KaControl electrical cabling - BMS control

** Lay shielded, paired cables, e.g. CAT5 (AWG23) of at least the same value, separately from high-voltage cables.
W1: Power supply
W2: Control signal for fan and actuator.
Subject to technical modifications: Refer to the control accessory documentation in the event of deviation from the circuit 
diagrams!

Unterflurkonvektor

Katherm QK nano

Unterflurkonvektor

Katherm QK nano

Mains power 

230 V AC

Fuse by others

Tr

ench heating

Katherm QK nano

Unit no. 1

230 V / KaContr

ol

Tr

ench heating

Katherm QK nano

Unit no. n

230 V / KaContr

ol

Automation station

actuator 

type 146906

actuator 

type 146906

Summary of Contents for Katherm QK 190

Page 1: ...Katherm QK Assembly installation and operating instructions Keep these instructions in a safe place for future use Issue11 22EN SAP No 1666194...

Page 2: ......

Page 3: ...ion 13 5 1 Overview 13 5 2 Brief description 13 6 Installation and wiring 14 6 1 Requirements governing the installation site 14 6 2 Installation 14 6 2 1 Installation steps 14 6 2 2 Screed work 18 6...

Page 4: ...e 3210002 type 3210006 40 10Maintenance 41 10 1 Securing against reconnection 41 10 2 Maintenance Schedule 41 10 3 Maintenance work 42 10 3 1 Clean the inside of the unit 42 11Faults 43 11 1 Fault tab...

Page 5: ...apply as do general safety provisions governing the use of the equipment Illustrations in this guide are intended to provide a basic understanding and may differ from the actual model Ongoing tests a...

Page 6: ...ding s sewage system and power grid The operating limits and limits of use described in Chapter 2 2 6 must be observed Intended use of the unit also includes adherence to these instructions Informatio...

Page 7: ...refer to VDI 2035 Sheets 1 2 DIN EN 14336 and DIN EN 14868 with regard to the properties of the medium used to protect the equipment The following values provide further guidance The water used shoul...

Page 8: ...erate the unit in aggressive or corrosive atmospheres e g sea air Never operate the unit above electrical equipment such as switch cabinets computers or other electrical units or contacts that are not...

Page 9: ...ntion regulations Guidelines and recognised technical regulations i e Association of German Electricians VDE regulations DIN and EN standards VDI 6022 maintenance personnel must be trained to Category...

Page 10: ...ite IMPORTANT NOTE 2 people are needed to transport the unit Wear personal protective clothing when transporting the unit Only lift the unit on both sides and not by the pipes valves IMPORTANT NOTE Ma...

Page 11: ...tions and shocks IMPORTANT NOTE Under certain circumstances packages can carry storage instructions that exceed the requirements listed here Comply with these instructions accordingly 3 4 Packaging Ha...

Page 12: ...41 Sound power level dB A 3 28 49 28 49 Power consumption W 3 6 21 1 3 6 21 1 Current consumption mA 54 173 54 173 Water content l 0 31 1 95 0 42 2 65 Weight kg 11 2 33 6 12 1 37 2 1 at LPHW 75 65 C t...

Page 13: ...5 Eurokonus valve connection 6 Height adjustment feet with sound insulation 7 Floor trench 8 Coil 9 EC fan 10 Roll up grille example 5 2 Brief description Katherm QK are decentralised units for the he...

Page 14: ...flow and return water connections on site Connection to the pipe network 20 There is a power supply on site Maximum electrical rating values 24 If need be provide a condensation connection with a suff...

Page 15: ...Katherm QK Assembly installation and operating instructions 15 6 2 1 Installation steps...

Page 16: ...Katherm QK Assembly installation and operating instructions 16...

Page 17: ...Katherm QK Assembly installation and operating instructions 17...

Page 18: ...tion covers to protect the trenches from dirt are rolled up in the factory The grille can become slightly over long due to the steel springs extending Unrolling the grille and laying it flat for a few...

Page 19: ...coverings Cover the grille and floor trench with the transparent installation cover to protect the trench from dirt or cement 6 3 Installation Actuator with First Open function When delivered the actu...

Page 20: ...thout cover panel Window side Window side Room side Room side 1 Flow 2 Return 3 Valve body straight type 346909 pre settable 4 Thermoelectric actuator 24 V type 146906 5 return shut off valve straight...

Page 21: ...Window side Window side Room side Room side 1 Flow 2 Return 3 Valve body straight type 346909 pre settable 4 Thermoelectric actuator 24 V type 146906 5 return shut off valve straight type 145952 6 Uni...

Page 22: ...r spigot 2 Connecting brackets 3 Supply air slider 4 Reinforcing struts 5 Perforated plate 6 Filter 7 Example of Optiline roll up grille 8 Kampmann QK shown with Optiline roll up grille 9 Slider Trenc...

Page 23: ...slider position The height of the supply air module is adjusted using the threaded rods and connected by the installation brackets to the sub strate The slider can be moved into different positions to...

Page 24: ...IP00 I 2600 230 50 17 0 15 200 IP00 I 2800 230 50 18 4 0 15 200 IP00 I 3000 230 50 19 8 0 16 200 IP00 I 3200 230 50 21 2 0 17 200 IP00 I Tab 5 Maximum electrical rating values Katherm QK Katherm QK 24...

