background image

Current Trans. Ratio  ( 5.......10000 / 5A )

1 5

Enter current transformer value

Apply

▲ +

▼ -

00500 

/ 5A

Enter current transformer value

Cancel

Okay

Exit

This is the section in which the primary value of current transformers in compensation system, is 

entered. The value is setup to the required step by using up and down keys starting from the digit 

where the blue line is.  Then, left key is pressed and the blue line moves next to left digit. All 

values are entered in the same way by using the up and down keys. Press “Apply” key inorder to 

take the current transformer (primary) value into memory. “Save changes” message will appear on 

the screen. When “Okay” key is pressed, the value is taken into memory.

00500 

/ 5A

Save

changes

1 2 3 4 5 6

1 2 3 4 5 6

Current Flow Direction

1 6

This is the section in which the function of searching of current transformer polarity directions are 

activated or de-activated. In case “Enable” is selected, internalization of current transformer 

direction is always “On”, and only checks the directions when the device is powered. If “disable” is 

selected, then the device internalize the current transformer directions at once and do not change 

it. The “disable” choice should be selected for some loads (producing negative active load).  

The required status for function is selected by using the up

and down keys. Press “Apply” key inorder to take this parameter

into memory. “Save changes” message will appear on the screen.

When “Okay” key is pressed, the value is taken into memory.

Apply

▲ +

▼ -

Enable

Direction Detection Status

1 2 3 4 5 6

Enter Power of Steps

1 7

Exit

Kvar

Select

R

S T

S1                       ---------

S2                       ---------
S3                       ---------
S4                       ---------
S5                       ---------

Step powers are adjusted manually...

30

Exit

Select

1.Step

0.000 KVAr

1.Step

Apply

▲ +

▼ -

Cancel

Okay

Exit

Exit

Select

1.Step

Cancel

Okay

Exit

R

S

T

- 0.000 KVAr

R

S

T

KVAr

R

S

T

- 0.000

Save

changes

This is the section in which the step powers 

are entered. The device directs the user 

with subcommand display continuously. It is 

moved on the step of which the power is 

required to be entered by using the up and 

down keys. In the meantime, that line are in 

red colour. Select key is pressed. 

The selected step number comes to screen.

The “Select” key is pressed and a blue 

underline appears on the last digit inside of 

the frame. The value is setup by using the 

up and down keys starting from the digit 

where the blue line is. Then, left key is 

pressed and the blue underline moves next 

to the left digit. All the values are entered in

1 8

Delete Power of Steps

the same way by using up and down keys. 

The “Apply” key is pressed to take them 

into memory. The sub-command screen 

changes and “Okay”, then “Exit” key is 

pressed. “Save Changes” will appear on 

the screen. When “Okay” key is pressed, 

the value is taken into memory.

1 2 3 4 5 6

1 2 3 4 5 6

1 2 3 4 5 6

1

2 3 4 5 6

This is the section in which the step parameters are deleted one by one, or all. In case the reactive 

load is changed in any step, the power of that step must be deleted to let the device internalize the 

the power of new step. The device fowards the user continuously by sub-command screen. Moving 

onto the step of which power required to be deleted, the up or down key is pressed. The line is in red 

colour in the meantime. In case of deleting only that step, “Delete” key is pressed; in case of deleting 

all steps (if a device used in somewhere else is connected to a new plant), “Delete All” key is 

pressed. If “Delete” key is pressed, “Step Delete?” warning appears on the screen. When “Okay” key 

is pressed, the power of that step would be deleted. The device will automatically try to internalize the

power of that step again. You can exit the menu by “Exit” key. In case “Delete All?” key is pressed, 

“Steps Delete?” warning appears on the screen.  When “Okay” key is pressed, the power of all

steps would be deleted. The device will automatically try to internalize the power of that step again. 

You can exit the menu by “Exit” key.

Summary of Contents for VARko-106-TFT

Page 1: ...VARko 106 TFT Reactive Power Control Relay Banks Markets Oil Stations Schools Workshops Hotels 6 Steps KAEL M hendislik Elektronik Tic ve San Ltd ti www kael com tr...

Page 2: ...ing system is used in the micro processor Password protected Measuring temperature Following electrical parameters of three phases at the same time Voltage of phase V L N Current of phase I Cos value...

Page 3: ...5 Do not use the device for different purposes other than compensation system 6 Fix the device tightly on the control panel with the apparatus given on the device without hanging around 7 Do not inter...

Page 4: ...ways located on the top of the screen LCD screen is used in VARko 106 TFT to provide it to be more easier in use and be intelligible In case the keys are not pressed for a long time the device switch...

Page 5: ...ired to draw enough current from each phase If enough current can not be drawn from any phase the device warns as current flow direction not detected and shows the phase or phases which are not intern...

Page 6: ...K5 K6 L2 L3 I1 k1 Voltage inputs Current Transformer Inputs Load Fuse compatible to the capacitor power ALR ALR Alarm output FAN Fan output FAN 2A 2A VARko 106 TFT 400V AC X 5A Main Screen Temperatur...

Page 7: ...es next to left digit All the values are entered in the same way by using up and down keys Press Apply key inorder to take the period of step activating into memory Save changes message will appear on...

Page 8: ...ers are entered The device directs the user with subcommand display continuously It is moved on the step of which the power is required to be entered by using the up and down keys In the meantime that...

Page 9: ...apacitors and devices in the system may be damaged or may not be operated properly Voltage protection activated may be preferred in the step protection function Phase Alarms Over Current enable In cas...

Page 10: ...e system may be kept in penalty Review the capacitor power distribution in the steps Please allow less powerful capacitors which can reach buffer values 1 9 1 2 5 General Alarms Total Under Compensati...

Page 11: ...e them into the memory Save changes message will appear on the screen Pressing Okay key the value is taken into the memory 170 Save changes In case voltage protection is activated in the step protecti...

Page 12: ...memory 005 Voltage HD Alarm Setting HDV Save Changes In case harmonic protection is activated in the step protection function Chapter 19118 all steps are de activated one by one to protect the capacit...

Page 13: ...utomatically and de activates the steps one by one 1 9 4 1 This is the section in which the temperature protection function is activated or de activated The over temperature alarm should also be activ...

Page 14: ...Exit Password active passive Change password 1 10 9 PASSWORD Enter New Password 0 Okay Exit Password active passive Change password 1 10 9 PASSWORD Re Enter New Password 0 Exit Password active passive...

Page 15: ...ues Under Voltage 350V Alarm Setting Values Over Temperature 70 C Alarm Setting Values THD Voltage 4 Alarm Setting Values HD Voltage 4 Alarm Setting Values THD Current 30 Alarm Setting Values HD Curre...

Page 16: ...Terminal Protection Class IP 00 Environment Temperature 5 C 50 C Humudity 15 95 without condensation Connection Type On the front cover of the panel Dimensions 144x144x45 mm Technical Info 37 mm 140m...

Reviews: