26
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
9.2 Installation
The Airblock housing
5
has six suspension points
1
as standard as screwable
mounting brackets with a slot fixing for universal installation. All Airblock
modules are suitable for the installation of accessories or attachments with
standard duct connection profiles thanks to the connecting flange with
several fixing holes.
The heat recovery module has a condensation tray
10
with a gradient on all
sides and a condensation drain connection on the side
11
.
• Align the unit in a horizontal position!
• Any condensation produced has to be drained off individually or through
a collecting line via the siphon connected to the condensation drain
connection.
• Condensation must be able to drain freely. Make sure that the
condensation drain connection has an appropriate free area.
• Lay a condensation line without any kinks or restrictions with a gradient
to the sewage pipe on site.
• Choose the correct condensation line diameter.
• Protect the siphon in the condensation line against drying out (use a ball
siphon if necessary).
Note:
Service hatches are to be provided on site below and alongside
the modules (connection side) for the installation and maintenance of the
Airblock modules!
Note:
The filters
13
can be removed from above and below for maintenance
purposes!
Heat Recovery Module
Model
Length L
[mm]
Width W
[mm]
Height H
[mm]
Weight
[kg]
Model 6
1600
1640
390
211
Model 7
1600
2040
390
237
Model 8
1900
2040
490
322
Model 9
1900
2440
490
361
All dimensions are external dimensions.
Module dimensions