Page 25: ...230 50 21 2 0 17 20 IP00 I Tab 7 Maximum electrical rating values Katherm QK 7 2 Electromechanical connection 24 V 24 Note these points in the following wiring diagrams with electromechanical control...

Page 26: ...d control signal for on site fuse 0 63 A and actuator Subject to technical modifications Refer to the control accessory documentation in the event of deviation from the circuit diagrams Trench convect...

Page 27: ...es W1 Voltage supply and control signal for fan on site fuse 0 63 A and actuator W2 Voltage supply and control signal for fan and actuator W3 Voltage supply fuse by others Central voltage supply 24 V...

Page 28: ...nductor is stated on the cable Cross sections are not stated as the cable length is involved in the calculation of the cross section With J Y ST Y 0 8mm Lay separately from high voltage lines If other...

Page 29: ...efer to the control accessory documentation in the event of deviation from the circuit diagrams 3 W1 W2 4 Automationsstation DI Netz 230 VAC Absicherung bauseits Bodenkanal Katherm QK nano 230 V 0 10...

Page 30: ...er optional Subject to technical modifications Refer to the control accessory documentation in the event of deviation from the circuit diagrams Trench convector Katherm QK 24 V 0 10 V DC Max 10 units...

Page 31: ...t KaControl unit in line with the wiring diagram The maximum bus length between the KaController and the KaControl master unit is 30 m The respective KaControl automatically becomes the master unit in...

Page 32: ...low voltage and bus cables Lay all BUS cables in a linear pattern Star shaped wiring is not permitted The KaController is connected via a bus connection to the respect ive control PCB on the unit Rig...

Page 33: ...other types of cables are used they must be at least equivalent Length of the BUS line from the KaController to unit 1 max 30 m Maximum number of parallel units 6 units CANbus cards type 3260301 neede...

Page 34: ...of deviation from the circuit diagrams W6 W6 KaController 24 V Type 3210001 or type 3210002 Trench heating Katherm QK nano Unit no 6 230 V KaControl Trench heating Katherm QK nano Unit no 2 230 V KaC...

Page 35: ...t to technical modifications Refer to the control accessory documentation in the event of deviation from the circuit diagrams Unterflurkonvektor Katherm QK nano Unterflurkonvektor Katherm QK nano Main...

Page 36: ...eck all external electrical connections and terminal connections are fixed in place and tighten if necessary Check whether DIP switches have been correctly set in accordance with the wiring diagram Wa...

Page 37: ...e applications surface mounted wall installation on a flush mounted box in visually unobtrusive design operation using 4 sensor keys timer with automatic summer winter switch over option for external...

Page 38: ...tion 7 MODE button Set operating modes disabled with 2 pipe applications 8 FAN button Set fan control 1 2 Fig 10 KaController type 3210001 KaController without operating keys one button operation type...

Page 39: ...t room temperature 2 Current time 3 Timer program enabled 4 Weekday 5 Alarm 6 Selected function is locked 7 External ventilation mode is locked 8 Filter alert 9 Eco mode 10 Setpoint setting enabled 11...

Page 40: ...Time setting Time setting Time setting Adjust the current time by turning and pressing the navigator dial Timer programs Timer programs Timer programs Adjust the switching times by turning and pressin...

Page 41: ...2 Maintenance Schedule The sections below describe maintenance work needed for the proper and trouble free operation of the equipment If there are signs of increased wear during regular checks shorten...

Page 42: ...ns 42 10 3 Maintenance work 10 3 1 Clean the inside of the unit Check all elements that come into contact with air internal surfaces of the unit outlet elements etc for dirt or deposits dur ing mainte...

Page 43: ...t exchanger if you need to Hydraulic connection not properly done Check flow and return and tighten if necessary Unit not heating or cooling sufficiently LPHW CHW Fan is not switched on Switch on fan...

Page 44: ...ature sensor in the KaController faulty tAL3 Real time clock in the KaController faulty tAL4 EEPROM in the KaController faulty Cn Communication fault with the external control Tab 11 KaController alar...

Page 45: ...ration of KaController sensor 0 60 60 C t006 LCD display contrast 15 0 15 t007 BEEP setting 0 BEEP ON 1 BEEP OFF 0 0 1 t008 Password for KaController Parameter menu 11 0 999 t009 Minimum settable setp...

Page 46: ...Katherm QK Assembly installation and operating instructions 46 13 Certificates...

Page 47: ...Typ Model slo v robku auf das sich diese Erkl rung bezieht mit der den folgenden Norm en oder normativen Dokumenten bereinstimmt to which this declaration relates is in conformity with the following...

Page 48: ...U Niederspannungsrichtlinie Hendrik Kampmann Lingen Ems den 01 09 2020 ___________________________________ Ort und Datum der Ausstellung Name und Unterschrift des Befugten Place and Date of Issue Name...

Page 49: ...3 Water quality 7 Tab 4 Technical data Katherm QK supply air module 22 Tab 5 Maximum electrical rating values 24 Tab 6 Maximum electrical rating values 24 Tab 7 Maximum electrical rating values 25 Ta...

Page 50: ......

Page 51: ......

Page 52: ...oducts trench technology katherm qk Country Contact Great Britain Kampmann UK Ltd Dial House Govett Avenue Shepperton Middlesex TW17 8AG T 44 1932 228592 F 44 1932 228949 E info kampmann co uk W Kampm...

Reviews: