Menu 1.1.1/2 OutdoorComp
Settings for outdoor temperature control. This menu is shown when the outdoor temperature control is
enabled. The menu consists of four submenus.
Maxtemp is the maximum allowable boiler temperature ie. cuts the curve at high end (programmable
temperature limiter). See example figure “example min./max.” below.
Setting range 30 - 95 °C
Default value 80 °C
Mintemp is the minimum allowable boiler temperature ie. cuts the curve at low end. See example figure
“example min./max.” below.
Setting range 0 - 50 °C
Default value 10 °C
Curve is the heating curve of the boiler. The curve name is the value of the curve at 0 °C. The boiler
temperature is adjusted against heating curve that indicates heating requirement at different outdoor
temperatures. See figure “example curves” below.
Setting range 22 - 60 °C
Default value 40 °C