8.2
Explanation and Applications of Relay Connector
Type
Pin #
Gi ON
Gi OFF Remarks:
Applications:
Relay-
contact
1
2
Max. 230 V, 2A cos(ɸ1).
Turning on/off an external
fan, light, or gas supply.
Safety Contact 3
4
The Gi checks the status of this input; it must be
closed before the start of the ignition cycle and
during the operational status of the Gi. If it is opened,
the Gi is deactivated, and a fault error is generated,
putting the Gi in a lockout status. This is
automatically reset when the input is closed.
Shut Down Switch, door
contact switch, extractor
hood, mechanical ventilation,
negative pressure sensor,
hotel switch
Safety Contact 5
6
The Gi checks the status of this input; it must be
closed before the start of the ignition cycle and
during the operational status of the Gi. If it is opened,
the Gi is deactivated, and a fault error is generated,
putting the Gi in a lockout status. This is
automatically reset when the input is closed.
Shut Down Switch, door
contact switch, extractor
hood, mechanical ventilation,
negative pressure sensor,
hotel switch.
Safety Contact 7
8
The Gi monitors the status of this input; it must be
closed before the start of the ignition cycle and
during the operational status of the Gi. If it is opened,
the Gi is deactivated, a fault error is generated, and
the Gi enters a lockout status. A manual RESET is
required.
Carbon monoxide sensor,
gas
leak detection sensor.
Summary of Contents for Gi75/59F
Page 1: ...INSTALLATION INSTRUCTIONS Balanced flue gas systems...
Page 2: ......
Page 45: ...45...
Page 46: ...46...
Page 47: ...47...
Page 49: ...49...
Page 50: ...50...
Page 51: ...51...
Page 52: ...52...
Page 53: ...53...
Page 54: ...54...
Page 59: ...59...
Page 60: ...Gelo rveldweg 21 5951 DH Belfeld info kalfire com KALFIRE COM V12 2023 EN...