5
Kamstrup A/S • 5512887_B2_GB_09.2015
ULTRAFLOW® 54 · DN150-300
1.2 Mounting of ULTRAFLOW® 54 electronics box
At
medium temperature below 90 °C
(T
med
< 90 °C) and at medium temperature less
than 5 °C below ambient temperature (T
med
>
T
amb
- 5 °C)
the electronics box can be mounted
directly on the low sensor housing via the
factory mounted itting.
If the low sensor is vertically mounted the
cable connections of the electronics box will
be horizontally oriented. This is permitted. If
the cable connections should preferably point
downwards, the electronics box can be mounted
via the enclosed distance piece, which moves
the box approx. 170 mm away from the low
sensor housing. Alternatively, a shorter distance
piece, which only moves the box approx. 45
mm away from the low sensor housing, can be
used. The short distance piece must be ordered
separately (6561-332).
Figure 4
At
medium temperature above 90 °C
(T
med
> 90 °C)
the temperature is too high for the
electronics box to be mounted directly on the
low sensor housing.
Therefore, the electronics box must be mount-ed
via the enclosed distance piece. The
cable connections must always point down-
wards (see paragraph 1.2.1 ”Orientation of low
sensor electronics box”, page 7).
Alternatively, the electronics box can be wall
mounted as long as the distance to low sensor
housing and pipe installation is minimum
170 mm.
Figure 5