Low Voltage Delay Time (Volt Undr dELy) :
It may be set between 1 – 300 sec. If the measured voltage
falls below the set voltage value, the relay contact is
released at the end of the delay time.
Low Voltage Mistake Repair Time (Volt Undr dLy0) :
It
may be set between
1 – 300 sec
Low Voltage Hysteresis value (Volt Undr
HySt) :
It may be set between % (1 – 30).
Düşük Gerilim Ayarlarından
ÇIKIŞ
Over Current Set value ( Curr Over Val):
It may bet set between (max. 50.000A) 0,1 and 50,000 A
depending on the maximum value of shunt resistance.
For ex: It may be set as max. 100A for 100A/60mV shunt.
Over Current Alarm Permit (Curr Over
EnbL) :
YES ; alarm mode enabled
NO; alarm mode disabled
Over Current Alarm Mode setting (Curr Over tYPE) :
Over Current Delay Time (Curr Over dELy) :
It may be set between 1 – 300 sec. If the measured voltage
exceeds the set voltage value, the relay contact is released
at the end of the delay time.
Over Current
Mistake Repair Time
(Curr Over
dLy0) :
It may be set between 1 – 300 sec.
Over Current Hysteresis Value (Curr Over
HySt) :
It may bet set between % (1 – 30) .
Aşırı Akım Ayarlarından
ÇIKIŞ
Alarm mode:
when alarm is set alarm relay is pulled. When
alarm is disabled alarm relay releases.
Latch mode:
when alarm mode is set alarm relay is pulled. Alarm
relay remains pulled even the alarm is disabled.
If latch mode iset
in models with alarm function, alarm should be certainly disabled
by pressing the set key.
Momentary mode:
In this mode, as an extra
the time seen in the adjacent box is displayed .
It may bet set between 300 msn and 5000msn.
When alarm is set, alarm relay remains pulled
until the end of this time then it is released.
This function may be used when continuous
alarm is not intended.