8.
Control - Menus
Menu 1 - Info
Overview
Menu 1 - Info
Temp
(informative)
Setting
(default)
OutdoorComp (
while enabled
)
Step
(informative)
Maxtemp
AC in
(informative)
Mintemp
Menu 2 -
Service
Curve
Parallel
Menu 1.1 Temp
Currently measured boiler temperature. Informative reading.
Menu 1.1.1/1 Setting
Target temperature of the boiler. This menu is shown when the outdoor temperature control is disabled.
Settable value:
Setting range 30 - 99 °C
Default value 70 °C
The target temperature is set in the control unit. The measured value of temperature sensor, located inside
the boiler, is compared to the target value and appropriate power step is taken into use. Hysteresis of the
temperature is ± 2°. The controller has a P-range of ± 3° C and is constantly adjusting to maintain the set
temperature. If the temperature increases or decreases, it is corrected by increasing or decreasing the
power output. If the boiler temperature is on the low limit of the P-range, the sensor will send a full power
command to the electric boiler.