background image

1 12

Factory Defaults

This is the section which is used to restore factory default values to the 

device.

Factory Default Values :

Target TanΦ(cosΦ)

: % 0 (1,00)

Switch on Time

: 10 sec

Switch off Time

: 10 sec

Current Transformer (Primary) Value

:

 

5

 

/ 5 A

Number of steps

: 06

Continuous Current Flow Direction Detection

: disable

Phase Alarms – Over Voltage

: disable

Phase Alarms – Under Voltage

: disable

Phase Alarms – Over Current

: disable

Phase Alarms – Over Compensation

: disable

Phase Alarms – Under Compensation

: disable

Phase Alarms – THD on Voltage

: disable

Phase Alarms – HD on Voltage 

: disable

Phase Alarms – THD on Current

: disable

Phase Alarms – HD on Current

: disable

General Alarms – 1. connector failure

: enable

General Alarms – Total Over Compensation

: enable

General Alarms – Total Under Compensation

: enable

General Alarms – System Failure

: enable

General Alarms – Over Temperature

: enable

General Alarms – Step Change

: disable

General Alarms – Step Zero

: enable

Alarm Setting Values – Over Voltage 

: 450V

Alarm Setting Values – Under Voltage 

: 350V

Alarm Setting Values – Over Temperature

: 70 °C

Alarm Setting Values – THD Voltage 

: % 4

Alarm Setting Values – HD Voltage 

: % 4

Alarm Setting Values – THD Current 

: % 30

Alarm Setting Values – HD Current 

: % 30

Fan Settings – Fan Temperature Value 

: 50 °C

Fan Settings – Fan Output

: disable

Level Protection Function–Temperature Protection : enable
Level Protection Function – Voltage Protection

: disable

Level Protection Function – Harmonic Protection : disable
Password Procedure – Password Settings

: disable

Password Procedure – Default Password 

: 0000 (refer to PS1)

Select

Exit

1 12

SETUP

Factory Defaults

Delete Step Powers
Alarm & Protection Par.
Password Settings

MODBUS RTU Settings

Yes

Cancel

Device 

will return

factory settings

Yes

Cancel

Factory defaults

of the device are loading

In case of restoring factory settings, all the changes that the user made, except password, will be cancelled.

  

PS 1 :

 User password is defined as “0000” at first. However, after password is changed, password will not change even if 

returned to the factory settings.  The last password that the user entered is valid. 

Device 

will return

factory settings

Device   

will reset ?

1

3 4 5

2

6

1

3 4 5 6

2

1

3 4 5 6

2

1

3 4 5

2

6

Summary of Contents for VARko-106-TFT

Page 1: ...VARko 106 TFT Reactive Power Control Relay Banks Markets Oil Stations Schools Workshops Hotels 6 Steps KAEL M hendislik Elektronik Tic ve San Ltd ti www kael com tr...

Page 2: ...ing system is used in the micro processor Password protected Measuring temperature Following electrical parameters of three phases at the same time Voltage of phase V L N Current of phase I Cos value...

Page 3: ...5 Do not use the device for different purposes other than compensation system 6 Fix the device tightly on the control panel with the apparatus given on the device without hanging around 7 Do not inter...

Page 4: ...ways located on the top of the screen LCD screen is used in VARko 106 TFT to provide it to be more easier in use and be intelligible In case the keys are not pressed for a long time the device switch...

Page 5: ...ired to draw enough current from each phase If enough current can not be drawn from any phase the device warns as current flow direction not detected and shows the phase or phases which are not intern...

Page 6: ...K5 K6 L2 L3 I1 k1 Voltage inputs Current Transformer Inputs Load Fuse compatible to the capacitor power ALR ALR Alarm output FAN Fan output FAN 2A 2A VARko 106 TFT 400V AC X 5A Main Screen Temperatur...

Page 7: ...es next to left digit All the values are entered in the same way by using up and down keys Press Apply key inorder to take the period of step activating into memory Save changes message will appear on...

Page 8: ...ers are entered The device directs the user with subcommand display continuously It is moved on the step of which the power is required to be entered by using the up and down keys In the meantime that...

Page 9: ...apacitors and devices in the system may be damaged or may not be operated properly Voltage protection activated may be preferred in the step protection function Phase Alarms Over Current enable In cas...

Page 10: ...e system may be kept in penalty Review the capacitor power distribution in the steps Please allow less powerful capacitors which can reach buffer values 1 9 1 2 5 General Alarms Total Under Compensati...

Page 11: ...e them into the memory Save changes message will appear on the screen Pressing Okay key the value is taken into the memory 170 Save changes In case voltage protection is activated in the step protecti...

Page 12: ...memory 005 Voltage HD Alarm Setting HDV Save Changes In case harmonic protection is activated in the step protection function Chapter 19118 all steps are de activated one by one to protect the capacit...

Page 13: ...utomatically and de activates the steps one by one 1 9 4 1 This is the section in which the temperature protection function is activated or de activated The over temperature alarm should also be activ...

Page 14: ...Exit Password active passive Change password 1 10 9 PASSWORD Enter New Password 0 Okay Exit Password active passive Change password 1 10 9 PASSWORD Re Enter New Password 0 Exit Password active passive...

Page 15: ...ues Under Voltage 350V Alarm Setting Values Over Temperature 70 C Alarm Setting Values THD Voltage 4 Alarm Setting Values HD Voltage 4 Alarm Setting Values THD Current 30 Alarm Setting Values HD Curre...

Page 16: ...Terminal Protection Class IP 00 Environment Temperature 5 C 50 C Humudity 15 95 without condensation Connection Type On the front cover of the panel Dimensions 144x144x45 mm Technical Info 37 mm 140m...

Reviews: