4. Installing encased
convectors on finished floors
•
Fix the finished floor brackets
1
using the hexagonal screws
2
supplied to the support plates at both
ends of the PowerKon heat exchanger
3
.
Units longer than 1600mm need a further
bracket
4
with support plate
5
as a
central bracket:
•
Fit the brackets using the hexagonal
screws supplied
6
to the support
plate.
•
Position the brackets and support
plates on the heat exchanger and push
the support plate between the fins of
the heat exchanger so that the heat
exchanger pipes fit into the recesses in
the support plates.
•
Place the heat exchanger with the
brackets fitted onto the floor where
it is to be installed and mark the drill
holes.
•
Fix the brackets using screws and
rawl plugs (by others)
7
onto
the floor and level the unit.
•
Connect up the flow
8
and
return
9
pipework. The 1/2” valve
set type 126102 and the thermostatic
valve head type 110210 from
the Kampmann accessories range can
be used. Fit the air vent
bl
to
the flow connection.
•
Fit the casing
bm
with the valve cut-
outs correctly positioned over the
PowerKon heat exchanger and rotate
the fixing plates
bn
(see detail)
underneath the convector.
Diag. 4 Encased convector; casing height 130 mm, casing depth180 mm