KAEL DC-MULTISER-1OH-DIN Manual Download Page 4

MEASURED ELECTRICAL PARAMETERS

(dc 

current

, dc 

voltage

, dc 

power

, dc ener

gy

 )

able to perform measurements in

 kV, A, kA, W, kW, MW, GW, kWh, MWh, GWh 

units

SHORTCUT KEY PROPERTIES

Allows entry to energy display unit

By presing 

 

key

 export, import, net (

difference

and total energy values may be accessed

 

Returns to main screen by pressing 

SET 

key

.

+

:

:

 device number is displayed for 3 sec. in models with 

RS485

 properties

:

 operation time of the device is displayed for 

sec

+

 

SET

 

:

   operation duration of the device with positive current is displayed for 

sec

+

 

SET

 

:

 operation duration of the device with negative current is displayed for 3 sec

If Latch function is selected in models with alarm properties, alarm should be absolutely deleted by pressing 

set key.

If pressed for 3 sec. It goes to parameter and settings menu.

SET

:

Export ener

gy I

mport ener

gy    

Net ene

rgy       

To

tal

 ener

gy

Export ene

gy

  = Po

sitive

 Ener

gy

I

mport ene

gy

  = Negati

ve

 Ener

gy

Net ener

gy

  = (Po

sitive 

Ener

gy

) - (Negati

ve

 Ener

gy

)

 

To

tal 

ener

gy

 = (Po

sitive

 Ener

gy

)  + (Negati

ve 

Ener

gy

)

SET

Main screen

ENTRY TO PARAMETERS

If set KEY is pressed for 3 sec. password should be entered before entry to parameters menu. At this stage, HHHH is displayed in the line at the bottom of the screen while the password 

screen flashes. When SET key is pressed, 0000 figures are displayed in the most bottom line and the screen begins to flash more rapidly. The flashing figures can bet set with ▼and ▲keys 

and next digit can be entered by pressing SET key. When all digits are completed, if the password is correct the first parameter Clear Energy (CLR energy) section may be entered. If the 

password is incorrect, the device returns to main measurement screen without entering to settings. The default value of the password is 0000. The user can change it.

SET

Blink

SET

Full scale setting of the current

(1 – 50.000A)

Shunt resistance setting

 

(50 – 100 mV)

YES : 

Clear energy

NO: 

Not clear energy

SET

SET

SET

Paramet

ers

CLEAR ENERGY

CURRENT FULL SCALE SETTING

SHUNT RESISTANCE mV SETTING

This is where the line current maximum value is set. For ex: if 

1000A/60mV  

shunt is used

then this value should be set as 

1000

 A.

This is the section where shunt resistance

 mV 

value can be set

.

For ex: if 

1000A/60mV 

shunt is used, then this value should be set 

as

 

60

 mV yapılmalıdır.

This is where all energies can be cleared

.

In this case, pulses that are to be transmitted in the pulse output are 

also cleared

.

 

Note :

 

Energies are reset when factory settings are enabled

.

Summary of Contents for DC-MULTISER-1OH-DIN

Page 1: ...1 1 1 2 1 1 1 2 1 1 1 2 1 1 DC MULTISER 2UH DIN DC MULTISER 2OH DIN DC MULTISER 2OL DIN DC MULTISER 2UL DIN Green Power Measurement Device Dimensions 105x90x59 mm Easy use via menus with shortcuts DC...

Page 2: ...f the system presents power quality problems insulation transformer or EMC filter should be used for auxiliary power supply Switch board cover or protection sheet With our DC MULTISER devices dc curre...

Page 3: ...t Connections AC DC AC DC Power Supply Relay Power Supply Digital Input Connections max 30Vdc Com DI2 Connect 1 5 2 5 mm cable Power Supply Optical Insulation Optik izolasyon DI1 Optical insulation An...

Page 4: ...eters menu At this stage HHHH is displayed in the line at the bottom of the screen while the password screen flashes When SET key is pressed 0000 figures are displayed in the most bottom line and the...

Page 5: ...arity no even odd Stop Bits May be set as 1 1 5 or 2 Baud rate It may be set as 2400 4800 9600 19200 28800 38400 57600 or 115200 Device No 001 255 SET SET SET SET Relay Contact Position nO normally sw...

Page 6: ...Momentary mode In this mode as an extra the time seen in the adjacent box is displayed It may bet set between 300 msn and 5000msn When alarm is set alarm relay remains pulled until the end of this tim...

Page 7: ...e Curr Over dELy It may be set between 1 300 sec If the measured voltage exceeds the set voltage value the relay contact is released at the end of the delay time Over Current Mistake Repair Time Curr...

Page 8: ...rrent Delay Time Curr Undr dELy It may be set between 1 300 sec If the measured current falls below set current value relay contact is released at the end of the delay time Low Current Mistake Repair...

Page 9: ...s disabled alarm relay releases Latch mode when alarm mode is set alarm relay is pulled Alarm relay remains pulled even the alarm is disabled If latch mode iset in models with alarm function alarm sho...

Page 10: ...disregarding the symbol of the measured value In this mode measred value may be set between 100 This menu is displayed when PErC is selected in the Analogue measurement range An rAng This screen does...

Page 11: ...utputs Measurement Value Analogue output value 2 5 V 5 V 5 V Voltage V 0 10 V Example 1 Voltage Full Scale Setting Analogue Parameters Voltage Output Type Analogue Operation range setting PERC PERC up...

Page 12: ...arm mode 10 sec 10 sec Over Current Set Value Curr Over Val Over Current Alarm Permit Curr Over EnbL Over Current Alarm Mode Setting Curr Over tYPE Over Current Delay Time Curr Over dELy Over Current...

Page 13: ...t Type Current Output Type Accuracy Load Capacity 0 10V 2 10V 0 5V 1 5V 0 20mA 4 20mA 0 2 In current type max load resistance 750 Ohm In voltage type load current max 20 mA Updating Duration 200ms 6 R...

Reviews: