Observe these points in the following layout plans with KaControl:
Comply with the details on cable types and cabling with due consideration of VDE 0100.
Without *: NYM-J. The requisite number of wires, including PE conductor, is stated on the cable. Cross-sections are not
stated, as the cable length is involved in the calculation of the cross-section.
With *: J-Y(ST)Y 0.8mm. Lay separately from high voltage lines.
With **: Lay UNITRONIC BUS LD 0.22 mm² or similar separately from high voltage lines.
If other types of cables are used, they must be at least equivalent.
Length of the BUS line from the KaController to unit 1: max. 30 m.
Maximum number of parallel units: 6 units. With CANbus card type 3260701 needed for each unit (see accessories) max-
imum 30 no.
Length of bus line from unit 1 to the last unit max. 30 m. The cable length can be increased to maximum 500 m with a
CANbus card per unit type 3260701 (see accessories).
The terminals on the unit for the mains power supply are suitable for a maximum wire cross-section of 2.5 mm².
All RCCBs used must at least be mixed frequency-sensitive (type F). Refer to the provisions of DIN VDE 0100 Parts 400
and 500 when designing the rated fault current.
Note the electrical data when rating the in-situ mains power supply and fuse (C16 A, max. 10 units).