Installing the inverter
Page 29
Operating Instructions for Powador 7700-9600_EN
EN
7.6
Starting up the inverter
DANGER
Lethal voltages are still present in the terminals and cables of the unit even after the inverter
has been switched off and disconnected.
Severe injuries or death may occur if the cables and terminals in the inverter are touched.
Only appropriately qualified and authorised electricians may start up the inverter.
FR
Attachment of safety label in accordance with UTE C 15-712-1
The code of practice UTE C 15-712-1 requires that, upon connec-
tion to the French low-voltage distribution network, a safety
sticker showing a warning to isolate both power sources when
working on the device must be attached to each inverter.
"
Attach the provided safety sticker visibly to the outside of
the inverter housing.
ATTENTION
Présence de deux
sources de tension
- Réseau de distribution
-Panneux photovoltaïques
Isoler les deux sources
avant toute intervention
7.6.1 Switching on the inverter
↻
The inverter has been mounted and electrically installed.
↻
The cover for the connection area is grounded and closed.
↻
The PV generator is supplying a voltage > 350 V.
1. Connect the grid voltage using the external circuit breakers.
2. Connect the PV generator using the DC isolator switch (0
→
1).
»
The inverter begins to operate.
»
During the initial start-up: Follow the instructions of the New Connection Wizard.