background image

Range test: 

To test the signal strength at the desired installation location, perform a range test. 

1.

 

Open the alarm panel menu “Sensors” 

 “Range” and press “Start”. 

2.

 

Press the Learn button of the smoke detector. 

3.

 

The sensor and the signal strength should be indicated. The higher the 

indicated number the better the reception (1 – 9). 

4.

 

Click “Stop” to end the test. 

 

Please note: 

If there is no signal at the installation location or the signal strength is below 4 or 

frequently falls below this level (signal fluctuations of 2 to 3 are normal), we 

recommend using a repeater to improve the signal. 

 
In case of an alarm: 

If the smoke concentration exceeds the limit, the smoke detector will notify the alarm 

panel and sound an alarm for ten seconds. If the smoke concentration is still too high 

after ten seconds, the smoke detector will again sound an alarm for ten seconds. This 

will continue until the smoke concentration drops to an acceptable value. 
If you press the test button during an alarm, the smoke detector is deactivated for 

ten minutes. After these ten minutes, the smoke detector emits two brief sounds and 

continues to work normally. 
If the smoke detector sounds an alarm but there are no signs of smoke or fire, it 

should still be assumed that the alarm was triggered by a fire. The building should be 

evacuated immediately. 
 
False alarm / troubleshooting: 

The smoke detector triggers, but there are no apparent reasons: 

 

The alarm of the smoke detector needs to be turned off directly at the 

smoke detector. 

o

 

Press the Learn button of the smoke detector to deactivate the alarm 

and activate the sleep mode. After ten minutes the smoke detector 

will beep 2 times and it return to the working mode. 

 

The alarm of the alarm panel and the sirens can be switched off by 

disarming the alarm panel. 

 

Look for steam, cooking fumes, etc., that come from the kitchen or 

bathroom and  may have passed the smoke detector by means of 

ventilation. Even colours and other fumes can trigger false alarms. 

 

Open fireplaces and strong tobacco smoke can also lead to false alarms. 

 

Check for possible spider web or dust contamination. If necessary, clean 

the smoke detector as described in the section "Contaminants". 

 

Perform a functional test as described in the section “Maintenance”. 

 

If there are more frequent unwanted alarms, the smoke detector must be 

repositioned – at a sufficient distance from these sources of error. 

 

Notes: 

 

The smoke detector will always sound an alarm even if the transmission 

between the smoke detector and the alarm panel is interrupted. 

 

It is not possible to network several smoke detectors so that all smoke 

detectors sound an alarm in the event of fire. The smoke detectors work 

together with the alarm system or independently. 

Summary of Contents for 2220000008

Page 1: ...1 1 User Manual FRM 100 2220000008 Smoke Detector ...

Page 2: ...ns in this manual were compiled with the greatest care However KATHREIN Digital Systems GmbH cannot entirely exclude mistakes in this manual Therefore we do not assume any legal responsibility or liability resulting from wrong information in this manual Descriptions technical illustrations and technical data are subject to change without notice according to technical progress In addition KATHREIN ...

Page 3: ...posure when operating the device in a commercial environment This product generates uses and may emit radio energy It may in addition interfere with other radio communication systems if not installed or used according to this manual Using the device in residential areas may cause disturbances to be possibly remedied at the user s expense Hereby KATHREIN Digital Systems GmbH declares that the Smoke...

Page 4: ...r close to strong electric power lines or magnetic fields as this may impair the transmission quality significantly Do not install the smoke detector directly on iron or aluminium surfaces as this may impair the wireless transmission significantly Use a non conducting material to insulate the device from the installation surface Do not install the smoke detector in moist very cold or very hot envi...

Page 5: ...uipment WEEE and therefore must not be disposed of with domestic waste Dispose of the device via your local collection point for waste electronic equipment This product contains software programs subject to the GPL free software license This product contains software that was developed by third parties and or software subject to the GNU General Public License GPL and or the GNU Lesser General Publ...

Page 6: ... In case of fire the siren s of the alarm panel will likewise sound an alarm Sensor data Dimensions without mount Ø 10 6 x 4 4 cm 4 17 x 1 73 in Weight 220 g 0 48 lbs Place of installation Only indoors walls corners Operating temperatures 10 C to 45 C 14 F to 113 F Humidity Maximum 95 non condensing Radio frequency 868 6375 MHz Detection method Optical Conforms to the following standards DIN EN 54...

Page 7: ... also recommended to equip all common rooms living rooms studies etc as well as cellars boiler rooms and corridors with smoke detectors If your building has more than one floor we recommend installing at least one smoke detector per floor The maximum coverage area is 60 m2 For larger rooms the number of smoke detectors must be increased The smoke detector should be installed centrally at the highe...

Page 8: ...rief signals and the LED begins to flash During the warm up phase of six minutes you can connect the smoke detector with your alarm panel 2 Open the web interface of the alarm panel go to the menu Sensors Add and press Start 3 Press the Learn button of the smoke detector Two brief signals are emitted 4 The alarm panel will confirm the successful addition of the smoke detector with a brief signal t...

Page 9: ...triggered by a fire The building should be evacuated immediately False alarm troubleshooting The smoke detector triggers but there are no apparent reasons The alarm of the smoke detector needs to be turned off directly at the smoke detector o Press the Learn button of the smoke detector to deactivate the alarm and activate the sleep mode After ten minutes the smoke detector will beep 2 times and i...

Page 10: ...r carefully or blow out the dust e g with a compressor The KATHREIN Digital Systems GmbH is not liable for contaminations This is considered normal wear Maintenance The function of the smoke detector should be checked regularly Learn button and if necessary cleaned To ensure proper function of the smoke detector it is recommended to check the smoke detector immediately after installation Press the...

Page 11: ..._______ __________________________________________________ __________________________________________________ __________________________________________________ __________________________________________________ __________________________________________________ __________________________________________________ __________________________________________________ ___________________________________...

Page 12: ..._______________ __________________________________________________ __________________________________________________ __________________________________________________ __________________________________________________ __________________________________________________ __________________________________________________ __________________________________________________ ___________________________...

Reviews: