Over Voltage Set Value ( Volt Over Val):
It can bet set between 0.1 and 300 in UH and UL models.
It can be set between 0.1 and 1200 V in OH and OL
models.
Over Voltage
Alarm Permit
(Volt
Over EnbL) :
YES ; alarm mod
e
enabled
NO ; alarm mod
e disabled
Over Voltage Alarm Mod setting (Volt Over tYPE) :
Over Voltage Delay Time (Volt Over dELy) :
It may be set between 1 – 300 sec. If the measured voltage
exceeds the set voltage value, the relay contact is released
at the end of the delay time.
Over Voltage
Mistake Repair Time
(Volt Over dLy0) :
It may be set between
1 – 300 s
ec.
Over Voltage
Hysteresis Value
(Volt Over
HySt):
May bet set between
% (1 – 30)
Exit from Over
Voltage settings
Alarm mode:
when alarm is set alarm relay is pulled. When
alarm is disabled alarm relay releases.
Latch mode:
when alarm mode is set alarm relay is pulled.
Alarm relay remains pulled even the alarm is disabled.
If latch
mode iset in models with alarm function, alarm should be certainly
disabled by pressing the set key
.
Momentary mode:
In this mode, as an extra
the time seen in the adjacent box is displayed .
It may bet set between 300 msn and 5000msn.
When alarm is set, alarm relay remains pulled
until the end of this time then it is released.
This function may be used when continuous
alarm is not intended.
Low Voltage Set Value (Volt Undr Val):
It may be set between 0.1 and 300 V in UH and UL
models.
It may be set between 0.1 and 1200 V in OH and
OL Models
.
Low Voltage Alarm Permit (Volt Undr
EnbL)
YES ; alarm mode enabled
NO ; alarm mode disabled
Low Voltage Alarm Mode setting (Volt Undr tyPE) :
Alarm mode:
when alarm is set alarm relay is pulled. When
alarm is disabled alarm relay releases.
Latch mode:
when alarm mode is set alarm relay is pulled. Alarm
relay remains pulled even the alarm is disabled.
If latch mode iset
in models with alarm function, alarm should be certainly disabled
by pressing the set key.
Momentary mode:
In this mode, as an extra
the time seen in the adjacent box is displayed .
It may bet set between 300 msn and 5000msn.
When alarm is set, alarm relay remains pulled
until the end of this time then it is released.
This function may be used when continuous
alarm is not intended.
LOW VOLTAGE SETTINGS
OVER VOLTAGE SETTINGS