background image

11

www.juwent.com.pl

Before  connecting  the  unit,  check  the  electrical  system,  especially  the  electrical 

connections.

The unit may by operated only with proper connection with grounding wire.

Unit must be permanently connected to the electric installation equipped with protective 

(earth) terminal, residual current device and service switch.

The thermostat protecting the heater from overheating must be included in the heater 

control system.

It is forbidden to switch on the unit without working fan. Every stop of air flow have to 

disconnect the heater.

Voltage-free status can only be obtained by turning off the service switch.

Service switch disconnecting all power lines should be located near the unit.

Due to the structure the unit does not emit harmful radiation.

Although  the  unit  was  designed  and  manufactured  in  compliance  with  the  requirements  of  the 

standards, according to their state at the moment of production launch, a probability of injury or 

health loss when using the unit is not to be avoided. This probability is connected with a frequency of 

access to the unit in the course of its use, cleaning or repair, presence of persons within a dangerous 

zone, acting against the safety rules specified in the instruction manual.

The gravity of body injury or deterioration of health condition depends on many factors that often 

can be foreseen only partially, taking them into consideration in the structure of the unit, specifying 

them and warning against them in the instruction manual.

Therefore there is a 

residual risk

 when the operator does not observe the recommendations and 

guidelines included in the instruction manual.

8.  MOUNTING

The walls, ceilings or constructional elements of the object to which the unit supports or 

suspensions are fixed should have proper strength.

It should be consulted with the designer of the object.

The  bearing  structures  of  the  units  or  for  the  units  with  intake  boxes  can  be  freely 

designed observing the strength requirements.

When it is necessary to locate the unit by a partition, e.g. made of steel sheets, stiffening 

profiles  should  be  used  to  avoid  vibrations  of  the  partition  generated  by  the  unit 

operation and the noise level increase in the compartment.

Summary of Contents for TERM-E-18

Page 1: ...00 fax 48 81 883 56 09 POLAND I CONTACTS II ORIGINAL INSTRUCTION MANUAL III WARRANTY TERMS AND CONDITIONS IV UNIT STARTUP REPORT V INSPECTION AND MAINTENANCE DOCUMENT VI SERVICE NOTIFICATION VII LIST...

Page 2: ...com pl I CONTACTS Szyma ski Nowakowski General Partnership 31 Lubelska Str 08 500 Ryki phone 48 81 883 56 00 fax 48 81 883 56 09 POLAND Export department mob 48 502 087 841 mob 48 664 465 243 export j...

Page 3: ...3 www juwent com pl ELECTRIC HEATING AND VENTILATION UNITS TERM E II ORIGINAL INSTRUCTION MANUAL...

Page 4: ...DEVICE DESCRIPTION 5 4 TECHNICAL DATA 6 5 ADDITIONAL EQUIPMENT 8 6 TRANSPORT 10 7 SAFETY RECOMMENDATIONS 10 8 MOUNTING 11 9 WIRING SYSTEM 14 10 AUTOMATICS 15 11 DEVICE COMMISSIONING 16 12 REPAIR MAINT...

Page 5: ...tion unit TERM E 27 D Heating power 18 27 kW Equipment single row grid K slot diffuser N discharge cone D Marking of unit s optional automation AT RTA Supply and control box AT Additional elements tem...

Page 6: ...heaters in units Voltage V 400 400 Power kW 18 27 Current A 27 39 Noise level dB A At distance of 1m 61 63 At distance of 5m 57 59 Noise level sound pressure level at a distance of 1 and 5m taking acc...

Page 7: ...A x B mm x mm c x d mm x mm Ld mm TERM E 555 x 525 350 x 350 190 The units are supplied with the single row grid as a standard Grids have the movable blades enabling the air stream direction and reac...

Page 8: ...728 20 0 S net o shield The roof intakes are whole made of galvanized steel sheets ROOF BASE PD The roof bases are intended to install the roof intakes CD and intake boxes SC of the TERM units Unit s...

Page 9: ...ut 5 ADJUSTMENT RANGES OF INTAKE BOXES SC IN STANDARD VERSION The intake boxes SC in standard version are delivered for all TERM units with a constant recommended circulating air grid closing angle eq...

Page 10: ...foil against pollution and weather impacts The Product Manual is delivered along with the unit The intake boxes and wall intakes constitute additional equipment and they are delivered separately prote...

Page 11: ...ided This probability is connected with a frequency of access to the unit in the course of its use cleaning or repair presence of persons within a dangerous zone acting against the safety rules specif...

Page 12: ...suspension elements EZ A set of elements to suspend the unit includes angle sections fastened to the construction partition 2pcs channel sections to suspend the unit 6 pcs The wall unit can operate i...

Page 13: ...E 880 560 930 Support WWt intake box with filter TERM E 1030 560 930 CS wall intake SC intake box K flexible connector GW suspension set WW support set Ceiling units suspension on threaded bars Unit s...

Page 14: ...required distance of the unit with intake box for removal of filtration section is 70cm For ceiling units intake boxes should be screwed to the roof base The unit with flexible connector should be su...

Page 15: ...protect water heating coils against freezing Depending on control method for dampers actuators of the following types are used open close on off NE1 NE2 of continuous operation 0 10V NE3 NE4 Setting o...

Page 16: ...y on adjust direction and range of supply air flow using blades on the outlet grille To turn the unit off turn the fan electric motor supply off 12 REPAIR MAINTENANCE AND WITHDRAWAL FROM USE Rolling b...

Page 17: ...t minimum distance from the wall or ceiling is not maintained use distances recommended in the instruction manual improper revolution direction execute a proper electric connection improper parameters...

Page 18: ...damages and aleatory damages or damages caused by the atmospheric factors b damages occurred as a result of non observance of typical rules or the rules required by the instruction manual related to...

Page 19: ...p name and signature Motor current A User s representative stamp name and signature Remarks V INSPECTION AND MAINTENANCE DOCUMENT Date of inspection Executor of inspection stamp name and signature Ser...

Page 20: ...y No Year of production Startup executed by Description of defect NOTE AFTER COPYING AND FILLING IN SEND THE NOTIFICATION BY FAX OR EMAIL TOGETHER WITH A COPY OF THE STARTUP REPORT JUWENT Company acce...

Page 21: ...1 Axial fan with single phase motor 4 18 kW heat exchanger 5 27 kW heat exchanger List of subassemblies installed in additional equipment Lp Name of subassembly 1 Fresh air damper 2 Side damper 3 Actu...

Reviews: