background image

16

Kamstrup A/S • 55121600_A4_GB_03.2015

MULTICAL® 6M2

Cable resistance 

< 29 Ohm

Cable capacity 

< 180 nF

The M-Bus network is connected to terminals 
24 and 25. The polarity is unimportant.
M-Bus comes with pulse inputs.

10.2.3  Lon Works, type 67-00-24 (rev. A1 or higher)

The LON module is used for transfer of data from MULTICAL® 6M2 either for data reading or for ad-
justment purposes via the LON bus, which is ideal for i.e. climate control and building automation. 
Data is communicated at a high speed which makes it possible to connect many applications to 
the same LON network. 
Cabling between the LON module and the other LON-nodes is made with a standard twisted pair 
cable. The length can be up to 2700 m using bus topology or 500 m using free topology. The LON 
module is built up as a separate network node with neuron chip, memory, transceiver and input/
output circuit. The module requires external supply (24 VAC /230 VAC) of MULTICAL® 6M2, battery 
supply is not possible.
The LON module collects new data from MULTICAL® 6M2 in a cycle which secures that all data are 
updated every 30 seconds.

10.2.4  BACnet®, type 67-00-66 (rev. J1 or higher)

The BACnet® module communicates with BACnet® on MS/TP via RS-485 as a master/slave or 
slave device.
The BACnet® module transfers a number of both actual data and accumulated data. Furthermore, 
info codes can be transmitted to the BACnet® Controller. The two pulse inputs allow connection 
and reading of two additional meters for e.g. water and electricity with pulse output.

10.2.5  Modbus, type 67-00-67 (rev. B1 or higher)

The Modbus base module for MULTICAL® 6M2 ensures simple integration from Kamstrup’s heat, 
cooling and water meters into a Modbus based system. The Modbus module communicates as 
an RTU (Remote Terminal Unit) slave device on RS-485. The Modbus module transfers a number 
of both actual data and accumulated data. The RS-485 port of the Modbus module is galvanically 
separated from the meter’s voltage potential, thereby improving the security for smooth opera-
tions. At the same time, the risk of influencing the meter due to influences of the RS-485 port is 
reduced to a minimum.

Summary of Contents for MULTICAL 6M2

Page 1: ...trivej 28 Stilling DK 8660 Skanderborg T 45 89 93 10 00 info kamstrup com kamstrup com V I Trade s r o pobo ka Ko ice Novoz mock 102 erme sk cesta 1 949 05 Nitra 040 01 Ko ice vit vit sk kosice vit sk...

Page 2: ...well as in closed locations indoors The ambient temperature must be within 5 55 C Maintenance and repair The district heating supplier can replace communication module battery and temperature sensor...

Page 3: ...Installation Guide MULTICAL 6M2 Kamstrup A S Industrivej 28 Stilling DK 8660 Skanderborg T 45 89 93 10 00 info kamstrup com kamstrup com...

Page 4: ...on of units with active pulses 11 6 3 Connection example 12 7 Voltage supply of calculator 13 7 1 Battery supply 13 7 2 Mains modules 13 8 Testing of function 14 9 Information codes INFO 14 10 Plug in...

Page 5: ...pe The other sensor marked with a blue sign is to be installed in the outlet pipe see paragraph 6 for further information Note The sensor cables must not be pulled Be aware of this in case of binding...

Page 6: ...irect sensor For mounting in existing installations with standard angle tees Kamstrup A S can furthermore supply R and R brass nipple fittings for the short direct sensors Fasten the sensor s brass un...

Page 7: ...placed immedi ately after a valve with the exception of block valves ball valve type which must be fully open when not used for blocking F A flow sensor should not be placed at the suction side of a p...

Page 8: ...in horizontal pipelines The meter type plate must always face upwards It is recommended to install shut off valves before and after the meter to facilitate the in stallation and removal of the meter...

Page 9: ...all fitting makes it possible to mount MULTICAL 6M2 direct on an even wall Use the fitting as a template to mark and drill two 6 mm holes in the wall Naturally wall mounting is ideal when mounting in...

Page 10: ...ze liquid and the concen tration are freely programmable and thus MULTICAL 6M2 can compensate for the unique specific heat capacity in each application ensuring a high accuracy regardless of the chemi...

Page 11: ...The polarity of temperature sensors T1 T2 and T3 is unimportant V1 V2 11 11 SIG 10 69 Terminal no Standard heat and cooling measurement T1 5 6 Sensor in inlet red T2 7 8 Sensor in outlet blue V1 11 10...

Page 12: ...ich is not galvanically separated This permits a cable length of max 10 20 m between flow meter and calculator MULTICAL 6M2 11 9 10 Example of connection of MULTICAL 6M2 type no 6M2 H and a flow senso...

Page 13: ...and must not be charged and must not be short circuited for more than 2 sec Used batteries must be handed in for approved destruction e g at Kamstrup A S 7 2 Mains modules The modules are protection c...

Page 14: ...erious error in measuring system or installation INFO is displayed and an info code can be read by activating the main key until the measuring unit says INFO The info code is only displayed when the e...

Page 15: ...scription 10 2 1 2 pulse outputs for CE and CV type 602 0C This top module has two configurable pulse outputs which are suitable for volume and energy pulses for heat meters cooling meters and combine...

Page 16: ...ssible The LON module collects new data from MULTICAL 6M2 in a cycle which secures that all data are updated every 30 seconds 10 2 4 BACnet type 67 00 66 rev J1 or higher The BACnet module communicate...

Page 17: ...elow example the Date has been selected The value of the flashing digit can be changed by pressing the sub key The digit is increased by one each time the key is pressed and passing 9 you start from 0...

Page 18: ...18 Kamstrup A S 55121600_A4_GB_03 2015 MULTICAL 6M2...

Page 19: ...ate followed by energy count on last year s target date Followed by monthly counts Consumed water Latest target date Volume count on latest target date followed by volume count on last year s target d...

Page 20: ...y In this example June 1 The calculator s serial number Followed by program number config 1 and 2 software edition and software checksum Display test Followed by top and base module types Reading of n...

Reviews: