KaDeck
Assembly, installation and operating instructions
19
Fig. 9: Design panel open
Release the design panel downwards.
CAUTION:
When opening/removing the
design panel, do NOT allow the opening angle to exceed 90° to prevent dam-
age!
Fig. 10: Unlocking hinges
Unlock the hinges on the right and left by pulling on them and remove the
design panel.
6.5
Installation
Actuator with ‘First Open’ function
When delivered, the actuator is normally open in a de-energised state, thanks to the First Open function. This enables
heating mode to run even if the electric wiring is not yet completed.
When subsequently commissioned and with the application of power (for longer than 6 minutes), the First Open function
is automatically unlocked so that the actuator becomes fully operational.
0,5 mm
> 0,5 mm
< 0,5 mm
Power on
> 6 min
Power off
Fig. 11: “First Open” function