6
Kamstrup A/S • 5512887_B2_GB_09.2015
ULTRAFLOW® 54 · DN150-300
It can also be an advantage to use the enclosed
distance piece if the low sensor housing is
insulated and the electronics box must be
removed from the insulation.
If the required position of the electronics box
differs from standard position, the distance
piece can be mounted with the enclosed collar
band around the low sensor housing. However,
please note that the cable connections must
always point downwards (see paragraph 1.2.1
”Orientation of low sensor electronics box”, page
7).
Figure 6
At
medium temperature more than 5 °C below ambient temperature (T
med
< T
amb
- 5 °C)
(typically
in cooling installations) it is important to take action to avoid condensation in the electronics box.
Therefore, the electronics box must be mounted via the enclosed distance piece. The cable
connections must always point downwards (see paragraph 1.2.1 ”Orientation of low sensor
electronics box”, page 7).
Alternatively, the electronics box can be wall mounted as long as the distance to low sensor
housing and pipe installation is minimum 170 mm.
Furthermore, when mounting the electronics box please make sure that the cable connections on
the box are at a higher level than the cable connection on the low sensor housing.
By vertical mounting of ULTRAFLOW® 54 in a riser this can be secured by mounting the distance
piece by means of the collar band as shown in Figure 6.
If ULTRAFLOW® 54 is mounted horizontally the electronics box can be mounted on the distance
piece by means of the collar band. The distance piece can then be turned upwards until the cable
connections on the electronics box are in a higher position than the cable connection on the low
sensor housing. See Figure 7.
Alternatively, the electronics box can be wall mounted at a suitable distance to the installation
(minimum 170 mm).
Figure 7