Country-
spec. Set-
tings
Level Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Insulation resistance
100 – 2000 [kOhm] /
300 [kOhm] /
1[kOhm]
1. Set threshold value at which the insulation monitor reports a fault.
2. Confirm the action field.
4
1
2
3
4
Grid Parameters
Input screens for network parameters
4
1
2
3
4
Country & Grid type
NOTE: This option influences the country-specific operating
settings of the device. Please consult KACO service for further
information.
1. Select country and grid type.
2. Observe the note for [See section 9.5.2
Nominal grid voltage &
Nominal grid frequency
Password protection
Status
F
Specify optional nominal grid voltage.
NOTE: The device switches off if the grid frequency deviates
from the nominal grid voltage by more than 9.5Hz.
1. Select optional nominal grid frequency.
2. Activate optional password protection.
3. Confirm the action field.
4
1
2
3
4
FRT (Fault Ride
Through)
NOTE: The device supports dynamic grid stabilization (Fault
Ride-Through)
.
NOTE: More detailed information at:
4
1
2
3
4
Operation mode –
On | Off
F
Select a control process.
On
: Activates dynamic grid support using dynamic reactive current.
Off
: Deactivates dynamic grid support using dynamic reactive current.
Dynamic grid support remains active on account of immunity to inter-
ference.
Setting | Manual |Pre-
defined zero current
F
Select a control process.
Priority – Reactive cur-
rent limitation | Active
current priority
F
Select a control process.
4
1
2
3
4
Constant k positive se-
quence dip &
Constant k positive se-
quence swell
k 0 – 10 2 0.1
F
Set amplification factor k for the pos. sequence for drop and increase
in the grid voltage.
4
1
2
3
4
Constant k negative se-
quence dip
Constant k negative se-
quence swell
k 0 – 10 2 0.1
F
Set amplification factor k for the neg. sequence for drop and increase
in the grid voltage.
4
1
2
3
4
Dead band
2 – 120 [% Uref]
10,0 0.1
F
Set dead band in %.
4
1
2
3
4
Dead band mode
Mode 1 | Mode 2
F
Select dead band mode for the active control process.
Manual
Configuration and operation | 9
KACO blueplanet 100 TL3
Page 49
EN