background image

 

– 22 – 

331551-002  

 Combustion  Tests

Burner adjustments:
Final burner adjustments must be made using combustion 
test equipment to assure proper operation.
1.  Fill heater with water. Do not fire heater without water or 

sections will overheat.

2.  Refer to burner manual for start-up.
3.  Allow heater to heat to design condition.
4.  Using combustion test equipment, adjust burner for:

a.  a trace of smoke between #0 smoke and #1 smoke.
b.  over-fire draft in combustion chamber per Table 4.

Note:

 For JW6 F307V also see additional “Installation 

Instructions for Through-the-wall Venting Components" that 
is supplied with the JW6 F307V.

Model #

Over-fire draft

 in. w.c. (Pa)

307, 507

+0.06 to +0.12 

657

-0.01 to -0.03 

307V

+0.2 to +0.3 

317, 517, 717

-0.01 to -0.03 

Table 4.   Over-fire Draft Pressures

 Routine Preventative Maintenance (By Owner/
Operator)

As a precaution against fire, and to maintain an adequate flow 
of combustion air to the heater:

• 

Keep the appliance area clear and free from combustible 
material, gasoline and other flammable  vapors and liquids.

• 

Keep the air ventilation openings unobstructed. If dust and 
lint is seen accumulating around the openings, remove it.

• 

Do not pile cartons, papers, or combustible materials on 
top, or near the heater (see Figure 1).

  Draining  And  Flushing

 Burn hazard.

 Hot water discharge.

 Keep hands clear of drain 

valve discharge.

BURN

HOT

HOT

DANGER

It is recommended that the tank be drained and flushed 
every 6 months to remove sediment that may build up during 
operation. The water heater should be drained if being shut 
down during freezing temperatures. To drain the tank, perform 
the following steps:
1.  Turn "OFF" the electrical supply to the water heater.
2.  Turn "OFF" the oil supply to the water heater.
3.  Close the cold water inlet valve.
4.  Open a nearby hot water faucet.
5.  Connect a hose to the drain valve and terminate it to an 

adequate drain.

Caution!

 The water being drained can be extremely hot! The 

drain hose should be rated for at least  200°F . If the drain hose 
does not have this rating, open the cold water supply valve 
until the water flow is no longer hot. Close the cold water 
supply valve and resume.
6.  Open the water heater drain valve and allow all the water 

to drain from the tank.

7.  Flush the tank with water as needed to remove sediment.
8.  Close the drain valve. Follow the instructions in the "Filling 

The Water Heater" section to refill the tank.

9.  Turn on the oil supply to the water heater.
10.  Turn "ON" the electrical supply to the water heater.

If the water heater is going to be shut down for an extended 
period, the drain valve should be left open.

Important:

 Condensation may occur when refilling the tank 

and should not be confused with a tank leak.

 Temperature And Pressure Relief Valve

Manually operate the temperature and pressure relief valve 
at least once a year to make sure it is working properly (see 
Figure 15). To prevent water damage, the valve must be 
properly connected to a discharge line that terminates at 
an adequate drain. Standing clear of the outlet (discharged 
water may be hot), slowly lift and release the lever handle 
on the temperature and pressure relief valve to allow the 
valve to operate freely and return to its closed position. If 
the valve fails to completely reset and continues to release 
water, immediately shut off the power to the heater and the 
cold water inlet valve and call a qualified service technician.

 Burn hazard.

 Hot water discharge.

 Keep clear of 

temperature-pressure 

relief valve discharge.

BURN

HOT

HOT

DANGER

TEMPERATURE-PRESSURE

RELIEF VALVE

DISCHARGE PIPE

Figure 15.  T&P Valve Test

Summary of Contents for JW F657

Page 1: ...ath or serious injury Instruction manual must remain with water heater WARNING Improper installation adjustment altera tion service or maintenance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified Oil Burner Technician or your oil supplier Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this o...

Page 2: ...hermal Expansion Temperature And Pressure T P Relief Valve The Temperature And Pressure Relief Valve The Discharge Line Driptube Temperature Pressure Relief Valve And Pipe Insulation Vacuum Relief Valves Installation Of The Aquastat Temperature Control Electrical Supply 18 Filling The Water Heater Installation Checklist 19 IV Operation 19 Startup 19 Water Temperature Regulation 20 Water Heater Ope...

Page 3: ...ur warranty Regularly service your water heater as directed in the Maintenance section of this manual Retain your original receipt as proof of purchase Do not discard this manual You or future users of this water heater will need it for reference Your safety and the safety of others is extremely important in the installation use and servicing of this water heater Many safety related messages and i...

Page 4: ...ACHUSETTS INSTALLATION REQUIREMENTS 1 CONNECT ELECTRONICALLY CONTROLLED TIMER TO AN ALL BRONZE PUMP PUMP MUST ACTIVATE EVERY 6 HOURS FOR 60 SECONDS TURN PUMP TIMER OFF BEFORE CLOSING PIPING LOOP SHUT OFF VALVE 2 ALL WATER PIPING MUST BE INSTALLED AND INSULATED IN ACCORDANCE WITH MASSACHUSETTS CODE 248 CMR 780 CMR 3 PIPING LOOP BETWEEN WATER HEATER AND AIR HANDLER MUST BE INSTALLED IN COMPLIANCE WI...

Page 5: ...r heater or air intake Due to the nature of air movement flammable vapors can be carried some distance from the point of storage A water heater igniter or burner flame can ignite these vapors causing a flashback fire or explosion which may result in severe property damage serious personal injury or death If flammable liquids or vapors have spilled or leaked in the area of the water heater leave th...

Page 6: ... inspected and approved by a qualified service technician THESE CONDITIONS CAN RESULT IN UNSEEN INTERNAL DAMAGE and are not subject to warranty coverage Flammable hydrogen gases may be present Keep all ignition sources away from faucet when turning on hot water Explosion Hazard WARNING Caution Hydrogen gas can be produced in a hot water system served by this heater that has not been used for a lon...

Page 7: ... any of its components DO NOTASSEMBLE OR INSTALLIT OR MAKE ANY ATTEMPT TO FIX THE DAMAGED PART S Contact the place of purchase for further instructions After installation dispose of packaging material in the proper manner Location Requirements The water heater must be installed indoors in an area not subject to freezing temperatures and in a vertical position on a level surface Water heaters locat...

Page 8: ...nd Accessibility The minimum clearances between the heater and combustible materials are listed in Figure 1 Note These requirements are also listed on the data plate located on the front of the water heater A minimum of 24 in of front clearance and 4 in on each side should be provided for inspection and service For continued protection against risk of fire Do not install water heater on combustibl...

Page 9: ...lable in 3 lengths 5 63320 10 63321 or 20 63322 Refer to additional Installation Instructions for Through the wall Venting Components that is supplied with the JW6 F307V Model Diam Flue location Flue size Clearance Center Rear Front Rear Sides Top Flue in in in in in in in JW6 F307 20 X 6 24 2 2 18 9 JW6 F507 22 X JW F657 26 X 16 6 JW6 F307V 20 X 18 JW6 317RF 24 X 6 6 14 18 JW6 517RF 28 X 7 JW717 ...

Page 10: ... 8 52 3 16 F in 44 3 16 51 1 2 59 1 2 44 3 16 G in 51 3 4 59 3 4 69 3 4 51 3 4 H in 6 6 6 6 Figure 2 Installation Dimensions Center Flue Models A B C D E F G H Model JW717 JW6 317RF JW6 517RF Diam in 32 24 28 A in 9 9 8 3 4 B in 19 1 2 20 20 C in 53 1 2 49 3 4 51 1 8 D in 61 5 8 58 3 4 59 E in 58 1 2 60 3 4 63 1 4 F in 32 1 2 23 1 3 23 G in 58 1 2 48 7 8 54 H in 7 6 7 Figure 3 Installation Dimensi...

Page 11: ...utside of the enclosure Lack of adequate fresh air supply may cause a poor flame Important Air for combustion and ventilation must not come from a corrosive atmosphere Any failure due to corrosive elements in the atmosphere is excluded from warranty coverage The following types of installation not limited to the following will require outdoor air for combustion due to chemical exposure and may red...

Page 12: ...e the necessary amount of fresh air to the water heater and other combustion equipment in the area If you are unsure that the structure meets this requirement contact your local fuel supplier or other qualified agency for a safety inspection When indoor air is used small enclosures and confined areas must have two permanent openings so that sufficient fresh air can be drawn from outside of the enc...

Page 13: ...tem to remove exhaust gases created by the burning of fossil fuels Air for combustion is taken from the immediate water heater location or is ducted in from the outside see Air Requirements and Vent and Exhaust Connections This water heater must be properly vented for the removal of exhaust gases to the outside atmosphere Correct installation of the vent pipe system is mandatory for the proper and...

Page 14: ...be equipped with an approved draft regulator of adequate size Ensure the draft regulator diameter is at least as large as the flue pipe diameter Follow manufacturers recommended instructions for installation It must be installed in the flue pipe before it enters the chimney and after the Blocked Vent Safety Switch Set the draft regulator at 0 03 in w c 7 46Pa as measured in the flue between the he...

Page 15: ...ed according to the applicable installation drawing Figure 9 and Figure 10 A pressure reducing valve and or an expansion tank may be required for installations where the water pressure is high The pressure reducing valve should be located on the supply to the entire house in order to maintain equal hot and cold water pressure Important Do not apply heat to the water fittings on the heater as they ...

Page 16: ...be connected to any existing heating system or component s previously used with a non potable water heating appliance All models are suitable for combination potable water and space heating applications COLD WATER SHUT OFF AQUASTAT TEMPERATURE CONTROL LOCATION T P VALVE COLD INLET AND DRAIN VALVE COMBINATION HOT WATER OUTLET 6 CENTER OF BLAST TUBE NON COMBUSTIBLE FLOOR Figure 10 Plumbing Connectio...

Page 17: ... not plug or remove the temperature and pressure relief valve Temperature And Pressure T P Relief Valve Temperature pressure relief valve must comply with ANSI Z21 22 CSA4 4 and ASME code Properly sized temperature pressure relief valve must be installed in opening provided Do not plug block or cap the discharge line Failure to follow this warning can result in excessive tank pressure serious inju...

Page 18: ...ation and tape must not block the discharge opening or hinder access to the manual relief lever Figure 12 Ensure a discharge pipe is installed into the T P valve discharge opening per the instructions in this manual Vacuum Relief Valves A vacuum relief valve installed in the cold water supply line above the top of the water heater shall protect the water heater against siphoning loss of water due ...

Page 19: ...construction as per specifications Is the water piping correctly connected Are you certain that there are no leaks Is the water heater filled with water Is the cold water supply valve open Is the flue pipe installed properly and are the vertical and horizontal runs properly supported Is the draft regulator intake opening unobstructed Is the T P valve installed Are the drain pipe if installed and T...

Page 20: ...n Water temperature over 125 F can cause severe burns instantly resulting in severe injury or death Children the elderly and the disabled and are at highest risk of scald injury Feel water before bathing or showering Temperature limiting devices such as mixing valves must be installed when required by codes and to ensure safe temperatures at fixtures BURN HOT HOT DANGER Once installed the operatio...

Page 21: ... be ordered if water odor or discoloration occurs This rod may reduce if not eliminate water odor problems The water supply system may require special filtration equipment from water conditioning company to successfully eliminate all water odor problems Artificially softened water is exceedingly corrosive because the process substitutes sodium ions for magnesium and calcium ions The use of a water...

Page 22: ...il supply to the water heater 3 Close the cold water inlet valve 4 Open a nearby hot water faucet 5 Connect a hose to the drain valve and terminate it to an adequate drain Caution The water being drained can be extremely hot The drain hose should be rated for at least 200 F If the drain hose does not have this rating open the cold water supply valve until the water flow is no longer hot Close the ...

Page 23: ...teel core exposed the anode s should be replaced EXPOSED SUPPORT WIRE EXPOSED SUPPORT WIRE PITTED ANODE ROD Figure 16 Anode Rod 9 Apply Teflon tape or sealing compounds approved for use with potable water to the threads of the anode s and install into the tank top 10 Open the cold water supply valve and open a nearby hot water faucet to purge air from the water tank as directed in Filling The Wate...

Page 24: ...s no water in it Re Starting The Heater After Shut Down Flammable hydrogen gases may be present Keep all ignition sources away from faucet when turning on hot water Explosion Hazard WARNING Caution Hydrogen gas can be produced in a hot water system served by this heater that has not been used for a long period of time generally two 2 weeks or more Hydrogen gas is extremely flammable and can ignite...

Page 25: ...F280 National Provincial Building Codes CSA C22 1 ANSI NFPA 70 CSA B51 and or codes having jurisdiction 5 The air handler fan coil and or the circulating pump in a baseboard hydronic loop will require a dedicated 120V circuit This must be provided and identified for this purpose 6 All piping between the water heater and the air handler or hydronic baseboard loop must be adequately insulated to red...

Page 26: ...ULATOR HYDRONIC BASEBOARDS SERIES CONNECTED SHOWN HOT WATER TO HOUSE FIXTURE C H M Figure 20 Combo Heating Baseboard WATER HEATER 8 in TO 12 in HOT OUTLET EXPANSION TANK OPTIONAL MIXING VALVE COLD INLET CHECK VALVE IF USED REQUIRES EXPANSION TANK COLD SUPPLY HOSE BIB OPTIONAL FLOW CONTROL SUPPLY RETURN CHECK VALVE EXTERNAL CIRCULATOR HYDRONIC IN FLOOR LOOP HOT WATER TO HOUSE FIXTURE C H M Figure 2...

Page 27: ...FG 0 75 CARLIN EZ 1 0 75 RIELLO 0 65 JW F657 BECKETT AFG 1 0 1 25 CARLIN EZ 1 1 0 1 25 RIELLO 0 85 1 0 Contact your RIELLO dealer for burner specifications Table 5 Listing Of Oil Burners INSTALLATION RECORD Record key data here for future reference and prompt service Installed By Purchased From Installation Date Location of Electrical Switch or Circuit Protector Model Number Serial Number SERVICE ...

Page 28: ...500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 800 433 2545 Fax 800 644 9306 www johnwoodwaterheaters com ...

Reviews: