background image

15

KT-PC4204 - 4-Relay and Additional Power Supply Module

KT-PC4204 Introduction

The KT-PC4204 module is an output module with four 
programmable relays. This module can be used to 
“repower” the Combus. The KT-PC4204 can also be used 
for elevator control.

NOTE: 

Do not use any power supply other than the KT-
PC4204 module to repower the Combus. If a power 
supply other than the KT-PC4204 is used, the 
Combus repower function will not operate as 
intended. 

KT-PC4204 Specifications

Current draw: 30 mA (from Combus)

40 VA 16 VAC transformer required

Maximum 7 A/h battery required

Connects to the controller via 4-wire Combus

Four programmable relay contacts rated 2 A, 30 VDC

AUX current: 1.0 A max.

Tamper contact input

Can be used to repower the Combus

Unpacking the KT-PC4204

The KT-PC4204 package should include the following 
parts/items:

One KT-PC4204 circuit board

One ground wire assembly

Five plastic standoffs

One 5 A replacement fuse

Mounting the KT-PC4204

The KT-PC4204 should be located inside a compatible 
cabinet (Kantech part no. KT-4051CAB), mounted in a dry, 
secure location. Preferably, it should be placed at a 
convenient distance from the connected devices. Perform the following steps to mount the unit:

1. Push the five plastic standoffs through the mounting holes on the back of the cabinet.
2. Secure the cabinet to the wall in the desired location. Use appropriate wall anchors when securing the cabinet to dry wall,

plaster, concrete, brick or other surfaces.

3. Press the circuit board into the plastic standoffs to secure the module to the cabinet.

NOTE: 

Wiring may take place once the unit is mounted.

Installation and Wiring

Before wiring the unit, ensure that all power (AC transformer and battery) is disconnected from the KT-315 controller. Perform 
the following steps to complete wiring:

1. Connect the four Combus wires to the KT-PC4204. Connect the red, black, yellow and green Combus wires to the RED,

BLK, YEL and GRN terminal respectively.

2. If the module is used for Combus Repower,

connect the Combus wires according to the 
diagram on the right. Note that for this option, 
Jumper J1 must also be set to “Combus Relay”.

3. Complete all output wiring.
4. Connect the external tamper switch, if used.

Summary of Contents for KT-315

Page 1: ...DN2016 1809 KT 315 Door Controller Installation Manual ...

Page 2: ...nstallation environment for the products damage caused by use of the products for purposes other than those for which it was designed damage from improper maintenance and damage arising out of any other abuse mishandling or improper application of the products Items Not Covered by Warranty In addition to the items which void the Warranty the following items shall not be covered by Warranty i freig...

Page 3: ...f it is found that it does not provide the protection expected Access by Intruders Intruders may enter through an unprotected access point circumvent a sensing device evade detection by moving through an area of insufficient coverage disconnect a warning device or interfere with or prevent the proper operation of the system Power Failure Control units readers exit detectors and many other security...

Page 4: ...ces 7 Hooking Up Inputs 8 Readers and Keypads 8 Relay Controlled Outputs 9 Auxiliary Outputs 9 Tamper Protection 9 Connecting the KT 315 9 Connecting to the RS 485 Bus 9 Connecting the Master Controller to the Host PC 10 Powering the KT 315 11 Installing Combus Modules 11 Introduction to Combus Modules 11 Combus Specifications 12 Combus Repower If Required 12 Module Housing Cabinet 13 KT PC4108 In...

Page 5: ...LCD Kantech LCD Time Date Display Module 18 KT3 LCD Introduction 18 KT3 LCD Specifications 18 Unpacking the KT3 LCD 18 Mounting the KT3 LCD 18 Wiring the KT3 LCD 18 Applying Power 18 Assigning the KT3 LCD Keypad 18 Troubleshooting Communication Problems 19 Default Initialization 19 How to Use the Default Initialization Hard Reset 19 VITAL LED status indications 19 Visual Status Indicators LEDs 20 ...

Page 6: ...uilding structure before operation Internal wiring must be routed in a manner that prevents Excessive strain on wire and on terminal connections Loosening of terminal connections Damage of conductor insulation The power supply must Be permanently connected fail safe with double or reinforced insulation between primary and secondary circuits In EU countries it must meet the applicable requirements ...

Page 7: ...Direct 562 3210 9662 Colombia Bogota Direct 57 1344 1422 Colombia Cali Direct 57 2891 2476 Colombia Medellin Direct 57 4204 0519 Costa Rica National Direct 506 4000 1655 Dominican Republic Santo Domingo Direct 1829 235 3047 El Salvador San Salvador Direct 503 2136 8703 Guatemala Guatemala City Direct 502 2268 1206 Mexico Mexico City Direct 5255 8526 1801 Panama Panama City Direct 507 836 6265 Peru...

Page 8: ...ery housing cabinet for the KT 315 Do not use the SmartLink option Use the Kantech IP Link Enhanced Ethernet Device Use the KT3 LCD module on each KT 315 controller should be installed near the controller Do not use a 220 V transformer not UL listed Europe version not evaluated by Underwriters Laboratories Use only UL listed cables Use only UL listed adaptors Use only a UL listed transformer such ...

Page 9: ...and reports Low battery or No battery status to the EntraPass system Power outputs are supervised and individually protected against short circuits and surges by self resetting PTC Locking devices are also supervised for short and open circuits Built in Combus Expansion The KT 315 supports expansion modules to add inputs outputs and an LCD time and date display for Time Attendance purposes KT PC41...

Page 10: ...use UL recognized tamper switch on cabinet housing to conform with UL 294 Points Maximum Wiring AWG 22 600 meters 2 000 feet Door Strike Power 12 VDC 11 1 VDC 13 8 VDC 250mA max each supervised Auxiliary Outputs 4 outputs 25mA max each open collector Relay Controlled Output 2 relay controlled outputs 25mA max each Open collector swtiched to ground use form C relays Kantech KT RM1 if needed Auxilia...

Page 11: ...wer supply module for KT 315 KT PC4216 16 Output expansion module for KT 315 KT RM1 External isolation relay SPDT for KT 315 output RL1 RL2 not UL listed KT3 LCD Time date LCD display unit for KT 315 KT 315CAB KT 315 black metal cabinet including KT LOCK KT 4051CAB Standard black metal cabinet for KT PCxxx modules order keylock separately KT LOCK Keylock for KT 315CAB KT 4051CAB metal cabinet 2key...

Page 12: ...vided to ensure proper operation Make an earth ground connection to the cabinet of the KT 315 as per the requirements of your local electrical code Wire the E GND terminal on the KT 315 printed circuit board directly to that connection point Door Locking Devices Connect door locks to and LK1 and L2 Maximum 250mA 12 VDC per output Check for local magnetic lock regulations LK1 LK2 and terminals are ...

Page 13: ...as input 2 Inputs 3 and 4 are automatically reserved for the second controlled door The contact is assigned input 3 and the associated request to exit detector as input 4 There is no obligation to follow these rules but this standard convention facilitates servicing Readers and Keypads READER CONNECTION TERMINAL WARNING Connection the red wire lead or power lead of a 5 VDC reader to the 12 VDC ter...

Page 14: ...xiliary outputs are used for visual and audible signals They can be activated according to schedules input conditions or events and local alarms Auxiliary outputs OUT DOOR 1 2 LED provide visual feedback of access operation and auxiliary outputs OUT DOOR 1 2 BUZ can activate audible warning devices such as T REX to signal door alarms Tamper Protection Install tamper switch on cabinet Kantech KT TA...

Page 15: ...4 000 feet If the master controller is located more than 30 m 200 feet an optional VC 485 multi function communication interface must be used It can also be used when running a communication cable in areas unusually high in electrical noise NOTE The host computer is used to program the KT 315 Controllers Over Corporate Network LAN If the master controller is used in a LAN enabled corporate setting...

Page 16: ...ry verification will cutoff battery power if the battery voltage level falls below 9 5 Volts NOTE The KT 315 Controller will not start on battery alone NOTE Power should only be applied to the unit when all connections are completed and tested Installing Combus Modules Introduction to Combus Modules The Combus terminals on the KT 315 Controller are used to connect expansion modules to add inputs o...

Page 17: ...t 500mA maximum for the Combus of each KT 315 Verify this voltage with a multi meter and determine if you need to install a KT PC4204 in repower mode Using this configuration you will be provided with an additional 1 amp of current on the controller s Combus The KT PC4204 is generally installed at the beginning of the loop When using the KT PC4204 in repower mode the first relay of the module will...

Page 18: ...4 16 end of line resistors 5600 ohms Three 3 plastic standoffs with adhesive One 1 installation instructions sheet Mounting the KT PC4108 Module The KT PC4108 module should be located inside a compatible cabinet Kantech part no KT 4051CAB mounted in a dry secure location Preferably it should be placed at a convenient distance from the connected devices Perform the following steps to mount the unit...

Page 19: ... be assigned to the system To assign the module perform the following steps 1 Establish communication between EntraPass 5 01 or higher and the controller 2 Remove the tamper switch wire or only the wire if tamper switch is not used If there is no connection to the TAM input use the Tamper Switch button to generate an event 3 An event will be displayed on the EntraPass workstation Desktop Message s...

Page 20: ...a compatible cabinet Kantech part no KT 4051CAB mounted in a dry secure location Preferably it should be placed at a convenient distance from the connected devices Perform the following steps to mount the unit 1 Push the five plastic standoffs through the mounting holes on the back of the cabinet 2 Secure the cabinet to the wall in the desired location Use appropriate wall anchors when securing th...

Page 21: ...e if tamper switch is not used 3 A serial number should be displayed in the EntraPass message desktop Look for the type of module and the controller to which it is connected 4 From the EntraPass controller definition window select the functionality of the module and enter the serial number in the appropriate field refer to Chapter 4 Defining Devices or your EntraPass Reference Manual for more deta...

Page 22: ...a convenient distance from the connected devices Perform the following steps to mount the units 1 Press the four plastic standoffs through the mounting holes at the back of the cabinet 2 Secure the cabinet to the wall in the desired location Use appropriate wall anchors when securing the cabinet to drywall plaster concrete brick or other surfaces 3 Press the circuit board into the plastic standoff...

Page 23: ...ides date and time via a 32 character liquid crystal display KT3 LCD Specifications Connects to control panel via 4 wire Combus Current draw 50 mA from Combus Input status green AC Fail red and Trouble yellow status lights Unpacking the KT3 LCD The KT3 LCD package includes the following parts items One KT3 LCD keypad Four mounting screws Mounting the KT3 LCD The keypad should be mounted where it i...

Page 24: ...d RL1 terminals 3 Place a jumper between the DOOR1 and RL1 terminals 4 Apply AC power to the transformer The VITAL LED should flash 4 times This means that the controller is in the initialization mode 5 Remove jumper 6 When the controller is connected to the computer the VITAL LED should flash 3 times alternately 7 Reconnect the battery VITAL LED status indications Communication status and other v...

Page 25: ...EDs are transmit receive activity indicators RS 232 YELLOW The RS 232 LEDs are ON when communicating to the EntraPass gateway or to the dial up modem COMBUS RX and TX YELLOW These LEDs are transmit receive activity indicators Only very small packets will be sent transmitted upon module activity LOCK1 LOCK2 RED This LED turns ON when the lock output is activated RELAY1 RELAY2 RED Each relay output ...

Page 26: ...deform the batteries Ensure that the above precautions are strictly observed by related departments including but not limited to production sales and outside contractors Regarding the recommended battery 7 A 12 V It is the end user and or installer responsibility to assure that the disposal of used batteries is made according to the waste recovery and recycling regulations currently applicable in ...

Page 27: ...22 KT 315 Wiring Diagram ...

Page 28: ... 2018 Tyco Security Products All rights reserved www kantech com ...

Reviews: