Country-
spec. Set-
tings
Level Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Reactive Power Control
(RPC)
NOTE: Activate the reactive power process in the mode menu.
More detailed information at:
4
1
2
3
4
Mode
Cos-phi const. | Q
const. | Cos-phi(P/Pn)
| Q(U)
Password protection
Status
1. Select a control process.
2. Activate optional password protection.
3. Confirm the action field.
4
1
2
3
4
Cos-phi constant
NOTE: Define the cos ϕ constant.
4
1
2
3
4
cos-phi const.
0,3 – 1 / 1 /
0,001
F
Determine the specified power factor.
4
1
2
3
4
Power gradient in-
creasing & power
gradient decreasing
1 – 65534 [% Slim /
min] / 65534 [%
Slim / min] / 1
1. Maximum change in the reactive power %S
lim
/min in the event of a
change to over-excited mode.
2. Maximum change in the reactive power %S
lim
/min in the event of a
change to under-excited mode.
4
1
2
3
4
Settling time
1000 – 120000
[ms] / 5000 [ms] /
10
Password protection
Status
1. Set the settling time in the event of an abrupt change in the reactive
power target value (e.g. caused by a voltage jump).
2. Activate optional password protection.
3. Confirm the action field.
4
1
2
3
4
Q constant
NOTE: Define the Q constant.
4
1
2
3
4
Q constant
0 – 100 [% Slim] /
0 [% Slim] / 0.1
F
Set the reactive power Q to a fixed value.
Under-excited |
over-excited
F
Select the type of phase shift.
NOTE: Under-excited relates to inductive load, over-excited
relates to capacitive load.
4
1
2
3
4
Output gradient limita-
tion increase & Output
gradient limitation de-
crease
1 – 65534 [% Slim /
min] / 65534 [%
Slim / min] / 1
1. Maximum change in the reactive power in the event of a change to
over-excited mode.
2. Maximum change in the reactive power in the event of a change to
under-excited mode.
4
1
2
3
4
Settling time
1000 – 120000
[ms] / 5000 [ms] /
10
Password protection
Status
1. Set the settling time in the event of an abrupt change in the reactive
power target value (e.g. caused by a voltage jump).
2. Activate optional password protection.
3. Confirm the action field.
4
1
2
3
4
Cos-phi (P/Pn)
NOTE: Define the cos ϕ (P).
Manual
Configuration and operation | 9
KACO blueplanet 100 TL3
Page 59
EN