 

 

• check if the water volume is lower

 

 

 

 

 

 

 

 

   

 

than maximum allowed water

 

 

 

   

 

volume (use graph below)

 

 

 

Actions required:

 

 

 

 

 

 

• Pre-pressure must be increased,

 

 

 

 

 

 

calculate according to "Calculating

 

 

 

 

>7 m

 

 

the pre-pressure of the expansion

 

Expansion vessel of

 

the unit too

 

 

 

vessel" below.

 

 

small for the installation.

 

 

 

 

Check if the water volume is lower

 

 

 

 

than maximum allowed water

 

 

 

 

 

 

volume (use graph below)

 

 

 

 

 

 

 

 

 

 

 

 

(a) Installation height difference: height difference (m) between the 

highest point of the water circuit and the unit. If the unit is located 
at the highest point of the installation, the installation height 
should be 0 m.

 

 

Calculating pre-pressure of the expansion vessel

 

 

The pre-pressure (Pg) to be set depends on the maximum installation 
height difference (H) and is calculated as follows: 
Pg(bar)=(H(m)/10+0.3) bar

 

 

Checking the maximum allowed water volume

 

 

To determine the maximum allowed water volume in the entire circuit, 
proceed as follows:

 

1.  Determine the calculated pre-pressure (Pg) for the 

corresponding maximum water volume using the graph below. 

 

20

 

Summary of Contents for KEM-05 DVN1

Page 1: ... Series Inverter Mini Chillers KEM 05 DVN1 KEM 07 DVN1 KEM 10 DVN KEM 12 DVN KEM 12 DTN KEM 14 DTN KEM 16 DTN Original instructions Thank you very much for purchasing our product INSTALLATION OWNER S MANUAL ...

Page 2: ...gn of the water circuit are given in a separate chapter of this manual Once the selection is done and the water system is designed this manual describes the procedures for handling installing and connecting the unit This manual has been prepared to ensure adequate maintenance of the unit and it will provide help if problems occur READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANU...

Page 3: ...ectivegloves Do not touch the internal parts pump etc during and immediately after operation Touching the internal parts can cause burns To avoid injury give the internal parts time to return to normal temperature or if you must touch them be sure to wear protectivegloves Before touching electrical parts turn off all applicable power to the unit Tear apart and throw away plastic packaging bags so ...

Page 4: ...rnment for information regarding the collection systems available If electrical appliances are disposed of in landfills or dumps hazardous substance can leak into the groundwater and get into the food chain damaging your health andwell being The wiring must be performed by professional technicians in accordance with national wiring regulation and this circuit diagram An all pole disconnection devi...

Page 5: ... control box is located inside the unit at the top of the technical compartment where the various components of the refrigerant circuit are also to be found To access the electrical panel remove the front panel of the unit by undoing the screws 19 20 22 23 21 17 15 24 10 16 18 25 HP 13 LP 26 14 12 ...

Page 6: ...OUT 5 PFC inductance port 2 6 N OUT 3 DC filter board The picture is for referenceonly 7 PFC control port 8 18V port 9 IPDU communication port 10 IPM power port N 11 Compressor connection port U V W 12 IPM power port P 1 IPM Power supply P 2 IPM Power supply N 1 3 PFC output power N 4 PFC output power P 2 5 DC 380V DC fan power supply port 3 5 4 Main control board DC filter board IPM PFC module bo...

Page 7: ... control box is located inside the unit at the top of the technical components 17 Electronic expansion valve 18 DC fan power supply port 19 DC fan port 20 Remote control port 21 Force cooling switch 22 Parameter checking switch 23 Tin Tout Tb1 temperature sensor 24 Discharge temperature sensor Tp 25 1 Outlet of outdoor heat exchanger temperature sensor T3 25 2 Ambient temperature sensor T4 26 1 Lo...

Page 8: ...ure valve port 9 Factory debug port 10 Wired controller port 11 Electric expansion valve port 12 Power supply input port L 13 Power supply input port N 14 Ground wire 15 Rectifier bridge input port N 16 Rectifier bridge input port L 17 8A fuse tube 18 Solenoid valve port Reserved 19 Exhaust valve electric heater port 20 Plate heat exchanger electric heater port 21 Flow switch electric heater port ...

Page 9: ...ctance port L_1 9 PFC inductance port L_2 10 PFC input N 11 IPM input N 12 Communication port to main control board Remove the inspection panel by unscrewing the five screws The electric control box is located inside the unit at the top of the technical components 1 Use grommet A for the electrical power cable and grommet B for the other external wires The picture below shows the position of the d...

Page 10: ...tch 9 Force cooling touch switch 10 Differential pressure valve port 11 Factory debugging port 12 Wired controller port 13 AC Current transformer 14 Remote control port 15 Electronic expansion valve port 16 AC 220V power supply port 17 Solenoid valve port Reserved 18 Exhaust valve electric heater port 19 Electric heater port of Plate heat exchanger 20 Electric heater port of differential pressure ...

Page 11: ...PM input P 8 Power supply port for switching power supply 1 Power supply port L3 2 Power supply port L2 3 Power input port L1 4 Power input port N 5 Ground wire 6 Loaded power supply port for main control board 7 Power supply port for main control board 8 Power output port L1 after filtering 9 Power output port L2 after filtering 10 Power output port L3 afterfiltering 11 Ground wire 4 Filter board...

Page 12: ... as possible Do not install the unit in places often used as a work space In case of construction work e g grinding etc where a lot of dust is created the unit must be covered Do not place any objects or equipment on top of the unit top plate Do not climb sit or stand on top of the unit Be sure that sufficient precautions are taken in case of refrigerant leakage according to relevant local laws an...

Page 13: ...gh off the ground to prevent it from being buried in snow 5 2 2 Selecting a location in hot climates As the outdoor temperature is measured via the outdoor unit air thermistor make sure to install the outdoor unit in the shade or a canopy should be constructed to avoid direct sunlight so that it is not influenced by the sun s heat otherwise protection may be possible to the unit 5 3 Installation s...

Page 14: ...t The condensed water outlets on the chassis for selection display as the follow figure 5 7kW Water Outlet 10 16kW Reserve water outlet Need to knock open Reserve water outlet Water Outlet With rubber stopper CAUTION While installing the outdoor unit pay attention to the installation place and the drainage pattern If it s installed at the alpine zone the frozen condensed water will block up the wa...

Page 15: ...ts NOTE If the volume of balance tank 9 larger than 30L the buffer tank 8 is unnecessary otherwise the buffer tank 8 should be installed and the total volume of buffer tank and balance tank should larger than 30L The drain valve 6 should be installed at the lowest position of the system An independent backup heater can be selected and installed in the door which can provide additional heating sour...

Page 16: ...ply 13 mixing station field supply field control 8 buffer tank field supply FHL 1 n floor heating loop NOTE If the volume of balance tank 9 larger than 30L the buffer tank 8 is unnecessary otherwise the buffer tank 8 should be installed and the total volume of buffer tank and balance tank should larger than 30L The drain valve 6 should be installed at the lowest position of the system An independe...

Page 17: ...n 30L The drain valve 6 should be installed at the lowest position of the system An independent backup heater can be selected and installed in the door which can provide additional heating source and ensure better performance of the system when the ambient temperature is low Mixing station As the unit is mainly to provide middle temperature and high temperature water when connecting floor heating ...

Page 18: ...ain valve NOTE If the volume of balance tank 9 larger than 30L the buffer tank 8 is unnecessary otherwise the buffer tank 8 B should be installed and the total volume of buffer tank and balance tank should larger than 30L The drain valve 6 should be installed at the lowest position of the system An independent backup heater can be selected and installed in the door which can provide additional hea...

Page 19: ...passed When the temperature is not high enough the 3 way valve will open and the water from outdoor unit will flow through the boiler and be heated again NOTE If you need to connect an auxiliary boiler or other additional heating source and can control auxiliary boiler you need to customize CAUTION Be sure that the boiler and the integration of the boiler in the system is in accordance with releva...

Page 20: ... and the total volume of buffer tank and balance tank should larger than 30L The drain valve 6 should be installed at the lowest positon of the system An independent backup heater can be selected and installed in the door which can provide additional heating source and ensure better performance of the system when the ambient temperature is low Operation When heating is required either the unit or ...

Page 21: ...g An automatic air purge is provided inside the unit Check that this air purge valve is not tightened too much so that automatic release of air in the water circuit remains possible 5 5 3 Checking the water volume and expansion vessel pre pressure The unit is equipped with expansion vessel that has a default pre pressure of 1 5 bar To assure proper operation of the unit the pre pressure of the exp...

Page 22: ... The unit is only to be used in a closed water system Application in an open water circuit can lead to excessive corrosion of the water piping Never use Zn coated parts in the water circuit Excessive corrosion of these parts may occur as copper piping is used in the unit s internal water circuit When using a 3 way valve in the water circuit Preferably choose a ball type 3 way valve to guarantee fu...

Page 23: ... fouling factor 1 For different fouling factors multiply the figures in the performance tables by the coefficient given in the following table Fouling factors Evaporator m 2 C W capacity compressor power total power input correction factor input correction factor correction factor 4 4 x 10 5 0 86 x 10 4 0 96 0 99 0 99 1 72 x10 4 0 93 0 98 0 98 5 5 8 Filling with water 1 Connect the water supply to...

Page 24: ... phase advancing capacitor as it could lead to an accident 5 6 2Precautions on wiring of power supply Use a round crimp style terminal for connection to the power supply terminal board In case it cannot be used due tounavoidable reasons be sure to observe the following instructions Do not connect different gauge wires to the same power supply terminal Loose connections may cause overheating When c...

Page 25: ... controllers can t start the unit Wire controller PUMP2 terminal only provides passive switching signal Additional water pump must be controlled by the AC contactor Remote alarm 5kW 7kW 10kW 16kW The wire controller is optional Please use 3 core shielded wire to connect the wire controller and the shielding layer must be grounded When connecting wire controller host unit control panel is mainly us...

Page 26: ...all your local dealer 9 Power supply voltage Check the power supply voltage on the local supply panel The voltage must correspond to the voltage on the identification label of the unit 10 Air purge valve Make sure the air purge valve is open at least 2 turns 11 Water leak check the inside of the unit on water leakage in case there is a water leakage close the water inlet water outlet shut off valv...

Page 27: ...on Quick green blinks Venting routine running Pump runs during 10min in venting function Afterwards the installer has to adjust the targeted performance Red green blinking Abnormal situation pump functional but stopped Pump will restart by itself after the abnormal situation disappeared 1 Under voltage or Overvoltage U 160V or U 280V 2 Module overheating T inside motor too high 1 Check voltage sup...

Page 28: ...ed on the user interface check the wiring between the user interface and unit More error code and failure causes can be found in 8 2 Error codes 0 5 1 0 1 5 2 0 Flow m3 h 80 0 70 0 10kW 7 THE HOST UNIT CONTROLLERELUCIDATION 60 0 50 0 40 0 30 0 20 0 7 1 To access the control panel open the door remove the screw 1 and screw 2 lift the door 3 10 0 0 0 0 8 1 4 2 0 2 6 3 2 Flow m3 h 12kW 80 0 70 0 60 0...

Page 29: ... function icon will flicker when setting timing on The icon will be constantly light when finish setting Timing off function icon will flicker when setting timing off The icon will be constantly light when finish setting 11 Breakdown light icon When the unit is broken down or under protection this icon will flicker and will be extinguished when malfunction and protection are eliminated 12 Compress...

Page 30: ...ming on Press to confirm and switch to minute setting automatically The last 2 digits of the nixie tube will flicker and press or to adjust minute setting of timing on minimal unit of minute adjustment 15 minutes Press to confirm The first group setting is finished and will be constantly light When processing the second timing setting repeat the 1 2 operation above When the nixie confirm the power...

Page 31: ... The last 2 digits of the nixie tube will flicker and press or to adjust minute setting of timing off Press to confirm The first group setting is finished and will be constantly light When processing timing setting of group 2 repeat the 1 2 operation above When the nixie tube displays 01 and flicker press or to choose the timing off group When the nixie tube displays 02 which means setting timing ...

Page 32: ...viewed not to use the machine for long periods After deactivating the chiller Make sure the model is in the Power off model or alternatively disconnect the unit from the powersupply Make sure the remote control switch is closed if present Close the water valves Table 11 1 Query orders No Content Remark 1 Frequency Display operating frequency when the unit is in cooling mode and heating mode 2 Mode...

Page 33: ...nger temperature or the inlet temperature sensor is less than 2 the electric exchanger temperature heating will turn on until the heat exchanger temperature or the inlet temperature sensor is above 7 If the unit is likely to operate below 0 it is advisable to add antifreeze to the water system to prevent the unit from freezing the system in the event of a power cut off or failure 7 Fin heat exchan...

Page 34: ...s or where a leakage detection system is installed at least every 24 months 2 For equipment that contains fluorinated greenhouse gases in quantities of 50 tones of CO2 equivalent or more but of less than 500 tones of CO2 equipment at least every six months or where a leakage detection system is installed at least every 12 months 3 For equipment that contains fluorinated greenhouse gases in quantit...

Page 35: ... 3 11 0 13 8 16 6 6 1 7 0 8 0 3 26 3 20 3 50 3 25 3 31 3 25 3 30 2800 3000 4800 5200 5200 5600 5900 14 6 15 6 25 0 26 0 8 9 9 6 10 1 R410A R410A R410A R410A R410A R410A R410A 2500 2500 2800 2800 2800 2900 3200 1008 963 396 970 1327 400 1120 1100 435 1082 1456 435 81 91 110 121 111 122 Cooling 5 C 46 C Heating 15 27 C Cooling 10 20 C 12 C Heating mode 35 50 C 40 C Cooling Capacity kW rated Input W ...

Page 36: ... 005 0 005 0 023 0 023 Psb Power consumption Standby mode kW 0 011 0 011 0 019 0 019 PCK Power crankcase heater model kW 0 032 0 032 0 060 0 060 Qelec Daily electricity consumption kWh Qfuel Daily fuel consumption kWh Part load conditions space heating average climate A condition 7 C Pdh declared heating capacity kW 5 51 5 70 10 20 10 50 COPd declared COP 2 50 2 30 2 30 2 25 Cdh degradation coeffi...

Page 37: ...rmostatoffmode kW 0 023 0 026 0 026 Psb Power consumption Standby mode kW 0 019 0 020 0 020 PCK Power crankcase heater model kW 0 060 0 062 0 062 Qelec Daily electricity consumption kWh Qfuel Daily fuel consumption kWh Part load conditions space heating average climate A condition 7 C Pdh declared heating capacity kW 11 10 12 30 11 40 COPd declared COP 2 50 2 45 2 10 Cdh degradation coefficient 0 ...

Page 38: ...d at indoor temperature 20 C and outdoor temperature Tj Tj 7 C Pdh 5 5 kW Tj 2 C Pdh 3 6 kW Tj 7 C Pdh 2 2 kW Tj 12 C Pdh 1 1 kW Tj bivalent temperature Pdh 5 5 kW Tj operating limit Pdh 5 1 kW Forair to waterheatpumps Tj 15 C Pdh kW Bivalent temperature Tbiv 7 C Cycling interval capacity for heating Pcych kW Degradation co efficient Cdh 0 9 Power consumption in modes other than active mode off mo...

