background image

© 2003 

D 360e - 06/03 

12 of 20 

Indoor Sensor

If an indoor sensor is used, connect the two wires from the 
sensor to the 

Com

 and 

Indr

 terminals (16 and 18). The indoor 

sensor is used by the 360e to measure the room air temperature.

Unoccupied Switch

If an external timer (kanmor Timer 032e) or switch is used, connect the two wires 
from the external switch to the 

UnO Sw

 and 

Com

 terminals (12 and 13). When these 

two terminals are shorted together, the control registers an unoccupied signal.

STEP FIVE 

 TESTING THE WIRING

Each terminal block 

must be unplugged

 from its header on the control before power is applied for testing. To remove a termi-

nal block, pull it straight down from the control.

The following tests are to be performed using standard testing practices and procedures, and should only be carried out by 
properly trained and experienced persons.

A good quality electrical test meter, capable of reading from at least 0 -300 V (ac) and at least 0 -2,000,000 Ohms, is essential 
to properly test the wiring and sensors.

 Test The Sensors

In order to test the sensors, the actual temperature at each sensor 
location must be measured.  A good quality digital thermometer 
with a surface temperature probe is recommended for ease of 
use and accuracy. Where a digital thermometer is not available, a 
spare sensor can be strapped alongside the one to be tested, and 
the readings compared. Test the sensors according to the instruc-
tions in the Data Brochure D 070e.

 Test The Power Supply

Make sure exposed wires and bare terminals are not in contact 
with other wires or grounded surfaces. Turn on the power and 
measure the voltage between the 

Power L

 and 

Power N

 terminals 

(3 and 4) using an AC voltmeter. The reading should be between 
207 and 253 V (ac).

 Test The Powered Inputs

Mixing Demand

Measure  the voltage between  the 

Mixing Demand

  terminals 

(1 and 2). When the mixing demand device calls for heat, you 
should measure between 20 and 260 V (ac) at the terminals. 
When the mixing demand device  is  off,  you  should  measure 
less than 5 V (ac).

16

Com

17

Out

18

Indr

12

UnO

Sw

13

Com

Timer Switch

13

Com

14

Boil

15

Mix

L

N

4

Power

V

207 to 253 V (ac)

3

1

2

Mixing

Demand

V

20 to 260 V (ac)

Summary of Contents for 360e

Page 1: ...or Sensor Optional Input Universal Sensor Included Input Universal Sensor Included Input Outdoor Sensor Included Output Boiler Input 230 V ac Power Supply Input kanmor Timer Optional Output Mixing Valve Actuating Motor Do not apply power Signal wiring must be rated at least 300 V L N Pmp N Sw Sys UnO Com Boil Mix Pwr Opn Cls Mix Com Out Indr 1 3 5 2 4 6 9 10 7 8 11 12 13 14 15 16 17 18 Mix Power B...

Page 2: ...serving the status field and pointers of the LCD The status field will indicate which of the control s outputs are currently active Most symbols in the status field are only visible when the VIEW menu is selected User Interface Pg 2 Description of Display Elements Pg 3 Sequence of Operation Pg 4 Section A General Operation Pg 4 Section B Mixing Pg 5 Section C Boiler Operation Pg 8 Installation Pg ...

Page 3: ...h or substantial property damage if ignored Double insulated Local level appliances INSTALLATION CATEGORY II OCC UNOCC F C Pump Displays when the mixing system pump is in operation Burner Displays when the boiler relay is turned on Occupied Schedule Displays when the control is in occupied Day mode Unoccupied Schedule Displays when the control is in unoccupied Night mode F C Displays the unit of m...

Page 4: ... is capable of providing boiler protection from cold mixing system return water temperatures If the boiler sensor temperature is cooler than the BOIL MIN setting while the boiler is firing the 360e reduces the output to the mixing valve This limits the amount of cool return water to the boiler and allows the boiler temperature to recover This feature can only be used if a boiler sensor is installe...

Page 5: ... and Indr terminals 16 and 18 In addition power must be applied to the Mixing Demand terminals 1 and 2 as described in the MIXING DEMAND section With the indoor sensor connected the 360e is able to sense the actual room temperature Indoor temperature feedback fine tunes the supply water temperature in the mixing system to maintain room temperature To adjust the room temperature use the ROOM OCC or...

Page 6: ...eat fancoil fin tuben convector radiator and baseboard When a terminal unit is selected the control automatically loads the design supply temperature MIX DSGN maximum supply temperature MIX MAX and minimum supply temperature MIX MIN The factory defaults are listed below To change defaults refer to section B3 If a default has been changed refer to Section A to reload the factory defaults High Mass ...

Page 7: ...ting and the MIX temperature is near the MIX MAX the MAX segment will be displayed in the LCD while either the MIX TARGET temperature or the MIX temperature is being viewed MIXING MINIMUM MIX MIN The MIX MIN is the lowest temperature that the control is allowed to use as a MIX TARGET temperature During mild conditions if the 360e calculates a MIX TARGET temperature that is below the MIX MIN settin...

Page 8: ...differential in order to prevent short cycling When the boiler supply temperature drops below the bottom rail of the differential the 360e closes the Boiler contact to fire the boiler When the boiler supply temperature rises above the top rail of the differential the 360e opens the Boiler contact to turn off the boiler With the 360e either a fixed or automatic differential setting is selected If a...

Page 9: ... all applicable codes and standards This electronic control is not intended for use as a primary limit control Other controls that are intended and certified as safety limits must be placed into the control circuit Do not open the control Refer to qualifed personnel for servicing Opening voids warranty and can result in damage to the equipment and possibly even personal injury STEP ONE GETTING REA...

Page 10: ... to the control Run wire from other system components pumps boilers etc to the control Run wires from the 230 V ac power to the control Use a clean power source with a 15 A circuit to ensure proper operation Multi strand 16 AWG wire is recommended for all 230 V ac wiring due to its superior flexibility and ease of installation into the terminals STEP FOUR ELECTRICAL CONNECTIONS TO THE CONTROL The ...

Page 11: ... These terminals are to be used as a switch to either make or break the boiler circuit When the 360e requires the boiler to fire it closes the contact between terminals 7 and 8 Sensor and Unpowered Input Connections Do not apply power to these terminals as this will damage the control Outdoor Sensor Connect the two wires from the Outdoor Sensor 070e to the Com and Out termi nals 16 and 17 The outd...

Page 12: ...operly test the wiring and sensors Test The Sensors In order to test the sensors the actual temperature at each sensor location must be measured A good quality digital thermometer with a surface temperature probe is recommended for ease of use and accuracy Where a digital thermometer is not available a spare sensor can be strapped alongside the one to be tested and the readings compared Test the s...

Page 13: ...ircuit is powered up the valve should move in the closing direction If it does not check the wiring between the terminals and the actuator Refer to any installation or troubleshooting information supplied with the motor If the motor closes correctly turn off the power to the circuit and remove the jumper Connecting The Control Make sure all power to the devices and terminal blocks is off and remov...

Page 14: ...ing is set to the desired room air temperature during the occupied Day mode Note To increase or decrease space temperature during the occupied Day mode only adjust the ROOM OCC setting Press and release the Item button to advance to the ROOM UNOCC adjustment Use the or button to set the desired temperature The ROOM UNOCC setting is set to the desired room air temperature during the unoccupied Nigh...

Page 15: ...it the ADJUST menu press and release the Item button to advance to the ESC item Then either press the or button or leave the buttons alone for 20 seconds S e c t i o n I n s t a l l e r A d v a n c e d Range Description Display Current outdoor air temperature as measured by the outdoor sensor This is also the default display for the control OUTDR DSGN OFF Current room air temperature as measured b...

Page 16: ...n for the heating system OUTDR DSGN OFF 35 to 100 F 2 to 38 C B3 The design supply water temperature used in the heat loss calculation for the heating system OUTDR DSGN OFF 70 to 220 F 21 to 104 C B3 The maximum supply water temperature for the mixing system OUTDR DSGN OFF 80 to 210 F 27 to 99 C B3 The minimum supply temperature for the mixing system OUTDR DSGN OFF OFF 35 to 150 F OFF 2 to 65 C B3...

Page 17: ...ges and possible causes When the Test button is pressed the test light is turned on The individual outputs and relays are tested in the following test sequence TEST SEQUENCE Each step in the test sequence lasts 10 seconds During the test routine the test sequence may be paused by pressing the Test button Only if there is a mixing demand can the control be paused in a step If the Test button is not...

Page 18: ... Sketch the piping of the system This is a relatively simple step that tends to be overlooked how ever it can often save hours of time in troubleshooting a system Note flow directions in the system paying close attention to the location of pumps check valves pressure bypass valves and mixing valves Ensure correct flow direction on all pumps This is also a very useful step if additional assis tance...

Page 19: ...to a short circuit If the BOIL MIN adjust ment is higher than 100 F 38 C the control closes the Boiler contact when the mixing valve starts to operate The boiler temperature is then limited by the operating aquastat If the BOIL MIN adjust ment is lower than 100 F 38 C the control does not operate the Boiler contact Locate and repair the problem as described in the Data Brochure D 070e To clear the...

Page 20: ...have not been authorized by kanmor or if the Product was not installed in compliance with kanmor s instructions and or the local codes and ordinances or if due to defective installation of the Product or if the Product was not used in compliance with kanmor s instructions THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES EXPRESS OR IMPLIED WHICH THE GOVERNING LAW ALLOWS PARTIES TO CONTRACTUALLY EXC...

Reviews: