■  The connection of the device should be done without the system power.

■  The device must be connected as shown in the connection diagram.

■  Do the Pt100 sensor inputs as shown on the back of the unit

■  Do not energize the device without checking all connections using the meter.

Making Connections

Information Panel

The upper part of the screen of the device has an information panel consisting of icons easily 

understood by the user. This panel is always on top of the screen no matter which part the user is 

in. The date, time, device operation status, FAULT status, ALARM status, TRIP status, FAN status 

information are observed in this panel at the same time. The operating status indicator indicates 

OK if the system is normal and returns to exclamation point when an error occurs in the system.

A color LCD display is used in our device to make it much easier and clearer to use. If the 

keys are not pressed for a long time, the device will switch to screen saver mode to extend the life 

of the screen and only step down from the top of the screen with the information panel on top. 

When any key is pressed, the main screen image appears again.

System  Normal

FAN 

14:25

11.10.2016

ALARM

TRIP

TRIP

FAULT (error existing)

TC - PT100

Temperature Controller

Power supply

Un : 24 ... 240V AC 
        50/60Hz / DC
Δn : (0,9 – 1,1) x Un

PT100

red
red
white

PT100

red
red

PT100

red
red

PT100

red
red

ch

1

ch

2

ch

3

ch

4

ALARM

TRIP

FAULT

FAN

K-FAN

SYSTEM

STOP

V

V

white

white

white

The fan icon turns on the screen while the fan is running.
If the screen shows a fan but does not turn, then the unit has gone into a saving mode for cooling.

Over-voltage 
protection
device

Summary of Contents for TC - PT100

Page 1: ...KAEL M hendislik Elektronik Tic ve San Ltd ti Temperature Controller For Dry Type Medium Voltage Transformers www kael com tr TC PT100...

Page 2: ...78 Sok No 10 Ulucak Village Kemalpa a ZM R The device must be commissioned and programmed by authorized and qualified persons in accordance with the instructions in the operating instructions If nece...

Page 3: ...cooling Continuously monitors temperature sensors for faults It detects errors Sensor cable is broken Sensor cable short circuit Sensor not attached Error detection in case of data recording center f...

Page 4: ...s normal and returns to exclamation point when an error occurs in the system A color LCD display is used in our device to make it much easier and clearer to use If the keys are not pressed for a long...

Page 5: ...The PT100 sensors must have 1 white 2 red output lines DIN 43760 IEC 751 Ch2 channel should always be connected to the middle column of the MV transformers The Ch4 channel can be connected to measure...

Page 6: ...NING 1 Step Choice Of Language The next screen will appear when it is first activated Up Down buttons to select one of the Turkish English or Russian language and press Set button After the language o...

Page 7: ...F Then click the Apply button In this case if OK is pressed the change is recorded If you want to change without recording press the Back key After recording the device starts to operate normally 11 1...

Page 8: ...t the system would not be damaged ALARM TRIP FAULT FAN 11 10 2016 14 25 Exit RELAY TEST Set ALARM TRIP FAULT FAN Control the contactors of the relay with multimeter during the test opeation 2 SENSOR T...

Page 9: ...own in red If the temperature value measured from the corresponding sensor is equal to or lower than the set alarm temperature setpoint the alarm of the ALARM relay is deactivated and the alarm log is...

Page 10: ...time m T p T p T p T s T s Saving Mode Saving Mode Continuous Cooling Instantaneous temperature increase analyzes the temperature rise T value in seconds C sec The user can choose from 1 C to 30 C T...

Page 11: ...Pass Men s Enter Your New Password Again 0 OK 14 25 Exit PASSWORD SET Change De i tirme Pass Aktif Pasif Pass Men s Enter Your New Password Again 0 Password Saved OK Correctness of the measurements an...

Page 12: ...ction class IP 00 Accuracy 1 fully scale 1 digit Sensor Type RTD sensor Pt100 type 3 wire max 1 5mm Ambient Temperature 20 C 60 C EMC Immunity EN 61000 6 2 EMC Emission EN 61000 6 3 Installation Type...

Page 13: ...r transformer coil wires In the distribution box 3 conductors of each PT100 sensor must be connected to the PT100 sensor inputs of the TC PT100 temperature controller with a minimum 0 50 mm cross sect...