Page 39: ...d at indoor temperature 20 C and outdoor temperature Tj Tj 7 C Pdh 5 7 kW Tj 2 C Pdh 4 4 kW Tj 7 C Pdh 2 9 kW Tj 12 C Pdh 1 3 kW Tj bivalent temperature Pdh 6 3 kW Tj operating limit Pdh 5 5 kW Forair to waterheatpumps Tj 15 C Pdh kW Bivalent temperature Tbiv 4 C Cycling interval capacity for heating Pcych kW Degradation co efficient Cdh 0 9 Power consumption in modes other than active mode off mo...

Page 40: ... at indoor temperature 20 C and outdoor temperature Tj Tj 7 C Pdh 10 2 kW Tj 2 C Pdh 6 1 kW Tj 7 C Pdh 3 8 kW Tj 12 C Pdh 2 1 kW Tj bivalent temperature Pdh 10 2 kW Tj operating limit Pdh 9 5 kW Forair to waterheatpumps Tj 15 C Pdh kW Bivalent temperature Tbiv 7 C Cycling interval capacity for heating Pcych kW Degradation co efficient Cdh 0 9 Power consumption in modes other than active mode off m...

Page 41: ... at indoor temperature 20 C and outdoor temperature Tj Tj 7 C Pdh 10 5 kW Tj 2 C Pdh 6 8 kW Tj 7 C Pdh 4 4 kW Tj 12 C Pdh 2 1 kW Tj bivalent temperature Pdh 10 9 kW Tj operating limit Pdh 10 0 kW Forair to waterheatpumps Tj 15 C Pdh kW Bivalent temperature Tbiv 6 C Cycling interval capacity for heating Pcych kW Degradation co efficient Cdh 0 9 Power consumption in modes other than active mode off ...

Page 42: ... at indoor temperature 20 C and outdoor temperature Tj Tj 7 C Pdh 11 1 kW Tj 2 C Pdh 7 0 kW Tj 7 C Pdh 4 3 kW Tj 12 C Pdh 2 0 kW Tj bivalent temperature Pdh 11 1 kW Tj operating limit Pdh 10 4 kW Forair to waterheatpumps Tj 15 C Pdh kW Bivalent temperature Tbiv 7 C Cycling interval capacity for heating Pcych kW Degradation co efficient Cdh 0 9 Power consumption in modes other than active mode off ...

Page 43: ... at indoor temperature 20 C and outdoor temperature Tj Tj 7 C Pdh 12 3 kW Tj 2 C Pdh 7 6 kW Tj 7 C Pdh 4 9 kW Tj 12 C Pdh 2 4 kW Tj bivalent temperature Pdh 11 2 kW Tj operating limit Pdh 10 9 kW Forair to waterheatpumps Tj 15 C Pdh kW Bivalent temperature Tbiv 5 C Cycling interval capacity for heating Pcych kW Degradation co efficient Cdh 0 9 Power consumption in modes other than active mode off ...

Page 44: ... at indoor temperature 20 C and outdoor temperature Tj Tj 7 C Pdh 11 4 kW Tj 2 C Pdh 8 5 kW Tj 7 C Pdh 5 8 kW Tj 12 C Pdh 2 8 kW Tj bivalent temperature Pdh 12 6 kW Tj operating limit Pdh 11 5 kW Forair to waterheatpumps Tj 15 C Pdh kW Bivalent temperature Tbiv 4 C Cycling interval capacity for heating Pcych kW Degradation co efficient Cdh 0 9 Power consumption in modes other than active mode off ...

Page 45: ...MD14IU 023LW ...

Page 46: ......

Page 47: ......

Page 48: ......

Reviews: