32
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
9.4.5 Filter Change
Observe the safety information on page 27 + 28, sections 9.4.1 and 9.4.2!
Filter cartridge in a Fiberplast frame
13
(filter class: ISO ePM10 70% for
exhaust air and ISO ePM2,5 65% for fresh air as per DIN EN 779).
• Check the filter cartridges
13
at least once a year (more often if necessary).
The filter cartridge must be changed if it is dirty.
• Open the service hatches
4
and unlock the safety catches. Then pull out
the filter cartridges downwards or upwards. The filter must be moved
past the service hatch when the service hatches are fully opened to the
bottom (swivel range = 1780 mm). To do this, the slide-in rail in which
the filter sits can be swivelled 10°. The filter can be pulled out easily in a
downward direction in a swivelled state (see dimension 1780 mm). Use a
collection bag if necessary to avoid dirt and dust dropping down.
• This filter folds in the middle with model 9 units. This makes it easier to
remove and it can be folded to save space with disposal so that very little
dirt can drop out.
• Push the replacement filter cartridge into the filter opening and lock the
filter catches. Replacement filter cartridges are available as accessories.
Filter cartridges cannot be recycled.
•
Caution:
Swivel the filter holder back into the vertical position before
closing the service hatches!
• Dispose of the dirty filter. Filter cartridges are metal-free and fully
incinerable.
0 - 20°
X
X
1780
0 - 10°
X
X
1780
Summary of Contents for Airblock FG 06
Page 51: ......