27
Airblock FG
1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
Sealing water height Hs
Condensation drains
• A siphon needs to be connected to all available condensation drain
connections.
• Ensure an adequate sealing water height (Hs) (see adjacent Fig.)
Sealing water height:
Hs = H + 50 mm
H = static negative pressure in the unit (mm H
2
O)
(1 mm H
2
O = 9.81 Pa)
Min. water trapp height = 60 mm
9.3 Control Components
Please refer to the enclosed technical information for technical data on the
following accessories delivered separately or fitted at the factory.
9.4 Maintenance
Observe the maintenance intervals prescribed by the legislature. The intervals
are dependent on various factors (e.g. structural conditions, level of dirt,
etc.) and may therefore differ from the manufacturer‘s recommendations.
If an increased level of dirty is detected during regular checks, adjust the
required maintenance intervals according to the actual wear and tear.
Description of accessory
Type suffix for
Airblock type
Type of accessory/
spare part supplied
separately
Enclosed technical
information from
manufacturer
Filter differential pressure switch, for use with supply air module
type **300300, chiller module type **302140, heat recovery
type **301700, particle filter module type ** 303130 and bag
filter module type **303170
...00D
30267
Filter differential pressure transmitter
...00P
enclosed
A 24 V power supply is also required for the operation of a filter differential pressure transmitter.