background image

Finding faults with the  

Electric Fence  

FAULT FINDER

 

2.  At each intersection 
 

check readings in 
each direction. 

1.  At the beginning of the fence. 
     A fault is indicated. 

Arrow says ‘this way’ 

Voltage 1.5 kV is 

lower 

than usual 

Current 9 amps is 

higher

 than usual

 

Types of faults 

 

There are two common types of faults on electric fences: 
1. An OPEN CIRCUIT is where the live wire is broken. In the sections of fence after the break there will 
be NO voltage. These are relatively easy to find by testing the fence for voltage.  
2.  A  SHORT  CIRCUIT  is  where  the  live  wire  touches  ground  or  an  earth  wire,  or  an  insulator  breaks 
down. This leads to a reduced voltage throughout the system and no (or little) voltage at  and beyond 
the fault. When a SHORT circuit occurs a large amount of current flows through the live wires.  

 

 

Checking your fence 

 

VOLTAGE: Use the FAULT FINDER to measure the voltage on the fence by placing the metal tip over the 
live  wire  and  pressing  the 

PRESS

  button.  The  reading  is  shown  by  the  2  digits  on  the  left  side  of  the 

display. If it is 

lower

 than usual then you may have a short circuit. To be an effective barrier the fence 

should read higher than 2.5 kV. For 

Bi-Polar 

Energiser users: A “+” sign in the middle of the LCD shows 

that the voltage polarity of the wire is positive. This is helpful in determining which of the two live wires 
you are testing in a Bi-Polar system. 

 

 

CURRENT: The FAULT FINDER will also be measuring current flow in the fence when the 

PRESS

 button is 

pressed. Current flow is shown on the right side of the display. A 

higher

 than usual reading  indicates 

that you may have a short circuit. 

 
 

Take the time to "play" with the FAULT FINDER. Place pretend "faults" (short the live wire to  

3. 

Keep following the direction                                                      
arrow to the fault.

 

Arrow says ‘this way’ 

grounded  metal)  on  your  fence  and  “find”  them.  The  experience  will  be  invaluable  when  you 
come to find “real” faults. Get to know the "usual" current used by your fence and the "usual" 
voltages around the system. As a guide, usual current will be approximately 1 amp for every 4 
kilometers of live wire. This will also depend on seasonal conditions such as grass and moisture. 

 

Fault Finding Technique 

 

Always start close to the energiser

 - (But not within 30cm).  Where the lead out wire connects 

to  the  fence  is  a  good  place  to  start.  This  way  you  will  always  start  on  the  energiser  side  of  a 
fault.  

1.  Place the metal tip over the lead out wire and press the 

PRESS

  button. If the voltage  is 

lower

 than usual and the current is 

higher

 than usual you may have a short circuit. (see 

‘Checking  your  fence’)  The  fault  direction  arrows  will  light  when  the  Fault  Finder  calcu-
lates that the leakage (current) is worse (

higher

) than an acceptable value. 

2.  Follow the direction arrows towards the fault. Check the fence at regular intervals and at 

every side fence or intersection, also each side of joins and underground cables.   

3. 

If  the  Fault  Finder  shows  faults  in  more  than  one  fence  line  or  wire  ALWAYS  follow  the 
direction with the worst (

highest

) current reading. 

 

 

Note:  for  a  multiwire  fence  the  current  flow  will  be  seen  on  the  “feed”  wire  but  not  on  the 
“blind”  (dead-end) wires.

 

 
 

No 

current and

 no 

arrows means 

not

 ‘this way’ 

Reviews: