9 Information codes ”INFO”
MULTICAL® 801 constantly monitors a series of important functions. If a
serious error occurs in the measuring system or in the installation, ”INFO”
appears in the display and an info code can be read by activating the upper
front plate button until the measuring unit shows ”INFO” in the display. The
info code is only visible while the error exists.
Info
code
Description
Response time
0
No irregularities
-
1
Supply voltage has been cut off
-
8
Temperature sensor T1 outside
measuring range
1…10 min.
4
Temperature sensor T2 outside
measuring range
1…10 min.
32
Temperature sensor T3 outside
measuring range
1…10 min.
64
Leak in the cold-water system
24 hours
256
Leak in the heating system
24 hours
512
Burst in the heating system
120 sec.
ULTRAFLOW® 54 info (activated when CCC=4XX)
16
Flow sensor V1, Datacomm error
After reset and 1 day (00:00)
1024
Flow sensor V2, Datacomm error
After reset and 1 day (00:00)
2048 Flow sensor V1, Wrong meter factor
After reset and 1 day (00:00)
128
Flow sensor V2, Wrong meter factor
After reset and 1 day (00:00)
4096 Flow sensor V1, Signal too low (Air)
After reset and 1 day (00:00)
8192
Flow sensor V2, Signal too low (Air)
After reset and 1 day (00:00)
16384 Flow sensor V1, Wrong flow direction
After reset and 1 day (00:00)
32768 Flow sensor V2, Wrong flow direction
After reset and 1 day (00:00)