10. Press the «Enter» key.
The setting is applied accordingly.
ok is displayed.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.5 External DI / AII signal
Menu
Load signal
DI1.04
ok ☑ Logic :
+
Active line with activated check box
······························
Idle signal
DI1.09
☐ Logic :
+
······························
11. Press the «Escape» key repeatedly to exit the menu.
Result The load signal is set to remote operation.
8.5.4.3 Setting the idle signal to remote operation
Precondition A load/idle valve is installed
Electrical connection via DI 1.09 – terminal -X15: 11+12 is established
Access level 2 is activated
The operating mode is displayed
1. Open the menu 5.5
<Configuration – External DI / AII signal>.
2. Using the «Up» or «Down» key, select the line
Idle signal.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.5 External DI / AII signal
Menu
Load signal
Active line
DI1.04
☐ Logic :
+
······························
Idle signal
DI1.09
☐ Logic :
+
······························
3. Press the «Down» key.
The input
DI has been selected.
4. Press the «Enter» key.
The display flashes for the input currently set.
5. Using the «Up» or «Down» key, select the input DI1.09.
6. Press the «Enter» key.
The setting is applied accordingly.
7. Press the «Right» key.
8. Press the «Enter» key.
The check box assigned to the input flashes.
9. Press the «Up» key.
The check box is activated.
8
Initial Start-up
8.5
Machine start and machine stop
No.: 901700 14 E
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 4.0.X
91