7
Kamstrup A/S • 5512887_B2_GB_09.2015
ULTRAFLOW® 54 · DN150-300
1.2.1
Orientation of low sensor electronics box
Mounting the electronics box, the cable connections must always be horizontally or downwards
oriented in order to avoid the risk of water and condensation being led into the electronics box via
the cables.
This is especially important in humid environments, when ULTRAFLOW® 54 is used as cooling
sensor, or if the medium temperature can become more than 5 °C lower than the ambient
temperature (T
med
< T
amb
- 5 °C).
Furthermore, the steel tube and wires must in general hang freely downwards after the cable
connections to form a drip nose for drainage of water and condensation.
Max 90°
Max 90°
Figure 8