Further setting options:
■ SMTP port
■ Timeout
■ Interval (repeats)
Result The email functions are configured and activated.
Suppress repeat messages (setting an interval)
To suppress messages repeating at short intervals, a period of 0 – 900 minutes can be set during
which a repeat of the same message is suppressed, i.e. is not sent.
Precondition Password level 2 is activated.
E-mail submenu is displayed as being active.
1. Press «Enter».
2. Press «DOWN» repeatedly until
Interval: is displayed as the active line.
3. Press «Enter» to switch into setting mode.
The
value for the time of suppression flashes.
8 9 p s i 0 8 : 1 5 1 7 6 ° F
8.1.3 E-mail
Menu
Password
·········
Port 25 ¦ Timeout 10 s
Interval: 5 min
Active line
4. Use the «UP» or «DOWN» keys to set the desired duration of suppression.
5. Press «Enter» to accept the setting.
6. Press «Escape» repeatedly to return to the main menu.
Result Suppression interval is set.
7.11 Configuring input and output signals
The controller's binary and analog inputs and outputs can be used for other requirements.
This chapter deals with the various options in the following sections:
■ 7.11.1: Outputting important operational states of the compressors.
■ 7.11.2: Displaying analog input values
■ 7.11.3: Displaying additional binary input signals
The controller only allows assignment of spare inputs and outputs.
Any assignment of a preassigned input or output is discarded by the controller.
When delivered from the factory, the outputs DO0.3 to DO0.5 are available for assignment.
Further spare outputs can be found in the machine circuit diagram.
➤ Configure the inputs and outputs as described in the following.
7
Initial Start-up
7.11 Configuring input and output signals
9_9450 03USE
Service manual Controller
SIGMA CONTROL 2 SCREW FLUID 1.1.3
123
Summary of Contents for ESD 442 SFC
Page 5: ......
Page 6: ......
Page 7: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 14: ......
Page 15: ......
Page 16: ......
Page 17: ......
Page 18: ......
Page 19: ......
Page 20: ......
Page 21: ......
Page 22: ......
Page 23: ......
Page 24: ......
Page 25: ......
Page 26: ......
Page 27: ......
Page 28: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 171: ...KKW SSC 2 03 en 01 BA SIGMA CONTROL FLUID KKW SSC 2 03 01 20130805 113302...
Page 173: ......
Page 175: ...Contents ii Quick user guide Controller SIGMA CONTROL 2 SCREW FLUID 1 1 3 9_9450 03 USE...
Page 215: ...Contents iv Service manual Controller SIGMA CONTROL 2 SCREW FLUID 1 1 3 9_9450 03USE...
Page 392: ...KKW GBASE 1 00 en ERSATZTEILE 10357405_10 ESD 2C 20130903 115349...