Error 

code

Error name

Relevant 

parts information

Review and resolve

E04

Electric heater over heat 
Protection

1. Check the Electrical heating Overheat protector open or not.

 

2. Check the Electrical heater.

E08

Communication failure 

between PCB and display

Communication error 

between PCB and DISPLAY

1. Check cable connection of PCB and DISPLAY.

 

2. Check the software version of PCB and DISPLAY.

E11

HP Protection

HP switch is open

1. Check whether showing the error after unit shutdown.

 

2. Measure the discharge pressure when unit is running.

 

3. Detect EEV step, suction pressure, inlet/outlet water discharge and suction temp.

 

4. Release all the gas of the system and refill refrigerant according to the nameplate.

E12

LP Protection

LP switch is open

1. Check whether showing the error after unit shutdown.

 

2. Measure the suction pressure when unit is running.

 

3. Detect EEV step, discharge pressure, inlet/outlet water discharge and suction temp.

 

4. Release all the gas of the system and refill refrigerant according to the nameplate.

E19

Primary Anti-freezing 

Protection

Ambient temp.≤0°C, A04-
2°C≤ water inlet≤A04°C

It is the protection in winter. Once the water temperature rises up to A04+4oC or the 
ambient temp is higher than 1, the error code disappears.

E29

Secondary Anti-freezing 

Protection

Ambient temp.≤0°C, water

 

inlet≤A04-2°C

It is the protection in winter. Once the water temperature up to A04+11 oC or the 
ambient temp is higher than 1, the error code disappears.

E19

Primary Anti-freezing 

Protection

Ambient temp.≤0°C, 2°C ≤ 
water inlet≤4°C

It is the protection in winter. Once the water temperature rises up to 8 oC or the 
ambient temp is higher than 1 oC, the error code disappears.

E29

Secondary Anti-freezing 

Protection

Ambient temp.≤0°C, water

 

inlet≤2°C

It is the protection in winter. Once the water temperature up to 15 oC or the ambient 
temp is higher than 1

 

oC, the error code disappears.

E032

Flow Switch Protection

Flow switch is open

1. Detect the connection of cables.

 

2. Detect the flow switch.

 

3. Detect the water valve is opened or opened fully.

 

4. Detect the water pump and the filter.

 

5. Maybe there is some air in the water route.

E051

Compressor Over current 

Shutdown Fault

Compressor Over current

1. Check ambient temp. and inlet/outlet water temp.;

 

2. Turn on the unit. Record and analyze the changing process of high/low pressure, 
discharge/suction temp., EEV step, compressor frequency and running current.

 

3. If they are OK, replace a new compressor driver board.

E065

High water outlet temp. 

protection

Check if the water flow is too low and the outlet water whether too high

E081

Communication failure 

between PCB and fan 

drive board

Communication error 

between PCB and fan drive 

board

1. Check the connection between PCB and fan board. All of 12V-12V, GND-GND, A-A, 
B-B should be closed;

 

2. If they are closed, turn on the power, then measure the voltage between 12V and 
GND on fan board, if higher than 15V or lower than 7V, replace a new fan board.

E103

Fan motor overload 
protection

1. Check if the fan motor running well.

 

2. Detect the current of fan motor.

 

3. If the current is more than 1A, it means the motor have problem and need 

to replace a new one. 

4. If the current is less than 1A, it means the motor control module have problem 

and nee to replace a new one.

E171

Anti-freezing Protection

inlet water ≤A04°C and the 
antifreeze temp ≤

 

A04-A05°C

1. Check the water flow.

 

2. Check the outlet water temp sensor.

 

3. Measure the ambient temp.

 

4. Detect the connection of cables.

 

5. Check the record of defrosting, whether the defrosting time is too long 

or too often.

7.2.

 Error Code Instruction

Summary of Contents for KHX-14PY3

Page 1: ...OWNER SMANUAL AIR TO WATER HEAT PUMP EN R290...

Page 2: ......

Page 3: ...ENNY TYPU SPLIT Instrukcja obs ugi Dzi kujemy za wyb r naszego produktu Dla zapewnienia prawid owej obs ugi zapoznaj si z instrukcj i przechowuj j do wykorzystania w przysz o ci W przypadku zagubienia...

Page 4: ...Content 1 Preface 5 2 Safety Instructions 6 3 Features 9 4 Unit Dimension mm 10 5 Parameters 11 6 Display Operation Guide 12 7 Failure List Troubleshooting 23...

Page 5: ...tions are adhered to at all times to keep the warranty The unit can only be opened or repaired by a qualified installer or an authorized dealer Maintenance and operation must be carried out according...

Page 6: ...der stand the following information correctly Mark Notes Icon Notes Mark Meaning A wrong operation may lead to death or grievous injury on people A wrong operation may lead to harm to people or loss o...

Page 7: ...rong or strange smells the power supply needs to be shut off to stop the unit Continue running may cause short circuit or fire Move and Repair Meaning Entrust When the heat pump needs to be moved or i...

Page 8: ...ANNOT be installed near the flammable gas Once there is any leakage of the gas fire may occur Fix the unit Make sure that the basement of the heat pump is strong enough to avoid any decline or fall do...

Page 9: ...pump Centralized controlling system can control several units by PC 3 2 Nice Appearance The heat pump is designed with beautiful looking The monoblock one has the water pump included which is very ea...

Page 10: ...nsion mm 4 1 Models KHX 14PY3 4 2 Models KHX 16PY3 Power line Power line Signal line Signal line Water outlet 1 Water outlet 1 238 363 928 458 540 500 125 1287 1250 975 216 Water inlet 1 Water inlet 1...

Page 11: ...put Range kW 1 27 4 65 1 90 7 10 Hot Water Current Input Range A 2 4 8 21 3 4 12 5 Max Power Input kW 5 3 9 Max Current Input A 10 5 15 8 Water Flow m3 h 1 7 2 9 Refrigerant Proper Input kg R290 0 85k...

Page 12: ...12 6 Display Operation Guide 6 1 Main Interface Display and Function 1 Power on Interface 2 Starting up Interface 13 12 11 10 9 8 7 14 15 6 5 4 3 2 1...

Page 13: ...er tapping this icon 9 is defrosting icon It will display in the defrosting process of the unit 10 is timing mute icon which displays only when activated 11 is timing switch which displays only when a...

Page 14: ...OFF 1 In shutting down interface on off key is in white status press on off key can start up the machine 2 Instartingupinterface on offkeyisinbluestatus presson offkey canshut downthemachine 6 2 1 Mo...

Page 15: ...ll not be displayed b If the machine model you purchased has no hot water function the key of hot water mode function will not be displayed In the main interface there are five modes that can be selec...

Page 16: ...interface to return to the main interface The function setting interface is shown in the figure below Take hot water heating mode for example 1 Tapping 1 the wire controller back to main interface 2...

Page 17: ...2 Factory parameter Click the key and enter the password to enter the factory parameter settings and status parameters interface 3 Curve key Click this key to view the temperature curve 4 Adjust brig...

Page 18: ...has been locked the pop up keyboard is shown as following When entering the page of system time setting the system time will be initialized to the time at the moment when the system time setting butt...

Page 19: ...to enable or disable the mute timer off function 2 The mute timer on setting point select from 0 00 23 59 The mute timer off settingpoint select from 0 00 23 59 3 The status of mute timer on Enable B...

Page 20: ...ion records the water inlet temperature water outlet temperature tank water temperature and ambient temperature 2 Temperature data is collected and saved every five minutes Timekeeping is made from th...

Page 21: ...y bar can be dragged or clicked to adjust the brightness of the screen with power down memory 2 Press the back key to return to the previous level and save the brightness setting value 3 The screen ha...

Page 22: ...to return to the main interface The status interface is shown in the figure below 1 Fault code 2 Fault name 3 Occurrence time of the fault Day an month hour minute second Note Ifthecurrenttemperaturei...

Page 23: ...the display whether shown locked icon Check the cable Reconnect the power cable and check if it works Heating effect is not good The compressor running low frequency The fan is not running or speed is...

Page 24: ...Anti freezing Protection Ambient temp 0 C water inlet 2 C It is the protection in winter Once the water temperature up to 15 oC or the ambient temp is higher than 1 oC the error code disappears E032...

Page 25: ...lure between DSP and PFC Only in single phase unit 1 Check the inverter board connection 2 If no problem replace a new compressor driver board F11 Communication Fault between DSP and Com munication bo...

Page 26: ...art and check if the motor is running normal or the error happens again 3 Replace a new fan motor F032 DC Fan Motor 2 Failure Pp1 Exhaust Pressure Sensor Fault 1 Detect the exhaust pressure sensor con...

Page 27: ...V 202109HH01 NOTES...

Page 28: ...kaisai com...

Reviews: