KANE455
manual
Page
18
When complete press
to start the tightness test:
TIGHTN’S
P1
20.01
→
Pressure at start of tightness test.
P2
20.01
→
Real time pressure reading.
TIME
119
→
Tightness default time is 2 minutes. Can
be changed via “Menu”.
When complete the display will show:
LOG
01
→
The tightness test is automatically stored in
the memory.
P1
20.01
→
Pressure at start of tightness test.
P2
19.98
→
Pressure at end of tightness test.
∆
P
0.03
→
Pressure drop during tightness test.
To print a tightness test, select MENU / REPORT / TIGHTN’S / VIEW.
Use
to select the log number to be printed.
Press
/
to print the tightness test (also sends to PC if Bluetooth
fitted)