- Data Brochure

Mixing Control 360e

D 360e

06/03

 

1 of 20 

© 2003  

D 360e - 06/03

The Mixing Control 360e is designed to control the supply water temperature to a hydronic system in order to provide outdoor 
reset or setpoint operation. The control uses a floating action mixing valve to regulate the supply water temperature, while 
protecting the boiler against flue gas condensation. The control has a Liquid Crystal Display (LCD) to view system status and 
operating information.

Additional Functions Include:

•  Quick Setup for easy installation and programming of 

control

•  User comfort adjustment to increase or decrease build-

ing space temperature

•  Advanced settings to fine-tune building requirements

•  Boiler Control for improved energy savings

•  Powered mixing system pump output

•  Optional indoor sensor for room air temperature control

•  Test sequence to ensure proper component operation

•  Setback input for energy savings

•  230 V (ac) power supply

• CE Approved

Input

Mixing

Demand

Signal

Output

Mixing System

Pump

Input

Indoor
Sensor

Optional

Input

Universal Sensor

Included

Input

Universal Sensor

Included

Input

Outdoor
Sensor

Included

Output

Boiler

Input

230 V (ac)

Power

Supply

Input

kanmor Timer

Optional

Output

Mixing Valve &

Actuating Motor

Do not apply power

Signal wiring must be 

rated at least 300 V.

L

N

Pmp

N

Sw

Sys

UnO Com Boil

Mix

Pwr Opn Cls

Mix Com Out Indr

1

3

5

2

4

6

9 10

7 8

11

12 13 14 15 16 17 18

Mix

Power

Boiler

Demand

Advanced

Installer

Boiler Sensor

Supply

30% Enable

10% Enable

Return

Item

Test

Terminal

Unit

Mixing

Demand

INSTALLATION CATEGORY II

Made in Canada

Power: 

230 V 

±

10% 50  Hz 2300 VA

Relays: 

230 V (ac) 10 A 1/3 hp, pilot duty 240 VA

Demand: 

20 to 260 V (ac) 2 VA 

H1

21

1B

To increase or decrease the
building temperature:

• Press the 

Item

,

,

 buttons

simultaneously for 1 sec. to
enter the ADJUST menu
• Use the 

,

 buttons to adjust

the 

ROOM

 setting

Display defaults back to VIEW
menu after 20 seconds.
 

  ROOM 

Set to desired room temperature.

  OUTDR DSGN 

Set to coldest (design)

  outdoor temperature.
  Terminal Unit 

 

Set to

 

  High Mass Radiant 

  1

 

  Low Mass Radiant 

2

 

  Fan Coil 

3

 

  Convector 4

 

  Radiator 5

 

  Baseboard 6

 

 

Refer to brochure for more information.

Installer Instructions

Mixing Control 360e

Floating Action

Open

Motor

Speed

Close

M

Summary of Contents for 360e

Page 1: ...or Sensor Optional Input Universal Sensor Included Input Universal Sensor Included Input Outdoor Sensor Included Output Boiler Input 230 V ac Power Supply Input kanmor Timer Optional Output Mixing Valve Actuating Motor Do not apply power Signal wiring must be rated at least 300 V L N Pmp N Sw Sys UnO Com Boil Mix Pwr Opn Cls Mix Com Out Indr 1 3 5 2 4 6 9 10 7 8 11 12 13 14 15 16 17 18 Mix Power B...

Page 2: ...serving the status field and pointers of the LCD The status field will indicate which of the control s outputs are currently active Most symbols in the status field are only visible when the VIEW menu is selected User Interface Pg 2 Description of Display Elements Pg 3 Sequence of Operation Pg 4 Section A General Operation Pg 4 Section B Mixing Pg 5 Section C Boiler Operation Pg 8 Installation Pg ...

Page 3: ...h or substantial property damage if ignored Double insulated Local level appliances INSTALLATION CATEGORY II OCC UNOCC F C Pump Displays when the mixing system pump is in operation Burner Displays when the boiler relay is turned on Occupied Schedule Displays when the control is in occupied Day mode Unoccupied Schedule Displays when the control is in unoccupied Night mode F C Displays the unit of m...

Page 4: ... is capable of providing boiler protection from cold mixing system return water temperatures If the boiler sensor temperature is cooler than the BOIL MIN setting while the boiler is firing the 360e reduces the output to the mixing valve This limits the amount of cool return water to the boiler and allows the boiler temperature to recover This feature can only be used if a boiler sensor is installe...

Page 5: ... and Indr terminals 16 and 18 In addition power must be applied to the Mixing Demand terminals 1 and 2 as described in the MIXING DEMAND section With the indoor sensor connected the 360e is able to sense the actual room temperature Indoor temperature feedback fine tunes the supply water temperature in the mixing system to maintain room temperature To adjust the room temperature use the ROOM OCC or...

Page 6: ...eat fancoil fin tuben convector radiator and baseboard When a terminal unit is selected the control automatically loads the design supply temperature MIX DSGN maximum supply temperature MIX MAX and minimum supply temperature MIX MIN The factory defaults are listed below To change defaults refer to section B3 If a default has been changed refer to Section A to reload the factory defaults High Mass ...

Page 7: ...ting and the MIX temperature is near the MIX MAX the MAX segment will be displayed in the LCD while either the MIX TARGET temperature or the MIX temperature is being viewed MIXING MINIMUM MIX MIN The MIX MIN is the lowest temperature that the control is allowed to use as a MIX TARGET temperature During mild conditions if the 360e calculates a MIX TARGET temperature that is below the MIX MIN settin...

Page 8: ...differential in order to prevent short cycling When the boiler supply temperature drops below the bottom rail of the differential the 360e closes the Boiler contact to fire the boiler When the boiler supply temperature rises above the top rail of the differential the 360e opens the Boiler contact to turn off the boiler With the 360e either a fixed or automatic differential setting is selected If a...

Page 9: ... all applicable codes and standards This electronic control is not intended for use as a primary limit control Other controls that are intended and certified as safety limits must be placed into the control circuit Do not open the control Refer to qualifed personnel for servicing Opening voids warranty and can result in damage to the equipment and possibly even personal injury STEP ONE GETTING REA...

Page 10: ... to the control Run wire from other system components pumps boilers etc to the control Run wires from the 230 V ac power to the control Use a clean power source with a 15 A circuit to ensure proper operation Multi strand 16 AWG wire is recommended for all 230 V ac wiring due to its superior flexibility and ease of installation into the terminals STEP FOUR ELECTRICAL CONNECTIONS TO THE CONTROL The ...

Page 11: ... These terminals are to be used as a switch to either make or break the boiler circuit When the 360e requires the boiler to fire it closes the contact between terminals 7 and 8 Sensor and Unpowered Input Connections Do not apply power to these terminals as this will damage the control Outdoor Sensor Connect the two wires from the Outdoor Sensor 070e to the Com and Out termi nals 16 and 17 The outd...

Page 12: ...operly test the wiring and sensors Test The Sensors In order to test the sensors the actual temperature at each sensor location must be measured A good quality digital thermometer with a surface temperature probe is recommended for ease of use and accuracy Where a digital thermometer is not available a spare sensor can be strapped alongside the one to be tested and the readings compared Test the s...

Page 13: ...ircuit is powered up the valve should move in the closing direction If it does not check the wiring between the terminals and the actuator Refer to any installation or troubleshooting information supplied with the motor If the motor closes correctly turn off the power to the circuit and remove the jumper Connecting The Control Make sure all power to the devices and terminal blocks is off and remov...

Page 14: ...ing is set to the desired room air temperature during the occupied Day mode Note To increase or decrease space temperature during the occupied Day mode only adjust the ROOM OCC setting Press and release the Item button to advance to the ROOM UNOCC adjustment Use the or button to set the desired temperature The ROOM UNOCC setting is set to the desired room air temperature during the unoccupied Nigh...

Page 15: ...it the ADJUST menu press and release the Item button to advance to the ESC item Then either press the or button or leave the buttons alone for 20 seconds S e c t i o n I n s t a l l e r A d v a n c e d Range Description Display Current outdoor air temperature as measured by the outdoor sensor This is also the default display for the control OUTDR DSGN OFF Current room air temperature as measured b...

Page 16: ...n for the heating system OUTDR DSGN OFF 35 to 100 F 2 to 38 C B3 The design supply water temperature used in the heat loss calculation for the heating system OUTDR DSGN OFF 70 to 220 F 21 to 104 C B3 The maximum supply water temperature for the mixing system OUTDR DSGN OFF 80 to 210 F 27 to 99 C B3 The minimum supply temperature for the mixing system OUTDR DSGN OFF OFF 35 to 150 F OFF 2 to 65 C B3...

Page 17: ...ges and possible causes When the Test button is pressed the test light is turned on The individual outputs and relays are tested in the following test sequence TEST SEQUENCE Each step in the test sequence lasts 10 seconds During the test routine the test sequence may be paused by pressing the Test button Only if there is a mixing demand can the control be paused in a step If the Test button is not...

Page 18: ... Sketch the piping of the system This is a relatively simple step that tends to be overlooked how ever it can often save hours of time in troubleshooting a system Note flow directions in the system paying close attention to the location of pumps check valves pressure bypass valves and mixing valves Ensure correct flow direction on all pumps This is also a very useful step if additional assis tance...

Page 19: ...to a short circuit If the BOIL MIN adjust ment is higher than 100 F 38 C the control closes the Boiler contact when the mixing valve starts to operate The boiler temperature is then limited by the operating aquastat If the BOIL MIN adjust ment is lower than 100 F 38 C the control does not operate the Boiler contact Locate and repair the problem as described in the Data Brochure D 070e To clear the...

Page 20: ...have not been authorized by kanmor or if the Product was not installed in compliance with kanmor s instructions and or the local codes and ordinances or if due to defective installation of the Product or if the Product was not used in compliance with kanmor s instructions THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES EXPRESS OR IMPLIED WHICH THE GOVERNING LAW ALLOWS PARTIES TO CONTRACTUALLY EXC...

Reviews: