Installing the inverter
Page 21
Operating Instructions for Powador 7700-9600_EN
EN
Authorised electrician
Connecting the PV generator
1. Unscrew the cable fittings.
2. Remove the outer cladding of the DC cables.
"
Insert the DC leads through the cable fittings into the connection area.
3. Strip the insulation from the DC cables.
4. Connect the ends of the cables to the DC connections.
5. Check that all connected cables are securely fitted.
6. Tighten the cable fittings.
7. The requirements of protection rating IP54 are met by closing the unused cable fittings with blind caps.
»
The inverter is connected to the PV generator.
7.2.2.3 External combiner box
1
2
3
4
PV+
PV-
S trang 1
S trang 2
S trang 3
S trang 4
U_
PV
+
+
-
-
U_
St
ar
t
PV+
PV-
F2
F4
F3
F1
R 4
R 3
TP6
TP5
TP3
TP1
TP4
TP2
TP
9
R 5
R 6
D2
TP8
TP7
TP10
CON6
CON7
CON1
CON2
CON3
CON4
CON5
LBL1
Figure 16: DC connection area for external combiner box
The photovoltaic generator connection leads of the combiner box are fed through the cable fittings into the
inverter. Connect these two leads to the terminals labelled PV+ and PV- on the fuse board (Figure 16)
7.2.2.4 DC-Plus string fuses
1
2
3
4
PV+
PV-
S trang 1
S trang 2
S trang 3
S trang 4
U_
PV
+
+
-
-
U_
St
ar
t
PV+
PV-
F2
F4
R 4
R 3
TP6
TP5
TP3
TP1
TP4
TP2
TP
9
R 5
R 6
D2
TP8
TP7
TP10
CON6
CON7
CON1
CON2
CON3
CON4
CON5
LBL1
F1
F3
Order no.
Designation
dimensions
22800169
PV fuse
8 A / 1000V DC (Type: 10 x 38 mm)
22800170
PV fuse
10 A / 1000 V DC (Type:
10 x 38 mm)
22800171
PV fuse
12 A / 1000 V DC (Type:
10 x 38 mm)
22800172
PV fuse
15 A / 1000 V DC (Type:
10 x 38 mm)
Table 5:
DC+ string fuses
Table 6:
Recommended fuses
When delivered, short-circuit jumpers are installed in the fuse holders of DC-Plus inputs 1 and 3 (Table 5).
Fuse holders 2 and 4 are not fitted in the factory default state. Use suitable fuse values
to fit the 4 fuse holders with string fuses.
If you use the included string fuses, you must observe the maximum possible short-circuit currents.
KACO new energy offers the appropriate fuses as accessories. (Table 6)
CAUTION
Damage to PV generator in case of faulty design of string fuses.
If the string fuses are too large, the PV generator can be damaged by excessive current.
Select suitable string fuses depending on possible short-circuit currents and the cable cross-sections
used.