41
Airblock FG
1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
11.2 Installation
The Airblock housing
5
has four suspension points
1
as standard as
screwable mounting brackets with a slot fixing for universal installation.
All Airblock modules are suitable for the installation of accessories
or attachments with standard duct connection profiles thanks to the
connecting flange with several fixing holes.
• Seal all joints with sealing tape. Screws and sealing tape are included in
the delivery.
• Several Airblock filter or chiller modules can be screwed together from
the inside using the connection sets included.
• Make sure that there is adequate working space for the operation and
maintenance of the respective Airblock modules and attachments when
installing the units. This applies in particular to the connection side area
(electrical connection
2
etc.).
• Provide rubber pads on site to decouple noises.
• Align the unit in a horizontal position.
• Note: The filter
3
can only be removed from below for maintenance
purposes!
Note:
Service hatches are to be provided on site below and alongside
the modules (connection side) for the installation and maintenance of the
Airblock modules!