9 of 12 

 © 2008                 D540e - 02/08

Cool Group Master

Cool Group 1

Master

Member

Member

tN4 Communication

In order to prevent heating and cooling at the same time, 
this thermostat can operate together with other thermostats 
on a tN4 system to form a cool group.

This thermostat can be set as the cool group master. The 
cool group master operates the cooling equipment for 
the group. Other thermostats can be set to be members 
of the cool group. 

When operating as a cool group, the air temperature 
readings of all the cool group member thermostats are 
communicated to the cool group master and a temperature 
average is determined.

This thermostat shows this cool group average temperature 
as the “Room” temperature while the mode is set to Cool, 
or the mode is set to Auto and the thermostat is allowing 
cooling operation. In all other modes, the cool group 
master thermostat measures and displays the built-in 
“local” temperature sensor measurement.

Fluctuations in the displayed “Room” temperature may 
occur during automatic mode switch over when the display 

changes from using the local temperature for heating to 
using the cool group average temperature for cooling.

When this thermostat is set to Cool mode or is cooling in 
Auto mode, the cooling system is operated to maintain 
the Set Room Cool setpoint and all thermostats in the 
cool group do not operate for air heating. However, cool 
group member thermostats that have a floor minimum 
temperature set are able to continue heating.

This thermostat is the master of cool group number 1 when 
switch setting 3 is set to cool master 1 (Off position).

Backlight

The backlight turns on for 30 seconds once a button is 
pressed.

Warm Weather Shut Down

The thermostat indicates warm weather shut down 
using the 

WWSD

 icon. The WWSD feature prevents the 

heating system from operating if the outdoor temperature 
is above the WWSD temperature. The WWSD feature is 

activated by the tN4 System Control. In order to disable 
the WWSD, the tN4 System Control’s WWSD setting 
must be adjusted.

Freeze Protection

In any event that the room temperature should fall below 
40°F (4.5°C), the heating is turned on.

Cycles Per Hour

When the thermostat is on a tN4 bus together with a tN4 
System Control, the thermostat operates the heating system 
on the cycles per hour determined by the tN4 System 
Control. The thermostat automatically determines the 
cycles per hour when operating the cooling system.

When the thermostat is not in communication with a tN4 
System Control, the Heating Cycles Per Hour setting in the 
Adjust menu allows the installer to select Auto or Sync.

When set to Auto, the thermostat automatically determines 
the cycles per hour.

When set to Sync, the thermostat synchronizes to cycle 
with other thermostats on the tN4 bus.

Synchronization

When the thermostat is on a tN4 bus together with a tN4 
System Control, all the thermostats are synchronized to 
start heating at the same time. This improves efficiency 
of the heating system by reducing short cycles.

When the thermostat is not in communication with a tN4 
System Control, the Heating Cycles Per Hour setting in the 
Adjust menu allows the installer to select Auto or Sync.

When set to Sync, the thermostat synchronizes with other 
thermostats on the tN4 bus.

When set to Auto, the thermostat does not synchronize 
with other thermostats.

Summary of Contents for 540e

Page 1: ...tings wiring details for future reference 6 D540e 02 08 tekmarNet 4 Thermostat 540e Data Brochure 1 of 12 2008 D540e 02 08 tN4 Communication Compatible Requires 6 Wires tN4 C R W G Y One Stage Heat One Stage Cool One Fan Pulse Width Modulation CE Approved Schedule Member Follows Schedule Master Optimum Start Scenes Outdoor Temperature Display Backlight Exercising Freeze Protection The tekmarNet 4 ...

Page 2: ... 10 Flushing 10 tN4 Address 10 Error Messages 11 Cleaning the Thermostat 12 Warranty 12 Display and Switch Settings Switch Settings 1 2 3 4 tNt 540e 540e 1001 07 1 2 3 4 Switch Position Action 1 ON Setback The thermostat follows a programmable setback schedule as a schedule member if available OFF OFF The thermostat does not follow a programmable setback schedule 2 ON Scene The thermostat responds...

Page 3: ...he unoccupied night temperature CLOCK Operating on a programmable schedule AWAY Operating at the Away scene temperature WARM WEATHER SHUT DOWN The heating system has been shut off for the summer COOL GROUP MASTER Thermostat operates the cooling for a group of thermostats tN4 COMMUNICATION Communication is present WARNING SYMBOL Indicates an error is present SECONDARY DISPLAY MAIN DISPLAY ...

Page 4: ...s whenever the cooling is on The fan will turn on with the heating if fan mode 2 is selected The Mode button selects between Auto Cool Heat Vent and Off HeatMode Theheatingsystemoperates to maintain the Set Room temperature The fan may turn on with the heating if the setting is selected Room Temperature Pressthe orthe buttontoselecttheroomtemperature The display indicates whether the HEAT or the C...

Page 5: ...button to change from F to C and vice versa STEP 2 ViewTypeandSoftware Version The large number shows the type number as 540 The software version is shown in the upper right hand corner STEP 3 View tN4 Address The thermostat s tN4 address is shown The address toggles between a number and Au when using automatic addressing STEP 4 Manually Change tN4 Address Press the or the button to manually selec...

Page 6: ...COOL AWAY Set the room cooling temperature while in the Away scene 1 or 2 Default 1 FAN MODE Select if the fan should operate with cooling Fan Mode 1 or with the heating and cooling Fan Mode 2 OFF On Default OFF VENTILATION Select whether or not ventilation is required Auto 10 to 90 On Default Auto FAN Set the minimum percentage the fan should operate while in the event This provides ventilation f...

Page 7: ...peration The thermostat operates the cooling system to maintain the Set Room Cool temperature The fan turns on whenever the cooling system is on The cooling system has a fixed minimum on time of 2 minutes and a minimum off time of 5 minutes in order to prevent cooling equipment short cycling Adjust Menu 2 of 2 for installer use only ADJUST MENU After the last item the control returns to the first ...

Page 8: ...at being on even though the room temperature is above the set room temperature This is due to the Optimum Start feature heating the room in order to reach the temperature on time The Optimum Start applies for both the heating and the cooling systems When the mode is set to Auto Optimum Start prioritizes for the heating system Optimum Start 10P M 5A M 8A M Occ 70 F 21 C UnOcc 65 F 18 C Room Temp Re...

Page 9: ...to cool master 1 Off position Backlight The backlight turns on for 30 seconds once a button is pressed Warm Weather Shut Down The thermostat indicates warm weather shut down using the WWSD icon The WWSD feature prevents the heating system from operating if the outdoor temperature is above the WWSD temperature The WWSD feature is activated by the tN4 System Control In order to disable the WWSD the ...

Page 10: ...NE TEST On If not selected the thermostat display will show ZONE TEST OFF The Zone Test is only available on this thermostat when switch setting 4 is set to hydronic Max Heat The installer can use the tN4 System Control to turn on all heating zones and at the same time operate the heating equipment at 100 output within temperature limits The thermostat operates at the temperature setting 5 F 3 C T...

Page 11: ... The device count must be lowered to 24 or less If possible move devices to other tN4 busses Error clears automatically once the number of devices on the tN4 bus is at 24 or lower ADDRESS ERROR This thermostat and another device have been manually given the same tN4 address Error clears automatically once this thermostat is given a new manually set address or if the thermostat is set to automatic ...

Page 12: ...pplies only to those defective Products returned to kanmor during the war ranty period This Limited Warranty does not cover the cost of the parts or labor to remove or transport the defec tive Product or to reinstall the repaired or replacement Product all such costs and expenses being subject to Purchaser s agreement and warranty with its customers Any representations or warranties about the Prod...

Reviews: