HAWK 5000 OPERATOR MANUAL
KANE INTERNATIONAL LIMITED
14
d) In three phase mode, if two of the CT lights flash, try swapping the CT clamps over. If
two of the CT lights are flashing, this may be because the phase rotation is marked
wrongly on the cables at that particular site. This can be confirmed by the use of a
phase rotation meter. If this is the case, swap over the CTs on the yellow and blue
phases.
Recorded data
a)
Some or all data is zero:
Are either of the input scale factors zero?
Were any or all of the CT clamps connected incorrectly?
Try using
survey OVERVIEW
to check that all the data really is zero.