4
Technical data
PowerKon QE
Control signal
[V]
Heat output [W]
Air volume flow
[m³/h]
Nominal current
[A]
Sound pressure
level [dB (A)]
4
Sound power
level [dB(A)]
Weight [kg]
9
Casing length 825 mm, casing height 200 mm, casing width 205 mm
10
800
91
3.5
28
36
15.4-16.7
8
660
86
26
34
6
500
70
21
29
4
320
52
<20
6
<28
6
2
160
43
<20
6
<28
6
Casing length 1250 mm, casing height 200 mm, casing width 205 mm
10
1600
183
7
31
39
21.9-23.8
8
1320
172
29
37
6
1000
139
24
32
4
640
104
<20
6
<28
6
2
320
87
<20
6
<28
6
Casing length 1700 mm, casing height 200 mm, casing width 205 mm
10
2400
274
10.6
33
41
28.9-31.5
8
1980
258
31
39
6
1500
209
26
24
4
960
156
<20
6
<28
6
2
480
130
<20
6
<28
6
4
The sound pressure level was calculated with an assumed room insulation of 8 dB(A). This corresponds to a dis-
tance of 2 m, a room volume of 100 m³ and a reverberation time of 0.5 s (in accordance with VDI 2081).
9
Depending on the grille design
6
Sound pressure level < 20 dB (A) and sound power level < 28 dB (A) outside the usual measuring and audible
range.
Summary of Contents for PowerKon QE
Page 2: ......
Page 15: ...PowerKon QE Assembly installation and operating instructions 15...
Page 16: ...PowerKon QE Assembly installation and operating instructions 16...
Page 17: ...PowerKon QE Assembly installation and operating instructions 17...
Page 18: ...PowerKon QE Assembly installation and operating instructions 18...
Page 31: ...PowerKon QE Assembly installation and operating instructions 31...
Page 33: ......
Page 34: ......
Page 35: ......