background image

 

                            www.kg-groep.com                                                                                                                  page 9

 

10

 

C

OMMON SETTINGS

 

In a marine application, it is NOT common for a fire suppression system intended for an engine room 
to be released by an automatic fire detector but ONLY by manual release. 

The most common Marine setting of the NANO MAR SYSTEM is based on marine rules and standards. 
Under normal condition only the green Power LED and the Manual Only LED lite to indicate the system 
is operating correctly. 

Ask your supplier for your system settings.

 

 

Example setting for a 

vessel’s engine room

 

The extinguishing delay time is 20 seconds  

 

The NANO MAR SYSTEM operate in the manual mode only  

 

The use of automatic fire detectors is only informative 

Example setting for an electronical cabinet or auxiliary space in a vessel 

 

The extinguishing delay time is set between 0 and 35 seconds   

 

The NANO MAR SYSTEM operate in the Automatic & Manual mode  

 

Dual zone alarm for automatic extinguishing release  

 

When release delay is programmed, the manual release is also delayed 

11

 

W

HAT TO DO RECOMMENDATIONS

 

11.1

 

W

HAT TO DO IN THE EVENT OF A FIRE ALARM CONDITION

 

 

Carry out the premises defined procedures. 

 

When it is safe to do so silence the fire alarm devices and reset the system. 

 

Note the time the fire alarm occurred and log the fire event in the logbook. 

11.2

 

W

HAT TO DO IN THE EVENT OF A FAULT CONDITION

 

 

Note the indications on the front of the NANO control panel. 

 

Note the time the fault was noticed and log the fault event in the logbook. 

 

Notify your service department or company of the fault condition. 

11.3

 

R

OUTINE TESTING RECOMMENDATIONS

 

The required management and maintenance tasks and their frequency may vary by application and 
Country. It is the responsibility of the Premises Management to undertake periodic tests to ensure 
the  fire  detection-/extinguishing  system  is  operational.  Record  the  test  results  each  time  in  your 
logbook. 

  

                     Always ensuring that the system is set to maintenance mode

 

11.4

 

W

ARNING

 

The NANO MAR SYSTEM is equipped with 2 activation techniques for activation of fire extinguishers. 
In the (DP3 OFF position) the system is set for the activation of electrical igniters meant for aerosol 
fire extinguishers. In the (DP3 ON position) the system is set for activating of an extinguishing system 
using a solenoid activator. DS 3 OFF = system is meant for electrical igniters intended for aerosol fire 
extinguishers 1,3A/50ms.  With DS 3 ON the system is meant for solenoid technology. 

When the DP3 is in the ON position (solenoid only) DO NOT USE this in combination with an 

ETB/BOX. This may cause irreparably damage to the ETB/BOX and the NANO panel. 

Summary of Contents for NANO MARINE

Page 1: ...www KG Groep com January 1 2023 version 1 0 Owner s manual NANO MARINE FIRE DETECTION EXTINGUISHING CONTROL SYSTEM...

Page 2: ...6 EXTINGUISHING RELEASE 6 9 LED INDICATORS 7 9 1 MANUAL RELEASE ONLY 7 9 2 AUTOMATIC MANUAL RELEASE 7 9 3 POWER 7 9 4 COMMON FIRE 7 9 5 FIRE ZONE ALARM 7 9 6 EXTINGUISHING RELEASED 8 9 7 EXTINGUISHING...

Page 3: ...abinets engine rooms in vessels yachts and other small areas or equipment The NANO MAR SYSTEM continuously senses its inputs and in the event of a fire gives the correct output to enable a product spe...

Page 4: ...depending on the DIP switch time settings In a marine application it is NOT common for a fire suppression system intended for an engine room to be released by an automatic fire detector But the NANO c...

Page 5: ...nt of a complete power failure the general fault relay becomes inactive 6 7 VFC FIRE RELAY ACTIVE IN SINGLE OF DUAL MODE ALARM A single or dual FIRE indication can trigger the VFC relay You can choice...

Page 6: ...d button as long this button is pressed the extinguishing release sequence will be halted and cause the yellow hold activated indicator flash Release the Hold button shall re start the countdown relea...

Page 7: ...differently indicating an abnormality in the power supply to the NANO control panel When starting the NANO MAR SYSTEM after a power failure or an extinguishers release the green power LED on the NANO...

Page 8: ...ators flash This yellow fault indicator will light continuously at any fault condition or power malfunction 9 9 FIRE ZONE FAULT When the NANO control panel has detected an error in one of the critical...

Page 9: ...m Note the time the fire alarm occurred and log the fire event in the logbook 11 2 WHAT TO DO IN THE EVENT OF A FAULT CONDITION Note the indications on the front of the NANO control panel Note the tim...

Page 10: ...sconnect extinguisher MOVE the disconnect switch of all in the YES position and the aerosol extinguisher is disabled and can not be activated A disablement will be signalized as fault on the NANO cont...

Page 11: ...ystem according to the instructions of the supplier 12 4QUARTERLY TESTING COMPETENT PERSON To be conducted by the Competent Person Included as reference for the Premises Management Check all previous...

Page 12: ...itness for a particular purpose It is the responsibility of the premises management to define the fire procedures and ensure that all relevant users are trained and that fire drills are performed with...

Reviews: