Configuration and Operation
Operating instructions KACO blueplanet 50.0 TL3 S/Basic/M/XL
Page 45
EN
Country-spec.
Setting
Menu
level
Display/setting
Action in this menu/meaning
All countries
4
1
2
3
1
Reactive power
"
Open the menu: Press the right arrow button or
the Enter button.
"
Activating reactive power process: select process
and press Enter. The active process is highlighted.
4
1
2
3
2
cos-phi const.
"
Determine the prescribed shift factor.
"
If not equal to 1 is selected: Select the type of phase
shift (under-excited (inductive load) /over-excited
(capacitive load)).
4
1
2
3
2
Q const.
"
Set the reactive power Q (as % of nominal power)
to a fixed value.
"
Select the type of phase shift (under-excited/
over-excited).
All countries
4
1
2
3
2
cos-phi(P/Pn)
"
Open the menu: Press the right arrow button or
the OK button.
4
1
2
3
3
Lock-in voltage
"
Set voltage range at which the grid support pro-
cess is active.
4
1
2
3
3
Lock-out voltage
4
1
2
3
3
Number of nodes
NOTE:
The maximum number of configurable nodes
depends on the selected grid type.
"
Specify the number of nodes for the reactive power
characteristic curve.
4
1
2
3
3
1st, ..., 10th node
"
Specify the power factor for the 1st , ... ,10th node.
"
Set cos-phi of node.
NOTE:
For the 1st node, the power must be 0%; for the
last node, the power must be 100%. The power values
of the nodes must increase continuously.
"
If a power factor not equal to 0 is selected: Select
the type of phase shift (under-excited/over-ex-
cited).
All countries
4
1
2
3
2
Q(U) 10 nodes
"
Open the menu: Press the right arrow button or
the Enter button.
4
1
2
3
3
Lock-in power
"
Set the effective power as % of nominal power, in
which the grid support process is active.
4
1
2
3
3
Lock-out power
4
1
2
3
3
Lock-in time
"
Set period for grid observation (in seconds) for the
active grid support process.
4
1
2
3
3
Lock-out time
4
1
2
3
3
Transient time
"
Set the response speed of the control.
4
1
2
3
3
Downtime
"
Set the intentional delay for the start of the Q(U)
function
4
1
2
3
3
Limitation of output
gradient
"
Specify output gradient increase and decrease in
0/00 - (per thousand) / minute.