Product Features
8
• If any one of the following conditions is satisfied,
defrosting ends and the machine switches to normal
heating mode:
• T3 rises above TCDE1+4
°C
.
• T3 maintained above TCDE2+4°C for 80 seconds.
• Unit runs for 15 minutes consecutively in defrosting
mode.
3.5.5 Evaporator Temperature Protection
• Off: Compressor stops.
• Decrease: Decrease the running frequency to the lower
level per 20 seconds.
• Hold: Keep the current frequency.
• Resume: No limitation for frequency.
3.6 Auto-mode
• This mode can be selected with the remote controller
and the setting temperature can be changed between
16°C~30°C
.
• In auto mode, the machine selects cooling, heating,
auto-drying or fan-only mode on the basis of T1,Ts, T4
and relative humidity.
• If the setting temperature is modified, the machine
selects a new running function.
3.7 Drying mode
• In drying mode, AC operates the same as auto fan in
cooling mode.
• All protections are activated and operate the same as
they do that in cooling mode.
• Low Room Temperature Protection
If the room temperature is lower than 10°C, the
compressor ceases operations and does not resume until
room temperature exceeds 12°C.
3.8 Forced operation function
• Forced cooling mode:
The compressor and outdoor fan continue to run(fixed at
rated frequency), and the indoor fan runs at rated speed.
After running for 30 minutes, the AC will switch to auto
mode with a preset temperature of 24°C.
• Forced auto mode:
Forced auto mode operates the same as normal auto mode
with a preset temperature of 24°C.
• The unit exits forced operation when it receives the
following signals:
• Switch on
• Switch off
• Timer on
• Timer off
• Sleep mode
• Follow me
• Changes in:
• mode
• fan speed
• setting temperature
• Forced defrosting mode:
• Press AUTO/COOL button continuously for 5s
under forced cooling mode to enter this mode.
• Indoor fan will stop, defrosting lamp will light on.
• Quit this mode and turn off the unit when:
• quit normal defrosting
• turn off by RC
• Press AUTO/COOL button continuously for 5s
again
3.9 Timer function
• Timing range is 24 hours.
• Timer on. The machine will turn on automatically
Summary of Contents for ICE Series
Page 1: ...SPLIT TYPE AIR CONDITIONER Service Manual ICE series...
Page 2: ......
Page 5: ...Contents 1 Precautions 2 2 Information servicing For flammable materials 3 Safety Precautions...
Page 17: ......
Page 19: ...Outdoor unit wiring diagram 16022000019533...
Page 20: ......
Page 21: ...Outdoor unit printed circuit board diagram 17122000048121 17122000046453...
Page 61: ...Outdoor Unit Disassembly 3 2 Dimension 2 1 Panel Plate X130...
Page 62: ...Outdoor Unit Disassembly 4 For US models Rounded grille...
Page 63: ...Outdoor Unit Disassembly 5 2 2 Panel Plate X230...
Page 64: ...Outdoor Unit Disassembly 6 For US models Rounded grille...
Page 65: ...Outdoor Unit Disassembly 7 For US models Square grille...
Page 66: ...Outdoor Unit Disassembly 8 2 3 Panel Plate X330...
Page 67: ...Outdoor Unit Disassembly 9 For US models Rounded grille...
Page 68: ...Outdoor Unit Disassembly 10 For US models Square grille...
Page 69: ...Outdoor Unit Disassembly 11 2 4 Panel Plate X430...
Page 70: ...Outdoor Unit Disassembly 12 For US models Rounded grille...
Page 71: ...Outdoor Unit Disassembly 13 For US models Square grille...
Page 72: ...Outdoor Unit Disassembly 14 2 5 Panel Plate D30...
Page 73: ...Outdoor Unit Disassembly 15 For US models...
Page 122: ...Troubleshooting 15...
Page 167: ......
Page 168: ...kaisai com...