Katherm HK

Assembly instructions

7

5

Pre-commissioning checks

Before initial commissioning, check whether all the necessary conditions have been met so that
the unit can function safely and properly.

Electrical tests

Check whether all lines have been properly laid.

Check whether all lines have the necessary cross-section.

Are all wires connected in accordance with the electric wiring diagrams?

Is the earth wire connected and wired throughout?

Check all external electrical connections and terminal connections are fixed in place and
tighten if necessary.

Check whether DIP switches have been correctly set in accordance with the wiring diagram.

Water-side checks

Check whether all supply and drainage lines have been properly connected.

Fill pipes and unit with water and bleed.

Check whether all bleed screws are closed.

Check leak tightness (pressure test and visual inspection).

Check whether the parts carrying water have been flushed through.

Check whether any shut-off valves fitted on site are open.

Check whether any electrically actuated shut-off valves have been properly connected.

Check whether all valves and actuators are working properly (note permitted mounting pos-
ition).

Condensation water connection

Check whether the condensation tray is free of building rubble.

Check the condensation drain and operation of the alarm signal on the condensation pump.

Check whether the cooling valve switches off in the event of an alarm signal.

Check whether the unit is connected leak-free to the on-site condensation connection.

Check whether the waste water lines are clean and have a sufficient gradient.

Check whether the condensation pump has a working power supply.

6

Cleaning the condensate tray

1

2

2

4

4

4

5

5

6

7

3

Remove the grille 

1

.

Remove the cover plates 

2

.

Loosen the clip from the condensate elbow and remove the condensate elbow from the drain
connection of the condensate tray 

3

.

Loosen the segment panel screws and the segment panels 

4

 from the brackets on the walls

of the floor trench.
Remove the motor connection plug from the tangential fan.
Remove the tangential fan from the fixing bolts 

5

 of the central wall 

6

.

Loosen the screws of the central wall 

6

 and remove the central wall from the trench.

Pull the condensate tray arranged below the condensate tray 

7

 to the room side of the

trench. Note: The condensate tray cannot be removed!
Use a damp cloth to clean the condensate tray 

7

 and then wipe away any damp patches

with a dry cloth.
After cleaning the condensate tray, refit the parts in reverse order to dismantling them.

Summary of Contents for Katherm HK

Page 1: ...NWEIS Gefahr bei Fehlgebrauch Bei Fehlgebrauch in untenstehenden Einsatzbereichen besteht die Gefahr der ein geschr nkten bzw ausfallenden Funktion des Ger ts Der Luftstrom muss unge hindert zirkulier...

Page 2: ...nschlagpunkte verwenden Verpackungen erst kurz vor der Montage entfernen 4 Montage und Anschluss 4 1 Voraussetzungen an den Aufstellort Das Ger t nur montieren wenn folgende Bedingungen erf llt sind D...

Page 3: ...frei arbeiten zul ssige Einbaulage beachten Kondensatwasseranschluss Pr fen ob die Kondensatwanne frei von Bauschmutz ist Kondensatabfuhr und Verarbeitung der Alarmmeldung bei Kondensatpumpe pr fen Pr...

Page 4: ...se beachten Beim Montieren des seitlichen Niederhalters f r die Kondensatwanne darauf achten dass der Niederhalter die Kondensatwanne gegen Hochdr cken und seitlich gegen Verschieben si chert Beim Wie...

Page 5: ...ct the unit from frost IMPORTANT NOTE Warning of misuse In the event of misuse as itemised below there is a danger of limited or failing operation of the unit Ensure that the airflow can circulate fre...

Page 6: ...use the holding points provided Only remove packaging shortly before assembling the unit 4 Installation and wiring 4 1 Requirements governing the installation site Only install and assemble the unit...

Page 7: ...pos ition Condensation water connection Check whether the condensation tray is free of building rubble Check the condensation drain and operation of the alarm signal on the condensation pump Check wh...

Page 8: ...tray once it has been cleaned When inserting the side retainer for the condensate tray make sure that the retainer prevents the condensate try from pushing up and moving sidewards When reinserting th...

Page 9: ...l AVERTISSEMENT Danger en cas d utilisation incorrecte En cas d utilisation incorrecte dans les secteurs d utilisation mentionn s ci des sous l appareil risque de fonctionner moins bien voire de ne pl...

Page 10: ...igurant sur l emballage Utiliser uniquement les points de fixation pr vus cet effet Attendre le moment du montage pour retirer l emballage 4 Montage et raccordement 4 1 Conditions sur le site d instal...

Page 11: ...tement respecter la position de montage autoris e Raccord d eau de condensation V rifier que le collecteur d eau de condensation n a pas t sali pendant les travaux V rifier l vacuation de l eau de con...

Page 12: ...e du bac condensat Lors du montage du dispositif de retenue lat ral pour le bac de condensat veiller ce que le serre flan emp che le bac de condensat de se soulever et de se d placer lat ralement Lors...

Page 13: ...A Pericolo di utilizzo errato In caso di utilizzo errato negli ambiti indicati sotto sussiste il pericolo di funziona mento limitato o malfunzionamento dell apparecchio Il flusso d aria deve poter cir...

Page 14: ...i punti di aggancio previsti Rimuovere gli imballaggi solo poco prima del montaggio 4 Montaggio e collegamento 4 1 Requisiti per il luogo di installazione Montare l apparecchio solo se le condizioni s...

Page 15: ...gio ammessa Attacco acqua di condensa Verificare se la vaschetta di raccolta della condensa priva di sporcizia da montaggio Verificare lo scarico della condensa e l elaborazione del messaggio di allar...

Page 16: ...lta condensa Durante il montaggio del premilamiera laterale per la vaschetta di raccolta condensa accer tarsi che il premilamiera impedisca alla vaschetta di sollevarsi e spostarsi lateralmente Durant...

Page 17: ...vaar bij verkeerd gebruik Bij verkeerd gebruik in de onderstaande situaties bestaat het gevaar dat het ap paraat slechts beperkt werkt of uitvalt De luchtstroom moet onbelemmerd kun nen circuleren Geb...

Page 18: ...Gebruik alleen de daarvoor bestemde aanslagpunten Verwijder verpakkingen pas kort v r de montage 4 Montage en aansluiting 4 1 Voorwaarden voor de opstelplaats Monteer het apparaat alleen wanneer aan...

Page 19: ...jvingen goed werken let op de toegestane inbouwpositie Condensaataansluiting Controleer of de condensaatbak geen bouwafval bevat Controleer de condensaatafvoer en verwerking van de alarmmelding bij de...

Page 20: ...let Bij het monteren van de aandrukker aan de zijkant voor de condensaatbak moet men erop letten dat de aandrukker de condensaatbak tegen omhoog drukken en zijwaarts tegen ver schuiven beveiligt Bij h...

Page 21: ...WSKAZ WKA Zagro enie na skutek nieprawid owego u ytkowania W przypadku nieprawid owego u ytkowania w podanych poni ej zakresach za stosowania zachodzi ryzyko ograniczenia dzia ania lub awarii urz dze...

Page 22: ...osowa wy cznie punkty mocowania przeznaczone do tego celu Opakowanie zdj dopiero bezpo rednio przed monta em 4 Monta i pod czenie 4 1 Wymagania wzgl dem miejsca monta u Urz dzenie montowa wy cznie wte...

Page 23: ...d owo pod czo ny sprawdzi czy wszystkie zawory i si owniki pracuj prawid owo zwr ci uwag na dopusz czaln pozycj monta ow Przy cze kondensatu sprawdzi czy wanna kondensatu jest wolna od zanieczyszcze b...

Page 24: ...ny kondensatu Podczas monta u bocznego elementu dociskowego wanny kondensatu nale y zwr ci uwag na to aby element dociskowy zabezpiecza wann kondensatu przed wypchni ciem do g ry i przesuni ciem w bok...

Page 25: ...m HK E Katherm HK 1 2 3 4 5 6 EC 7 8 9 10 11 2 QR EN 60335 1 2 1 2 2 25 2 2 C 5 120 C 15 40 15 75 10 1000 25 50 230 50 60 2 3 2 4 VDE DIN EN VDI 6022 B C Kampmann GmbH Co KG Friedrich Ebert Str 128 13...

Page 26: ...Katherm HK 26 2 5 3 3 1 Kampmann 2 4 4 1 4 2 4 3 29...

Page 27: ...Katherm HK 27 5 DIP 6 1 2 2 4 4 4 5 5 6 7 3 1 2 3 4 5 6 6 7 7...

Page 28: ...Katherm HK 28...

Page 29: ...29...

Page 30: ...30 Katherm HK 290 160 mm Katherm HK 360 210 mm Katherm HK 320 130 mm Katherm HK 320 E 130 mm Katherm HK 245 160 mm...

Page 31: ...31 bauseits Dehnfuge bauseits...

Page 32: ...32...

Reviews: