SETPOINT CONTROL
Access the ADJUST menu by pressing and holding simultaneously for 1 second, the
Item
,
▲
and
▼
buttons. The display will
now show the word ADJUST in the top right corner.
Press and release the
Item
button to advance to the OUTDR DSGN adjustment. Press and hold the
▲
button until OFF is displayed.
Press and release the
Item
button to advance to the MIX TARGET adjustment. Use the
▲
or
▼
button to
select the desired temperature. The MIX TARGET setting is set to the desired setpoint supply temperature.
Press and release the
Item
button to advance to the units adjustment. Use the
▲
or
▼
button to set
the scale to °F or °C.
To exit the ADJUST menu, press and release the Item button to advance to the ESC item. Then
either press the
▲
or
▼
button, or leave the buttons alone for 20 seconds.
SectionInstallerAd
va
nced
Range
Description
Display
Current outdoor air temperature as measured by the outdoor
sensor. This is also the default display for the control.
(OUTDR DSGN
≠
OFF)
Current room air temperature as measured by the indoor sensor.
(Indoor Sensor is present)
Current mixed supply water temperature as measured by the
mixing sensor
Target mixed supply is the temperature the control is currently
trying to maintain at the mixing sensor.
Current boiler temperature as measured by the boiler sensor.
(Boiler sensor is present)
-67 to 149
°
F
(-55 to 65
°
C)
23 to 113
°
F
(-5 to 45
°
C)
---, 14 to 266˚F
(---, -10 to 130˚C)
14 to 266
°
F
(-10 to 130
°
C)
14 to 266
°
F
(-10 to 130
°
C)
B1
B3
B2
B1
B3