www.kg-groep.com page 9
10
C
OMMON SETTINGS
In a marine application, it is NOT common for a fire suppression system intended for an engine room
to be released by an automatic fire detector but ONLY by manual release.
The most common Marine setting of the NANO MAR SYSTEM is based on marine rules and standards.
Under normal condition only the green Power LED and the Manual Only LED lite to indicate the system
is operating correctly.
Ask your supplier for your system settings.
Example setting for a
vessel’s engine room
:
▪
The extinguishing delay time is 20 seconds
▪
The NANO MAR SYSTEM operate in the manual mode only
▪
The use of automatic fire detectors is only informative
Example setting for an electronical cabinet or auxiliary space in a vessel
▪
The extinguishing delay time is set between 0 and 35 seconds
▪
The NANO MAR SYSTEM operate in the Automatic & Manual mode
▪
Dual zone alarm for automatic extinguishing release
▪
When release delay is programmed, the manual release is also delayed
11
W
HAT TO DO RECOMMENDATIONS
11.1
W
HAT TO DO IN THE EVENT OF A FIRE ALARM CONDITION
▪
Carry out the premises defined procedures.
▪
When it is safe to do so silence the fire alarm devices and reset the system.
▪
Note the time the fire alarm occurred and log the fire event in the logbook.
11.2
W
HAT TO DO IN THE EVENT OF A FAULT CONDITION
▪
Note the indications on the front of the NANO control panel.
▪
Note the time the fault was noticed and log the fault event in the logbook.
▪
Notify your service department or company of the fault condition.
11.3
R
OUTINE TESTING RECOMMENDATIONS
The required management and maintenance tasks and their frequency may vary by application and
Country. It is the responsibility of the Premises Management to undertake periodic tests to ensure
the fire detection-/extinguishing system is operational. Record the test results each time in your
logbook.
Always ensuring that the system is set to maintenance mode
11.4
W
ARNING
The NANO MAR SYSTEM is equipped with 2 activation techniques for activation of fire extinguishers.
In the (DP3 OFF position) the system is set for the activation of electrical igniters meant for aerosol
fire extinguishers. In the (DP3 ON position) the system is set for activating of an extinguishing system
using a solenoid activator. DS 3 OFF = system is meant for electrical igniters intended for aerosol fire
extinguishers 1,3A/50ms. With DS 3 ON the system is meant for solenoid technology.
When the DP3 is in the ON position (solenoid only) DO NOT USE this in combination with an
ETB/BOX. This may cause irreparably damage to the ETB/BOX and the NANO panel.