background image

4

GB

APPLICATION CONDITIONS

Support Frame

Several different types are available, depending 
on the desired installation.
The structures supplied support snow loads of 
1200 Pa  and wind loads of  900 Pa (130 km/h)If 
necessary, request the assistance of an expert in 
structural loads.

Support Structure:

Qualified  person  to  inspect  and  ensure  that 
the  installation  structure  can  support  the 
installation  of  the  support  frame  and  solar 
system. Strengthening of the structure may be 
required.

Maximum operating pressure

The  collector  has  a  maximum  operating 
pressure of 8 bar.

Minimum and maximum angle of inclination

The collector can be installed with an inclination 
of between 15° and 35°. 

All collector connections 

and  breather  holes  must  be  protected  from 
infiltration of water and dirt.

Collector inclination will normally be determine 
by  the  roof  pitch,  or  the  pitch  of  the  support 
frame used. Please refer to the specific mounting 
system for more information.

Formation of condensation

Early in the morning or late in the afternoon, the 
glass on the panel may steam up on the inside 
or experience condensation on the outside.
The damper the air, the greater the likelihood of 
condensation occurring.
If  it  does  form,  the  condensation  should 
gradually  disappear  as  soon  as  suitably  sunny 
conditions are created.
The  phenomenon  does  not  jeopardize  the 
correct operation of the system.

Transportation and handling

•  The  solar  collector  should  be  transported 

in  an  upright  position,  avoiding  sudden 
movements.

•   During transportation, particular care should 

be taken when positioning the glass side. Do 
not  place  the  collectors  so  that  the  glass  is 
facing downwards or transport them in this 
manner.

•  Before  installing  the  solar  collector,  never 

leave  it  exposed  to  the  elements  with  the 

glass side facing downwards; if it rains, water 
could  enter  the  collector.  This  would  cause 
condensation to form inside the panel.

•  Leave the collectors in their packaging until 

they  reach  the  place  where  they  are  to  be 
installed; this will prevent damage.

•   Do not rest the rear side of the collectors on 

uneven or pointed surfaces.

•  Always  keep  the  glass  side  of  the  collector 

covered  until  the  system  is  ready  for 
operation.

Orientation

The  solar  collectors  offer  maximum  energy 
performance  when  the  surfaces  are  facing 
directly  the  equator  (therefore  directly  south 
for  Northern  Hemisphere  installations  and 
directly  north  for  Southern  Hemisphere 
installations).  Different  local  conditions,  for 
example the amount of shade or the direction 
of the roof slants, may lead to a slight variation 
of  the  equator-facing  position  (the  maximum 
recommended variation is 30° in relation to the 
equator).

Positioning

Before  installing  the  solar  collector  you  must 
choose  its  position,  so  that  the  following 
conditions are satisfied:
•   the collector must be placed in areas that are 

not in the shade during hours of sunlight;

•   there must be minimal wind exposure;
•   it must be placed as close as possible to the 

storage cylinder;

•   it  must  be  accessible  for  any  necessary 

maintenance work;

•   it must be firmly secured in place and able to 

withstand wind pressure;

•    in  order  to  minimise  wind  loads,  avoid 

installing  the  appliance  on  roof  edges. 
Minimum  distance:  1.2  m;  increase  this 
distance  for  tall  buildings  and  heavily 
exposed areas.

Earthing system and anti-lightning 

protection

The  metal  piping  used  in  the  solar  heating 
circuit  and  parts  that  carry  electricity  must 
be  proportionally  connected  to  the  general 
earthing  system,  with  a  green/yellow  copper 
wire with a minimum section of 16 mm² (H07 
VU  o  R).  If  an  anti-lightning  system  is  in  place, 

the collectors can be connected to it. The earth 
connection  may  be  performed  using  an  earth 
rod.  The  earth  conductor  must  be  installed 
outside  the  building.  The  ground  electrode 
must  be  connected  to  the  general  earthing 
system using a proportionate wire of the same 
section.
Work  must  only  be  carried  out  by  a  company 
specialising in electrical circuitry.

Warning

Hot  water  supplied  at  a  temperature  above 
50°C to the taps at the point of use could cause 
immediate serious scalds. Children, the disabled 
and the elderly are more exposed to this risk. We 
therefore recommend the use of a thermostatic 
mixer valve screwed onto the appliance water 
outlet pipe.
This  device  shall  be  able  to  withstand  the 
maximum  possible  domestic  hot  water 
temperature from the solar system. (110 ° C).

Stagnation Behaviour

The THERMO DR-2 resistance to overheating has 
been tested according to 5.2 of EN 12976-2:2017 
with extremely sunny climate conditions; these 
systems  are  therefore  suitable  for  the  climate 
class type A+ (according to ISO 9806:2018).

Low temperature behaviour

Heat  radiating  towards  a  cold  night  sky 
may  cause  frost-related  damage,  even  at  air 
temperatures of 5°C. 
If  the  temperature  falls  below  5°C,  drain  the 
system as follows:
1) Close the cold water supply
2) Open  a  hot  water  tap  downward  the  solar 

system

3) Open  the  hot  water  outlet  (Fig.1  A)  of  the 

tank to allow air to go inside

4)  Dismount  the  hydraulic  closure  (Fig.1  B)  of 

the collector to drain the system

5)  When  the  system  is  drained,  close  the  hot 

water tap downward the solar system

6) Close the hot water outlet of the tank
7) Mount the hydraulic closure of the collector
8) When it will be necessary to restart the system 

,  please  refer  to  the  section “Preparation  of 
the system for operation” an following.

B

A

Fig.1

Summary of Contents for THERMO DR-2

Page 1: ...THERMO DR 2 THERMO DR 2 100 1 N THERMO DR 2 150 1 N THERMO DR 2 200 1 B GB Instruction manual for authorized service personnel...

Page 2: ...of the appliance and on the potential risks connected with it Children must not play with the appliance Any cleaning and maintenance performed by the user must not be effected by unsupervised childre...

Page 3: ...om dangerous obstacles and that any impact upon falling is cushioned by semi rigid or deformable surfaces Personal injury caused by falling from a height Make sure that adequate levels of hygiene and...

Page 4: ...ing position the maximum recommended variation is 30 in relation to the equator Positioning Before installing the solar collector you must choose its position so that the following conditions are sati...

Page 5: ...t 200 lt 150 lt WARNING The boiler herein can only be used as an integral part of the new solar devices or as a spare part of the same produced by Ariston Thermo Spa the manufacturer does not authoris...

Page 6: ...to thermal energy heat For this to occur sunlight must be captured by the surface of the absorber The latter consists of a uniform network of tubes through which heat is conveyed The specific shape of...

Page 7: ...er supply The appliance must be grounded with a cable yellow green and longer than the phase cable connected to the terminals marked fig 6 Before starting up the appliance check that the power rating...

Page 8: ...Inspect valve mechanism ensure that it is free from any build up and still functioning Confirm valve overflow is not plugged Pressure Control Valve Inspect valve and ensure that the expansion relief v...

Page 9: ...ipe of diam ter at least equal to the of the outlet itself with a funnel to permit an airgap of at least 20 mm for visual inspection to prevent damage or injury to persons animals and property when th...

Page 10: ...10 GB...

Page 11: ...11 GB...

Reviews: